Trane Engineered Smoke Control System for Tracer Summit manual System termination diagrams

Models: BAS-APG001-EN Engineered Smoke Control System for Tracer Summit

1 156
Download 156 pages 43.26 Kb
Page 45
Image 45
System termination diagrams

System termination diagrams

System termination diagrams

System termination diagrams show wire terminations at panels and field devices. Guidelines for creating system termination diagrams include:

Diagrams for Tracer MP581 panels may be formatted as lists.

Diagrams for field devices show: normal state, expected operation, and voltage requirements. An example of a normal state notation is normally open. An example of an expected operation description is closed contact opens damper.

Diagrams for field devices not furnished by Trane are created during installation. After installation, the diagrams become part of the as- built documentation.

Diagrams for the control of starters and variable flow devices (VFDs) must show the required relays and connections for the hierarchy of control (Figure 12 on page 33). Relays must enable starters and VFDs to bypass some safety devices and the local manual switches. Also, manual controls from the firefighter’s smoke control station (FSCS) must be wired to give them the highest priority of control.

Figure 12. Sample fan starter wiring diagram

Note: Pressure cutouts, duct smoke detectors and auto shutdown are two-pole.

BAS-APG001-EN

33

Page 45
Image 45
Trane Engineered Smoke Control System for Tracer Summit System termination diagrams, Sample fan starter wiring diagram