Trane Engineered Smoke Control System for Tracer Summit manual Wiring high-voltageac power

Models: BAS-APG001-EN Engineered Smoke Control System for Tracer Summit

1 156
Download 156 pages 43.26 Kb
Page 55
Image 55
Wiring high-voltage ac power

Wiring high-voltage ac power

2.Set the enclosure back aside and drill holes for the screws at the marked locations.

Drill holes for #10 (5 mm) screws or #10 wall anchors. Use wall anchors if the mounting surface is dry wall or masonry.

3.Insert wall anchors if needed.

4.Secure the enclosure back to the mounting surface with the supplied #10 (5 mm) screws.

Wiring high-voltage ac power

Verifying model number for local power requirements

Table 12 lists the available BMTX BCU model. You can find the model number on the shipping label or on the product label inside the enclosure.

Table 12. BMTX BCU model number

Model

Description

BMTX001DAB000

BMTX BCU, 120 Vac, UUKL listed

To ensure proper operation of the BMTX BCU, install the power supply circuit in accordance with the following guidelines:

The BCU must receive power from a dedicated power circuit. Failure to comply may cause control malfunctions.

A disconnect switch for the dedicated power circuit must be near the controller, within easy reach of the operator, and marked as the dis- connecting device for the controller.

High-voltage power-wire conduits or wire bundles must not contain input/output wires. Failure to comply may cause the controller to mal- function due to electrical noise.

High-voltage power wiring must comply with the National Electrical Code (NEC) and applicable local electrical codes.

High-voltage wiring requires three-wire 120/230 Vac service (line, neutral, ground).

Note:

The transformer voltage utilization range is 120 Vac. The panel automatically detects whether the current is 50 or 60 cycle.

To connect high-voltage power wires:

￿WARNING

Hazardous voltage!

Before making electrical connections, lock open the supply-power dis- connect switch. Failure to do so may cause death or serious injury.

BAS-APG001-EN

43