Methods of smoke control
Figure 1: Sample pressure difference across a barrier
Table 1 provides the National Fire Protection Association (NFPA) recommended minimum pressure difference between the
Table 1: Recommended minimum pressure difference
|
| Minimum pressure |
| Ceiling height | difference |
Building type | (ft [m]) | (In.w.c. [Pa]) |
|
|
|
Sprinklered | Any | 0.05 (12.4) |
|
|
|
9 (2.7) | 0.10 (24.9) | |
|
|
|
15 (4.6) | 0.14 (34.8) | |
|
|
|
21 (6.4) | 0.18 (44.8) | |
|
|
|
Notes:
• The minimum pressure difference column provides the pressure difference between the high pressure side and the
• The minimum pressure difference values incorporate the pressure induced by the buoyancy of hot smoke.
• A smoke control system should maintain the minimum pressure differences regardless of stack effect and wind.
• The minimum pressure difference values are based on recommendations in NFPA 92A (NFPA 2000, Recommended Practice for Smoke Control Systems).
• In.w.c. is inches of water column.
• Pa is Pascals.
Table 2 on page 4 provides the NFPA recommended maximum allowable pressure difference across doors. The listed pressure differences take into account the door closer force and door width.
3 |