Trane Engineered Smoke Control System for Tracer Summit manual Setting the I/O bus addresses

Models: BAS-APG001-EN Engineered Smoke Control System for Tracer Summit

1 156
Download 156 pages 43.26 Kb
Page 105
Image 105
Setting the I/O bus addresses

Setting the I/O bus addresses

Setting the I/O bus addresses

Each EX2 on the link with the Tracer MP581 must have a unique address. Configure the address using the DIP switches on the EX2 circuit board (Figure 50). Table 23 shows the DIP switch settings for expansion modules 1 through 4.

Figure 50. DIP switch on board

Table 23. EX2 DIP switch settings

EX2 module

D1

D2

 

 

 

1

Off

Off

 

 

 

2

Off

On

 

 

 

3

On

Off

 

 

 

4

On

On

 

 

 

Input/output terminal wiring

All input/output terminal wiring for the EX2 module must meet the fol- lowing requirements:

All wiring must be in accordance with the National Electrical Code and local codes.

Use only 18 AWG twisted-pair wire with stranded, tinned-copper conductors.

Binary output wiring must not exceed 20 ft (6.1 m) and must be in conduit.

Binary input wiring must not exceed 20 ft (6.1 m) and must be in conduit.

Analog and 24 Vdc output wiring distances depend on the specifica- tions of the receiving unit. Use shielding for analog and 24 Vdc outputs.

Do not run input/output wires in the same wire bundle with ac-power wires.

BAS-APG001-EN

93

Page 105
Image 105
Trane Engineered Smoke Control System for Tracer Summit manual Setting the I/O bus addresses, Input/output terminal wiring