SMC Networks 5000 manual Section A.1 Example Counterbalance Configuration

Page 53

Appendix A Configuration Examples

This section of the manual will go though an example setup of each kind of system on a “typical” press. Each example assumes that the hardware installation has been completed and the system is ready for configuration.

The following examples assume the access system is using “Key Only” mode as described in section 2. Other modes may require entering a user code to change certain parameters.

Section A.1 Example Counterbalance Configuration

This example assumes the counterbalance system has been wired to the option board at “AS1". First, some information needs to be gathered.

From the press counterbalance table mounted on the frame of the machine (or found in the press manual), we find that at zero die weight, the counterbalance pressure should be 25 psi. The maximum upper die weight for our example press is 7500 pounds. At that weight, the table says the pressure should be 78 psi.

The pressure transducer installed on the system is a Setra model C206 that has a pressure range of 0 to 250 psi and an output of 4 to 20 ma.

A type “C” integrated valve controls the pressure (see section 3.1 for a discussion of valve types).

Now we go to the “Auto Sets” screen and with the RUN/PROG switch in PROG hit the “CONFIGURE” softkey. After typing the configuration code, we press the “CONFIGURE AIR” softkey.

Since the counterbalance is wired in at “AS1", if the slot reported on the screen in not already “AS1", we hit the “NEXT AIR SLOT” softkey until it is. The hardware detected should be “Fill/Dump”.

The first thing we must configure is the “Name” of the system. The cursor should already be on the “Name” line so we check to see if the name is already “Counter-Balance #1". If not, place the editing cursor on the name and press the “CHANGE NAME” softkey to cycle through the systems.

Using the arrow keys, we move the editing cursor to the “Transducer Type” line. Looking at table 4.1, we see that the transducer type for any model pressure transducer with a 250 psi pressure range and a 4 to 20 ma output is “Type 3” . We hit the “CHANGE TYPE” softkey and select Type 3 from the list that appears. When the proper type is selected, the “Air Pressure” line should change to read the pressure currently in the counterbalance system.

Next we use the arrow keys to move the editing cursor to the “Maximum Pressure” line. Since we found earlier that the pressure used to balance the heaviest die the press supports is 78 psi, we hit the “CHANGE MAX PRES” softkey and key in this value.

Going to the “Minimum Pressure” line, we enter in 25 psi, the value that balances only the slide.

Next, “Max. Die Weight” is entered as 7500, the weight counterbalanced at the maximum air pressure.

April 17, 2000 Man ual Versio n 1.0

A.1

Image 53
Contents OmniLink Table of Contents April 17, 2000 Man ual Versio n Iii April 17, 2000 Man ual Versio n Cushion Control Section IntroductionCounterbalance Control Hydraulic Overload Control Shut Height Control2 Text Entry Parameter Entry and Access Control1 Numeric Entries April 17, 2000 Man ual Versio n 2 Key or Password Mode Access Control1 Key Only Mode 4 Key and Password Mode 3 Password Only Mode6 Access Control Operation 6.1 RUN/PROG Key Switch OperationExample Password Entry Sequence 6.2 Password System OperationApril 17, 2000 Man ual Versio n Installation Auto-Setup Module Installation April 17, 2000 Man ual Versio n Valve Systems Type B Valve ConfigurationCounterbalance Control Installation Type C Valve ConfigurationAuto-Counterbalance with Type a Integrated Valve 1 Counterbalance Pressure Transducer Mounting 2 Counterbalance Air Valve System Mounting 3 Counterbalance System WiringCushion System Installation 2 Cushion Air Valve System Mounting 3 Cushion System Wiring1 Cushion Pressure Transducer Mounting 1 Rotary Transducer Mounting Hydraulic Overload System InstallationSlide Adjust System Installation 3 Linear Transducer Mounting 2 Rotary Slide Adjust Wiring4 Linear Transducer Slide Adjust Wiring Setting up the OmniLink 5000 for the Auto-Setup Module ConfigurationExample Air Configuration Screen Configuring the Auto-Setup boardAir Slot HelpHardware Detected Air PressureMax. Die Weight Regulator settingMin. Die Weight Display Weight AsMin. Cushion Force Max. Cushion ForceDisplay Force As Max. Trip PointTolerance Fault TimeTransducer Types Valve Type2 Configuring Slide Adjust Modules Shut Height Units Slide SlotShutheight Lower Limit Upper LimitPulse Distance Pulse TimeSerious injury or death 2.1 Calibrating Linear Slide Adjust SystemsLock Time Or death 2.2 Calibrating Rotary Slide Adjust SystemsResolver Turns System may fail to calibrateApril 17, 2000 Man ual Versio n April 17, 2000 Man ual Versio n Section Operation April 17, 2000 Man ual Versio n Actual Position Slide Adjust OperationSetpoint 1 Slide On, Manual, and Off Settings FaultStatus MAN manualApril 17, 2000 Man ual Versio n Die Weight Set 4 Slide Fault and Status3 Manual Slide Movement Pressure SetPress Trip Set 1 Air System On, Manual, and Off SettingsActual Pressure 2 Pressure and Force SetpointsJob Storage and Recall Issues 3 Air System Fault and StatusApril 17, 2000 Man ual Versio n Main Module Messages Diagnostics Fault and Status MessagesUnable to Fill Pressure Switch LowUnable to Dump Max. Press. ExceededSlide Adjust Fault Messages Slide Adjust Status Messages Waiting S/A Switch Auto-AdjustingMin Position Reached Moving UpSection A.1 Example Counterbalance Configuration Section A.2 Example Cushion Configuration Section A.3 Example Hydraulic Overload Configuration April 17, 2000 Man ual Versio n Section A.4 Example Linear Slide Adjust Configuration April 17, 2000 Man ual Versio n Section A.5 Example Rotary Slide Adjust Configuration April 17, 2000 Man ual Versio n April 17, 2000 Man ual Versio n Figure B.1 Typical Counterbalance Wiring Diagram Appendix B Typical Wiring DiagramsFigure B.2 Typical Cushion Wiring Diagram Figure B.3 Conceptual Dual Resolver Mounting Figure B.4 Typical Amci Dual Resolver Wiring Diagram Figure B.5 Typical Gemco Dual Resolver Wiring Diagram Figure B.6 Conceptual Linear Transducer Mounting Figure B.7 Typical Gemco Linear Transducer Wiring April 17, 2000 Man ual Versio n Figure B.11 Typical Slide Air Motor Solenoid Wiring April 17, 2000 Man ual Versio n Figure C.1 Logic Module Firmware Chip Locations Appendix C Installation Of OmniLink 5000 FirmwareApril 17, 2000 Man ual Versio n Must be done even if a LOX valve is opened in since Section D.2 Valve Type a Lockout ProcedurePower is on Section D.4 Valve Type C Lockout Procedure Section D.3 Valve Type B Lockout ProcedureApril 17, 2000 Man ual Versio n April 17, 2000 Man ual Versio n Section E.2 Shut height Calibration Sheets April 17, 2000 Man ual Versio n Section F.3 5000-10C Rotary Shut Height Control Board Section F.2 5000-10B Linear Shut Height Control Board

5000 specifications

SMC Networks 5000 is a robust and versatile networking solution designed to meet the demands of modern digital infrastructures. This device is a part of SMC Networks' extensive product lineup, which caters to both enterprise and small to medium-sized businesses. The SMC 5000 stands out due to its high performance, reliability, and advanced feature set.

One of the key features of the SMC Networks 5000 is its high-speed connectivity. It supports multiple Gigabit Ethernet ports, allowing for fast data transfer and seamless connectivity. This makes it ideal for environments where bandwidth is critical, such as in data centers, large office environments, and educational institutions. The device also includes advanced traffic management capabilities, ensuring efficient data flow and minimizing latency.

Another impressive characteristic of the SMC 5000 is its scalability. As organizations grow and their networking needs evolve, the SMC 5000 can adapt accordingly. It supports a modular design, allowing users to add or remove components based on their specific requirements. This flexibility enables businesses to optimize their network setup without the need for a complete overhaul.

Security is a top priority for SMC Networks, and the 5000 model incorporates advanced security features to protect sensitive data. With built-in firewalls, virtual private network (VPN) support, and robust encryption protocols, the device ensures that unauthorized access is prevented. This is particularly crucial in today’s digital landscape, where cyber threats are increasingly sophisticated.

In terms of management and monitoring, the SMC 5000 offers a user-friendly interface that simplifies network administration. Administrators can easily configure settings, monitor performance metrics, and troubleshoot issues through a centralized dashboard. This streamlines network management tasks and enhances overall efficiency.

The SMC Networks 5000 is also compatible with various networking technologies, including VLAN (Virtual Local Area Network) support, QoS (Quality of Service) features, and IPv6 readiness. These technologies contribute to a more efficient network setup and pave the way for future-proofing as networking standards evolve.

Overall, the SMC Networks 5000 is a reliable and powerful networking solution that provides the performance, security, and scalability necessary for today's demanding network environments. Its combination of advanced features and user-friendly management options makes it an excellent choice for businesses looking to enhance their networking infrastructure. With SMC Networks 5000, organizations can ensure seamless connectivity while effectively managing their growing digital demands.