Trane Engineered Smoke Control System for Tracer Summit manual Lamp test and audio alarm silence

Models: BAS-APG001-EN Engineered Smoke Control System for Tracer Summit

1 156
Download 156 pages 43.26 Kb
Page 129
Image 129
Lamp test and audio alarm silence

Lamp test and audio alarm silence

Triggering a lamp test affects all LEDs on the smoke control panel. Figure 69 shows an example of how to use the lamp test signal in combination with any smoke alarm information.

Note:

Note that the lamp test is not allowed to start or run if there is a smoke alarm.

Figure 69. Example of lamp test controlling FSCP damper LEDs

BAS-APG001-EN

117

Page 129
Image 129
Trane Engineered Smoke Control System for Tracer Summit manual Lamp test and audio alarm silence, BAS-APG001-EN