Tracer MP581 to FACP wiring

System termination diagrams

Tracer MP581 to FACP wiring

The wiring between the Tracer MP581 and the FACP is non-supervised and power limited. In addition:

Tracer MP581 and FACP must be in the same room.

Wiring between the Tracer MP581 and FACP must be in conduit.

Wiring distance cannot exceed 20 ft.

Wire must be #18 AWG.

The number of wires needed between the Tracer MP581(s) and the FACP is determined by the total number of zones in the fire alarm system. Multiple Tracer MP581 panels may be required to monitor and control the FACP.

Table 10 gives wiring information for a typical Tracer MP581 that communicates to an FACP.

Figure 15 on page 38 shows the details for wiring a Tracer MP581 to an FACP.

Table 10. Wiring for a typical Tracer MP581 that communicates to an

FACP

Cables

Type of

 

per Tracer

Function

wiring

MP581

 

 

 

1–36

22 Vdc

Two binary input wires per FSCS switch

 

 

(up to 36 per Tracer MP581)

 

 

 

1

22 Vdc

Common

 

 

 