Premier Floors manual Panel Core

Page 44
Manual background
Maximum Floor Span Maximum Roof Span

44

Panel Core

Deflection

 

 

 

 

Panel Span (ft.)

 

 

 

 

Thickness

 

 

 

 

 

 

 

 

 

 

 

4’

8’

10’

12’

14’

16’

18’

20’

22’

24’

 

 

 

 

 

 

 

 

 

 

 

 

 

L/360

132

136

93

60

48

40

29

21

 

 

7 1/4”

 

 

 

 

 

 

 

 

 

 

 

L/240

318*

148*

107*

91

70

54

42

31

NA

NA

 

 

 

 

 

 

 

 

 

 

 

 

 

L/180

318*

148*

107*

92*

85

54

48

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9 1/4”

L/360

197

164*

124*

72

66

61

48

34

29

24

 

 

 

 

 

 

 

 

 

 

 

L/240

318*

164*

124*

107*

96*

84*

70

49

43

36

 

 

 

 

 

 

 

 

 

 

 

 

 

L/180

318*

164*

124*

107*

96*

84*

76*

65

56

47

 

 

 

 

 

 

 

 

 

 

 

 

 

L/360

258

143*

103*

86

83

77*

61

42

37

31

11 1/4”

 

 

 

 

 

 

 

 

 

 

 

L/240

318*

143*

103*

93*

85*

77*

68*

59*

54*

47

 

 

 

 

 

 

 

 

 

 

 

 

 

L/180

318*

143*

103*

93*

85*

77*

68*

59*

54*

49*

 

 

 

 

 

 

 

 

 

 

 

 

* indicates ultimate load divided by 3 for the design capacity. 4’ span is a minimum two span condition.

Panels require a minimum of 1-1/2” bearing. I-Joist splines are spaced 4’ o.c.

Floor panels should have a 3/4” minimum top skin or a 7/16” top skin overlayed with 7/16” finish flooring perpendicular to the panels.

More information on this chart can be found in Technical Bulletin #13 (www.pbssips.com). Refer to Technical Bulletin #21 for floor applications (www.pbssips.com).

Transverse Load Chart 5:

Premier SIPs Type I (I-Joist)

Transverse Load Chart (psf)

Image 44
Contents installation guide Introduction Table of Contents PBS SIPs Tips Do not put plumbing inside SIPs Fill all voids with expanding foamStorage & Handling Checklist of Tools Spline Connection Lumber Connection I-JoistConnection Panel Basics - Assembly Fasteners Field FabricationPage Field Fabrication Rake/Gable Walls Floors Page PANEL TIP Stagger your panel placement with two panels on one side of the beam, four panels on the other side, and four back on the first side of the beam. This will help your beam stay straight Sill Plates Page Walls STEP 2. LAYOUT TRANSFER STEP 3. PANEL TILTSTEP 4. ADJACENT PANEL STEP 5. FASTENING STEP 6. TOP PLATEHeaders Page Intermediate Floors Page Roofs On the Ground Lifting PanelsPage Page Insul-Lam Electrical Where walls terminate against a panel you can drill at the horizontal electricalPlumbing Shearwalls Premier Panel R-Values Panel Core Panel Core Panel Span ft Panel Core Panel Core Panel Core Panel Core Load Chart Header Header Insul-BeamII Header LoadsPremier Load ChartNo. of Panel Panel Minimum Speed Pressure Chart 1 ofLoad Chart 12 Wind Speed Pressure Chart 2 ofLoad Chart 12 Wind Page REGIONAL FIELD OFFICES NORTHWEST 4609 70th Ave. East Fife, WASOUTHWEST 3434 W. Papago St. Phoenix, AZ