Trane BAS-APG001-EN manual Nondedicated smoke purge, Programming, Controlling damper actuators

Models: BAS-APG001-EN Engineered Smoke Control System for Tracer Summit

1 156
Download 156 pages 43.26 Kb
Page 130
Image 130
Nondedicated smoke purge

Chapter 7 Programming

Nondedicated smoke purge

(UL-864: 3.21.h)

The term nondedicated refers to a system that provides the building’s HVAC functioning under normal conditions and a smoke control objective during a fire alarm condition.

The main concern when designing a nondedicated system is for programming to ensure that, once a smoke alarm or FSCP override occurs, any component of the smoke control system is controlled solely by automatic smoke control or manual override commands. For details regarding priority, see Table 28 on page 101.

Figure 70 shows an example of programming for a nondedicated system to implement the priorities in Table 28. In this figure, the smoke control dampers for Floor 1 are controlled. The actuator position, either Open or Closed, will default to whatever the HVAC system commands. There are two states that will turn control over to either automatic smoke control or FSCP overrides:

If the broadcast general smoke alarm is TRUE, or

If the FSCP override switch is set to either Open or Closed.

Figure 70. Implementing priorities for a nondedicated system:

Controlling damper actuators

118

BAS-APG001-EN

Page 130
Image 130
Trane BAS-APG001-EN manual Nondedicated smoke purge, Programming, Controlling damper actuators