Trane BAS-APG001-EN manual UUKL binding list actuator Open/Close or, On/Off status

Models: BAS-APG001-EN Engineered Smoke Control System for Tracer Summit

1 156
Download 156 pages 43.26 Kb
Page 140
Image 140
UUKL binding list (actuator Open/Close or

Chapter 8 Network variable bindings

UUKL binding list (actuator Open/Close or

On/Off status)

Table 34 shows an example list of actuator status custom bindings. Actuator Open/Close or On/Off status is sent from the mechanical system directly to the FSCP.

Table 34. Actuator status custom bindings

Function

Originator

Network variable

Destination

 

 

 

 

supplyFanStatus

Mechanical system

nvoSwitch01

MP580-3/nviSwitch04

 

 

 

 

returnFanStatus

Mechanical system

nvoSwitch02

MP580-4/nviSwitch03

 

 

 

 

stairFanStatus

Mechanical system

nvoPercent01

MP580-2/nviPercent02

 

 

 

 

oaDamperStatus

Mechanical system

nvoPercent04

MP580-3/nviPercent01

 

 

 

 

raDamperStatus

Mechanical system

nvoPercent05

MP580-2/nviPercent01

 

 

 

 

eaDamperStatus

Mechanical system

nvoPercent06

MP580-4/nviPercent01

 

 

 

 

supplyDamperFloor01

Mechanical system

nvoPercent07

MP580-3/nviPercent02

 

 

 

 

returnDamperFloor01

Mechanical system

nvoPercent08

MP580-3/nviPercent03

 

 

 

 

supplyDamperFloor02

Mechanical system

nvoPercent09

MP580-3/nviPercent04

 

 

 

 

returnDamperFloor02

Mechanical system

nvoPercent10

MP580-3/nviPercent05

 

 

 

 

supplyDamperFloor03

Mechanical system

nvoPercent11

MP580-4/nviPercent02

 

 

 

 

returnDamperFloor03

Mechanical system

nvoPercent12

MP580-4/nviPercent03

 

 

 

 

supplyDamperFloor04

Mechanical system

nvoPercent13

MP580-4/nviPercent04

 

 

 

 

returnDamperFloor04

Mechanical system

nvoPercent14

MP580-4/nviPercent05

 

 

 

 

128

BAS-APG001-EN

Page 140
Image 140
Trane BAS-APG001-EN manual UUKL binding list actuator Open/Close or, On/Off status, Network variable bindings