Trane BAS-APG001-EN manual Equipment supervision, Tracer MP581 programmable controller

Models: BAS-APG001-EN Engineered Smoke Control System for Tracer Summit

1 156
Download 156 pages 43.26 Kb
Page 38
Image 38
Tracer MP581 programmable controller

Chapter 2 Pre-installation considerations

and dampers: status switches, differential pressure switches, airflow paddle switches, current-sensing relays, limit switches, and end switches.

Status switches at fans and dampers monitor the operation of the devices. Multiple binary inputs at the Tracer MP581s verify the On and Off status of fans and the Open and Closed status of dampers. If a status switch does not confirm the commanded (automatic or manual) operation, a Fail indicator activates at the FSCS. Failure detection must incorporate a time delay to give the devices time to function.

Differential pressure switches, airflow paddle switches, and current- sensing relays monitor fan operations. Differential switches piped across fan and paddle switches in the air stream can give erroneous indications.

IMPORTANT

A current-sensing relay is the preferred way to confirm the operating status of a fan.

Limit switches and end switches monitor dampers. The switches activate damper Open and Closed signals for the FSCS. The damper blades activate the switches. Some codes require two switches in order to sense both the fully opened and fully closed position of the damper.

Tracer MP581 programmable controller

The Tracer MP581 must have multiple binary inputs to verify the On and Off operation of fans. It must also have multiple binary inputs to verify the Open and Closed positions of dampers.

Equipment supervision

Equipment supervision is a pre-installation consideration. Smoke control equipment must be supervised to ensure it is operational. Supervision techniques consist of confirming communications among system control panels, confirming operation in normal use situations, and performing weekly self-tests.

Confirming communications among all system control panels is a supervision technique that monitors basic system integrity. If any panel loses its communications, a Trouble alert is sent to the FSCS.

Normal use operations confirm the integrity of field point wiring for nondedicated equipment. Nondedicated equipment provides conditioned air to the building daily. When nondedicated equipment is not operational, comfort conditions deteriorate and building tenants notify maintenance personnel.

26

BAS-APG001-EN

Page 38
Image 38
Trane BAS-APG001-EN manual Equipment supervision, Tracer MP581 programmable controller, Pre-installationconsiderations