Trane Engineered Smoke Control System for Tracer Summit, BAS-APG001-EN I/O bus wiring example

Models: BAS-APG001-EN Engineered Smoke Control System for Tracer Summit

1 156
Download 156 pages 43.26 Kb
Page 103
Image 103
I/O bus wiring

I/O bus wiring

I/O bus wiring

The EX2 communicates with the Tracer MP581 and up to three other EX2 modules on an IEEE-485 link. This link must be a daisy chain. Typi- cally, the Tracer MP581 is at one end of the daisy chain, but any device can be at the ends of the link (Figure 48 and Figure 49 on page 92).

Wiring for the I/O bus must meet the following requirements:

All wiring must be in accordance with the National Electrical Code and local codes.

Recommended wire is low-capacitance, 22-gauge, Level 4, unshielded, twisted-pair. Existing sites that have already been wired with low- capacitance, 18-gauge, shielded, twisted pair with stranded, tinned- copper conductors (Trane-approved, purple-jacketed wire) don't have to be rewired. This shielded wire will work if properly terminated.

Total I/O wiring length cannot exceed 1000 ft (300 m).

At the first three modules, splice the shield with the shield from the next section of communication-link wiring, and tape the shield to pre- vent any connection to ground. At the final module on the end of the daisy chain, terminate the shield as shown in Figure 48. Note that you can use one, two, three, or four EX2 modules with each

Tracer MP581.

Figure 48. I/O bus wiring example 1

Tracer MP581

EX2

EX2

EX2

Up to 1000 ft (300 m)

EX2

BAS-APG001-EN

91

Page 103
Image 103
Trane Engineered Smoke Control System for Tracer Summit, BAS-APG001-EN manual I/O bus wiring example