Models: BAS-APG001-EN Engineered Smoke Control System for Tracer Summit

1 156
Download 156 pages 43.26 Kb
Page 141
Image 141
UUKL binding list (actuator failure status)

Custom bindings

UUKL binding list (actuator failure status)

Table 35 shows an example list of actuator failure status bindings.

Actuator failure status is sent directly from the mechanical system to the

FSCP.

Table 35. Actuator failure status bindings

Function

Originator

Network variable

Destination

 

 

 

 

supplyFanFail

Mechanical system

nvoSwitch20

MP580-3/nviSwitch05

 

 

 

 

returnFanFail

Mechanical system

nvoSwitch21

MP580-4/nviSwitch04

 

 

 

 

oadamperFail

Mechanical system

nvoSwitch22

MP580-3/nviSwitch03

 

 

 

 

radamperFail

Mechanical system

nvoSwitch23

MP580-2/nviSwitch01

 

 

 

 

eadamperFail

Mechanical system

nvoSwitch24

MP580-4/nviSwitch02

 

 

 

 

stairFanFail

Mechanical system

nvoSwitch25

MP580-2/nviSwitch02

 

 

 

 

supplyDamperFloor01Fail

Mechanical system

nvoSwitch26

MP580-3/nviSwitch07

 

 

 

 

returnDamperFloor01Fail

Mechanical system

nvoSwitch27

MP580-3/nviSwitch08

 

 

 

 

supplyDamperFloor02Fail

Mechanical system

nvoSwitch28

MP580-3/nviSwitch10

 

 

 

 

returnDamperFloor02Fail

Mechanical system

nvoSwitch29

MP580-3/nviSwitch11

 

 

 

 

supplyDamperFloor03Fail

Mechanical system

nvoSwitch30

MP580-4/nviSwitch06

 

 

 

 

returnDamperFloor03Fail

Mechanical system

nvoSwitch31

MP580-4/nviSwitch07

 

 

 

 

supplyDamperFloor04Fail

Mechanical system

nvoSwitch32

MP580-4/nviSwitch09

 

 

 

 

returnDamperFloor04Fail

Mechanical system

nvoSwitch33

MP580-4/nviSwitch10

 

 

 

 

checkSupervisedCircuits

Mechanical system

nvoSwitch40

MP580-2/nviSwitch04

 

 

 

 

UUKL binding list (FSCP control)

Table 36 shows an example list of smoke control panel control custom bindings. Smoke control panel commands affect all MP581s panel control units.

Table 36. Smoke control panel control custom bindings

Function

Originator

Network variable

Destination

 

 

 

 

lampTest

MP580-2

nvoSwitch01

MP580-3/nviSwitch40

 

 

 

 

 

 

nvoSwitch01

MP580-4/nviSwitch40

 

 

 

 

panel enable/disable

MP580-2

nvoSwitch03

MP580-3/nviSwitch36

 

 

 

 

 

 

nvoSwitch03

MP580-4/nviSwitch36

 

 

 

 