Selecting a mounting location

Selecting a mounting location

Selecting a mounting location

Make sure that the location meets the operating environment require- ments and clearance requirements described in the following sections. The Tracer MP581 controller must be installed indoors. Trane recom- mends locating the Tracer MP581 controller in the same room (within 20 ft) of the controlled equipment to reduce wiring costs.

CAUTION

Equipment damage!

Install the Tracer MP581 in a location that is out of direct sunlight. Fail- ure to do so may cause the Tracer MP581 to overheat.

Operating environment requirements

Make sure that the operating environment conforms to the specifications listed in Table 14.

Table 14. Operating environment specifications

Temperature

From –40°F to 120°F (–40°C to 49°C)

Humidity

10–90% non-condensing

Altitude

6500 ft (2000 m)

High-voltage power

North America: 98–132 Vac, 1 A maximum, 1 phase

requirements

 

Weight

Mounting surface must be able to support 25 lb (12 kg)

 

 

BAS-APG001-EN

55