Smoke alarm annunciation

Smoke alarm annunciation

Smoke alarm annunciation

Systems serving two or more zones shall visually identify the zone of origin of the status change (UL-864: 33.2.1). The visual annunciation shall be capable of displaying all zones having a status change (UL-864: 33.2.2). These requirements are interpreted to mean that any smoke zone alarm is annunciated by the smoke control panel regardless of alarm order. If any smoke zone alarm is triggered, the alarm state is sent to MP580 controllers that interface with and control the smoke control panel. Figure 54 illustrates a means of programming to meet requirements 33.2.1 and 33.2.2. An additional value, smokeAlarmAny, is broadcast as a means to provide information for priority-based decisions (see Table 28 on page 101).

Figure 54. Smoke alarm annunciation

BAS-APG001-EN

103

Page 115
Image 115