Response times
Response times
Response times are a
Table 7. NFPA response time requirements
Component | Response time |
|
|
Damper operation to desired state | 75 seconds |
(open or closed) |
|
|
|
Fan operation to desired state | 60 seconds |
(on or off) |
|
|
|
Note:
Some building codes such as the Uniform Building Code have much more stringent response times. As with all of the considerations discussed in this chapter, the local authority having jurisdiction (AHJ) has the final word.
Cable distance considerations
Table 8 on page 30 given cabling distance requirements for data of two different types:
•Hardware based, such as from analog or binary inputs and outputs
•Communication based, such as from the Lontalk communication link or I/O bus (EX2)
The table also presents different cabling distance requirements depending on whether the data path is monitored or unmonitored.
There are no stated distance limitations for monitored information paths. The maximum distance allowed is the same as the manufacturer’s stated maximum distance for that particular data type. A data path is considered monitored if some notification for opens,
29 |