Use copper conductors only!

Chapter 4 Installing the Tracer Summit BMTX BCU

CAUTION

Use copper conductors only!

Unit terminals are designed to accept copper conductors only. Other conductors may cause equipment damage.

1.Lock open the supply-power disconnect switch.

2.At the top-right corner of the enclosure, remove the knockout for ½ in (13 mm) conduit.

3.Open or remove the enclosure door if it has already installed.

4.Inside of the enclosure at the top-right corner, remove the high-volt- age area cover plate.

5.Feed the high-voltage power wire into the enclosure.

6.Connect the line wire to the L terminal as shown in Figure 19 on page 45.

7.Connect the neutral wire to the N terminal.

8.Connect the green ground wire to the chassis ground screw. The ground wire must be continuous back to the circuit breaker panel.

9.Replace the cover plate.

￿WARNING

Hazardous voltage!

The cover plate must be in place when the BCU is operating. Failure to replace the cover plate could result in death or serious injury.

10.On a label, record the location of the circuit breaker panel and the electrical circuit. Attach the label to the cover plate.