Custom bindings
UUKL binding list (actuator failure status)
Table 35 shows an example list of actuator failure status bindings.
Actuator failure status is sent directly from the mechanical system to the
FSCP.
Table 35. Actuator failure status bindings
Function | Originator | Network variable | Destination |
|
|
|
|
supplyFanFail | Mechanical system | nvoSwitch20 | |
|
|
|
|
returnFanFail | Mechanical system | nvoSwitch21 | |
|
|
|
|
oadamperFail | Mechanical system | nvoSwitch22 | |
|
|
|
|
radamperFail | Mechanical system | nvoSwitch23 | |
|
|
|
|
eadamperFail | Mechanical system | nvoSwitch24 | |
|
|
|
|
stairFanFail | Mechanical system | nvoSwitch25 | |
|
|
|
|
supplyDamperFloor01Fail | Mechanical system | nvoSwitch26 | |
|
|
|
|
returnDamperFloor01Fail | Mechanical system | nvoSwitch27 | |
|
|
|
|
supplyDamperFloor02Fail | Mechanical system | nvoSwitch28 | |
|
|
|
|
returnDamperFloor02Fail | Mechanical system | nvoSwitch29 | |
|
|
|
|
supplyDamperFloor03Fail | Mechanical system | nvoSwitch30 | |
|
|
|
|
returnDamperFloor03Fail | Mechanical system | nvoSwitch31 | |
|
|
|
|
supplyDamperFloor04Fail | Mechanical system | nvoSwitch32 | |
|
|
|
|
returnDamperFloor04Fail | Mechanical system | nvoSwitch33 | |
|
|
|
|
checkSupervisedCircuits | Mechanical system | nvoSwitch40 | |
|
|
|
|
UUKL binding list (FSCP control)
Table 36 shows an example list of smoke control panel control custom bindings. Smoke control panel commands affect all MP581s panel control units.
Table 36. Smoke control panel control custom bindings
Function | Originator | Network variable | Destination |
|
|
|
|
lampTest | nvoSwitch01 | ||
|
|
|
|
|
| nvoSwitch01 | |
|
|
|
|
panel enable/disable | nvoSwitch03 | ||
|
|
|
|
|
| nvoSwitch03 | |
|
|
|
|