Trane BAS-APG001-EN manual Network variable bindings, Function, Originator, Destination

Models: BAS-APG001-EN Engineered Smoke Control System for Tracer Summit

1 156
Download 156 pages 43.26 Kb
Page 136
Image 136
Originator

Chapter 8 Network variable bindings

In Table 31, the term multi-vibratoris used to indicate a network variable whose state is changed regularly. The receiver expects this value to change state within a certain interval. If it does not, a communication fault is generated. The term comm. status is used to indicate a network variable whose state is dependent on that particular MP581’s EX2 and BMTX communication status. If either are down, a communication fault is generated.

Table 31. Watchdog communication alarm custom bindings

Function

Originator

Network

Destination

variable

 

 

 

 

 

 

 

Communication check from hub

MP580-2

nvoSwitch36

Mechanical system/nviSwitch38

multi-vibrator

 

 

 

 

nvoSwitch36

MP580-3/nviSwitch38

 

 

 

 

 

 

 

 

nvoSwitch36

MP580-4/nviSwitch38

 

 

 

 

Communication check to hub

Mechanical system

nvoSwitch38

MP580-2/nviSwitch34

multi-vibrator

 

 

 

 

 

 

 

Communication check to hub:

MP580-3

nvoSwitch38

MP580-2/nviSwitch35

FSCP unit multi-vibrator

 

 

 

MP580-4

nvoSwitch38

MP580-2/nviSwitch36

 

 

 

 

 

BMTX/EX2 communication

Mechanical system

nvoSwitch39

MP580-2/nviSwitch37

check

 

 

 

 

 

 

 

BMTX/EX2 communication

MP580-3

nvoSwitch39

MP580-2/nviSwitch38

check to FSCP unit comm. status

 

 

 

MP580-4

nvoSwitch39

MP580-2/nviSwitch39

 

 

 

 

 