Chapter 7 Programming

information. A program fragment illustrating the collection process is shown in Figure 65.

Figure 65. Collection of Tracer and EX2 communication status at an individual MP581

Figure 65 also shows that each MP581 in the smoke control system should send back its won watchdog signal to the main FSCP control MP581.

At the main FSCP control MP581, all the communication status signals are collected together to determine overall communication status. Figure 66 on page 115 shows a TGP sample of the programming. Each MP581 in the smoke control system sends its own watchdog signal, its Tracer Summit communication status, and its EX-2 module communication status. In addition, the main FSCP control MP581 will have its own Tracer Summit communication status and EX-2 module communication to determine and add to the calculation. The Comm Fault LED should indicate if any communication link in the system is not working correctly.

114

BAS-APG001-EN