Balcar R410A service manual 177, Address No. setup table SW01, Procedure

Page 101

Setup of the Address No.

To connect the indoor unit to the central remote controller using the adapter, it is necessary to set up the network address No.

It is required to agree the network address No. with the central remote controller system No.

The network address No. is set to 1 at the shipment from the factory.

The following two methods are used for setup.

1.Setup from the remote controller at the indoor unit side

• This method is available only when [7] of the setup switch SW01 on the adapter P.C. board is OFF.

<Procedure> Set up the address No. while the air conditioner stops.

1 Push and buttons for 4 seconds or more.

In case of the group control, the unit No. ALL is displayed, and then all the indoor units in the group control are selected. (Fig. 1)

In this time, the fans of all the selected indoor units start and the swing operation also starts in the models with flaps. (Keep the display status of ALL without pushing UNIT button.)

In case of individual remote controller with no group control, the system address and the indoor unit address are displayed.

Address No. setup table (SW01)

Address No.

01

02

03

04

05

06

07

08

09

10

11

12

13

14

15

(Table 2)

: ON side, : OFF side

Address No.

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

– 177 –

2 Using / buttons, specify the item code 03.

3 Using buttons, select the setup data.

The following table shows the setup data. (Table 1)

4 Push SET button.

(When the display goes on, the setup data is accepted.)

To change the setup item, return to the step 2 .

5 Push button. The status returns to the normal stop status.

 

(Table 1)

 

 

Setup data

Network address No.

0001

1

0002

2

0003

3

0064

64

0099

No setting (Shipment from the factory.)

 

 

1

5

(Fig. 1)

CODE No.

SET DATA

UNIT No.

R.C. No.

 

UNIT

2

SET CL

 

4 3

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

48

49

50

51

52

53

54

55

56

57

58

59

60

61

62

63

64

2. Setup by the switch on the adapter P.C. board

Requirement in Service Time

When the remote controller is not found, or when you do not want to change the setup of network address No. on the remote controller, set up the address No. by using the setup switch SW01 (Network address No. setup switch) on the adapter P.C. board.

When using this product as the service part for change of the adapter P.C. board, be sure to set the setup switch SW01 (Network address No. setup switch) on the adapter P.C. board so that it is same as one before change.

<Procedure>

1 Turn off the power supply.

2 Set [7] of the address No. setup switch SW01 to ON side.

Address No. setup on the remote controller is invalid.

Accordingly, the setup of the address No. from the remote controller is invalidated. (Fig. 2)

3 The network address No. is set up by com- bining ON/OFF of the address No. setup switch, from SW01 [6] to [1].

For the relation between ON/OFF combination and the address No., see (Table 2).

A case when the address No. is set to 16 is

SW01

1 2 3 4 5 6 7

Address No. setup

Setup example (Address No. 16)

ON side

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON side

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF side

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF side

(Numeral side)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Numeral side)

1

2

3

4

5

6

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TCB

shown in (Fig. 3).

(Fig. 2)

(Fig. 3)

-PCNT20E

When the network address No. has been changed, turn on the power of the central remote controller again or reset the central remote controller from the reset hole on the control panel of the central remote controller.

Image 101
Contents Split Type DC motor AC motor Type Indoor unit Outdoor unitName 0BT-E ∗∗ 1BT-E ∗∗ 1CT-EContents Outdoor Installation ManualNew Refrigerant Air Conditioner Installation Precautions for SafetyTo Disconnect the Appliance from Main Power Supply RAV-SP1100, 1400AT-E RAV-SM1100, 1400AT-ERefrigerant Piping Accessory and RefrigerantAccessory and Installation Parts Before installation Selection of InstallationNecessary Space for Installation Installation PlaceObstacle at rear side Upper side is free Obstacle at front side Upper side is freeStandard installation Installation of Outdoor UnitSerial installation at front and rear sides Obstacle also at the upper sideRefrigerant Piping Connection Optional Installation Parts Local ProcureFor Reference Knockout of Pipe CoverPipe Forming/End Positioning Refrigerant PipingOuter dia. of copper pipe Tightening torque Tightening of Connecting PartVacuum pump EvacuatingAir Purge Charge port How to open the valveValve size Electrical Work Stripping length power cord and connecting cableHow to wire Self-Diagnosis by LED Indication Final Installation ChecksCheck and Test Operation New tools for R410A Applicable to R22 model Changes Changes in the product and componentsNew tools for R410A Indoor Separate sold parts Part name ’ty Shape Standard wired remote ControllerRAV-SM560, 561, 800, 801BT-E RAV-SM1101, 1401BT-E Part name ’ty ShapeConnect the connecting cable correctly Inappropriate grounding may cause electric shock Installation space Selection of installation place Selection of Installation PlaceAdvice Secure the space required to installation and servicingInstallation procedure Installation of Indoor UnitExternal view Dimension100 RAV-SM1101, 1401BTMounting of clamp Accessory Installation of remote controller Sold separatelyHanging down of indoor unit Clamp mounting Removal of air filterInstallation clearance Restriction to installationConcealed duct type Ledge ceiling concealed duct type103 Static pressure characteristics of each modelAIR Ducting Work RAV-SM1401BT Round duct RAV-SM1101BT Round ductConnecting method of the duct 106 Points at installation workGeneral cautions Hanging of indoor unit Mounting of remote controllerMounting of filter and canvas for suction port 107Piping material Drain Piping WorkPiping and cautions Thermal-insulating processConnection of the drain hose Drain-upCheck of water drain After electric piping workFlaring dia meter size a Unit mm Permissible piping length and heatTightening connection Tightening torque of flare pipe connectionsOpen valve fully Packed valve handling precautionsGas leak check Use a vacuum pump112 For 801, 1101, 1401AT model801, 1101, 1401 type valve at gas side 113 Cabling diagram Remote controller cablingCabling 114Case of wired remote controller How to execute a test runTest RUN Before test runConfirmation of error history TroubleshootingProcedure Description Confirmation and check117 Applicable ControlsAutomatic address When using wireless remote controller Setup of external static pressureTo incorporate a filter sold separately Short plug position CN112, CN111, CN110 from the left119 Change of lighting time of filter signTo secure better effect of heating Maintenance INSTALLATION/SERVICING ToolsCleaning of Return grille Clean the Return grilles with waterRAV-SM561, 801CT-E RAV-SM1101, 1401CT-E 121Part name ’ty Shape Usage Part name122 123 124 Installation spaceAvoid installing in the following places Height of ceiling Case of wireless type126 How to use attached installation patternModel name 561CT 801CTKnockout hole of power cable take-in port Installation of hanging boltsPipe knockout hole Draw-out direction of pipe/cableInstallation of indoor unit Drain up Piping/Heat insulating materialCollective piping Adhesive inhibitedConnection of drain pipe Connection of drain hose Thermal insulating processCase of taking pipe from the left side 130Flaring diam. meter size a Unit mm Refrigerant Piping and Evacuating131 Outer diam. of copper pipeOpen the valve fully Piping with outdoor unitRefrigerant amount to be added Gas leak check133 Be sure to connect earth wire. Grounding workRemote controller wiring 134 Cable connection135 Wiring diagram136 137 138 139 Case of installation to high ceilingSet data 0000 Set data140 Tools Removal of suction grille141 Cleaning of air filter Accessories 144 RBC-EXW21EProgram button Cancel button Operation procedureTimer set button Holiday setting indication mark146 147 148 149 RBC-AS21EAutomatic Cool/Heat 150AS21E 151 RBC-AX22CE152 Remote ControllerSignal Receiving Part Operation Section Display Section 153154 155 How to Check the Address To Use the Remote Controller Setting to Wall, etcHow to Match the Address When a signalis correctlyreceived, Pisoundcan be heardStart 157Phenomenon Cause Measures Phenomenon Cause158 Requirement for installation Multiple remote controllers Accessory partsRemote controller test run setup How to perform cabling of the remote controller160 Program Weekly TimerRequirement to install the remote sensor Accessory partsHow to install the remote sensor 161162 Installation of sensor unitAccessory How to set the room temperature sensor How to perform cabling of sensor unitsHow to set the address switch Slide switchHow to handle the remote controller How to set up filter sold separately of the high ceiling164 Test runTo Personnel Charged in Installation Work and Service Ceiling panel Never modify or repair the product’ty ØM5mm x 40mm ØM4mm x 12mm FlapInstallation of suction grille Installation of adjust corner capCheck after installation For wireless remote controller168 TCB-DP22CENew Refrigerant Air Conditioner Installation Connect the connecting cable correctlyTo Disconnect the Appliance from Main Power Supply 169170 Before installationKnockout hole Connection of Elbow Piping KIT171 How to install drain up kitThermal insulating process Tightening connectionConnection of drain hose at indoor unit side 172Connection of drain hose at drain up kit side Piping/Heat insulating materialCheck the draining 173174 175 For Installation ProfessionalsUse for Indoor Unit Only Combination List of Adapter PartsCase of Concealed Duct RAV-SM **0 BT-E 176Case of 4-way Ceiling Cassette RAV-SM **0 UT-E Procedure Address No. setup table SW01Setup from the remote controller at the indoor unit side Setup by the switch on the adapter P.C. boardTo Customers 178179 TCB-KP12CE TCB-KP22CE180 Parts List181 Setup of fan when building in the high-efficiency filter Installation of high-efficiency filter182 High-Efficiency FilterDeodorant Filter, Ammonium Filter Setup of fan when building in the filter sold separately183 Page Memo