Trane Engineered Smoke Control System for Tracer Summit manual BAS-APG001-EN

Models: BAS-APG001-EN Engineered Smoke Control System for Tracer Summit

1 156
Download 156 pages 43.26 Kb
Page 63
Image 63
Manual background

Transtector, Ethernet (UUKL nondedicated only), and LonTalk connections on the BMTX BCU

Transtector, Ethernet (UUKL nondedicated only), and LonTalk connections on the BMTX BCU

To comply with UUKL, a protection device must be wired to the BMTX BCU to reduce transients in the ac power. Figure 24 describes connecting an ac power transient protection device to a BMTX BCU.

Figure 24. AC power transient protection wiring to the BMTX BCU

BAS-APG001-EN

51

Page 63
Image 63
Trane Engineered Smoke Control System for Tracer Summit manual BAS-APG001-EN