Trane Engineered Smoke Control System for Tracer Summit Smoke detection and system activation

Models: BAS-APG001-EN Engineered Smoke Control System for Tracer Summit

1 156
Download 156 pages 43.26 Kb
Page 25
Image 25
Smoke detection and system activation

Smoke detection and system activation

Zoned smoke control detection and activation

Zoned smoke control activation occurs on a signal from either a sprinkler water flow switch or a heat detector. For maximum benefit, the zoned smoke control system should only respond to the first alarm. Two design techniques that prevent detection of smoke in zones other than the first zone reporting are:

Not activating smoke control on smoke detector signals

Activating smoke control on signals from two separate smoke detectors located in the same zone

Note:

Zoned smoke control should not activate on a signal from a manual pull station (pull box). If pull box activation does not occur in the zone that contains the fire, activation incorrectly identifies the smoke zone.

Stairwell smoke control detection and activation

Stairwell smoke control activation occurs on an alarm signal from any device, including sprinkler water flow switches, heat detectors, smoke detectors, and manual pull stations (pull boxes). Most stairwell smoke control systems operate in the same manner regardless of the source of the alarm signal.

Elevator smoke control detection and activation

Elevator smoke control activation occurs on an alarm signal from any device, including sprinkler water flow switches, heat detectors, smoke detectors, and manual pull stations (pull boxes). Most elevator smoke control systems operate in the same manner regardless of the source of the alarm signal.

Note:

The description of elevator smoke control detection and activation does not apply to pressurization systems for elevators intended for occupant evacuation.

Atrium smoke exhausting detection and activation

Atrium smoke exhausting activation occurs on a signal from a beam smoke detector. A beam smoke detector consists of a light beam transmitter and a light beam sensor. Typically, the transmitter and the sensor are located apart from each other. However, when located together, the transmitter sends its beam to the opposite side of the atrium. At the opposite side, the beam reflects back to the sensor.

Note:

Atrium smoke control should not activate on a signal from a manual pull station (pull box). Atrium smoke exhaust systems have different operating modes depending on fire location.

BAS-APG001-EN

13

Page 25
Image 25
Trane Engineered Smoke Control System for Tracer Summit, BAS-APG001-EN manual Zoned smoke control detection and activation