Balcar R410A service manual 178, To Customers

Page 102

– 178 –

To Customers

Cautions in using the remote controller

1.After all the power supplies of the air conditioner have been turned on, turn on the power supply of the central remote controller. (16-systems : RBC-CR1-PE, 64-systems : RBC-CR64-PE)

If the power supplies of the air conditioner and the remote controller are turned on at the same time, or if they are turned on in reverse order, the check code [97] may be temporarily displayed on the central remote controller. When the connection cabling and setup of the central address are correct, the connected air conditioner is displayed on the central remote controller.

2.As described below, there are differences of the display on LCD and the individual restrictions for the operation in the handy remote controller (RBC-AMT21E) and the central remote controller.

 

 

Contents

 

 

 

 

 

 

 

Item

 

 

 

Cautions

 

 

 

 

Main

Central

 

 

 

 

 

 

 

 

 

 

 

 

 

 

remote controller

remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Fan speed select

 

 

Display of air speed selection differs.

 

 

 

 

 

 

 

 

 

 

 

 

 

When operating the main remote controller,

is not displayed.

2

Fan speed select

 

 

If selecting

at the central side,

is displayed on the main

 

in FAN mode

 

 

remote controller.

 

 

 

 

 

 

 

 

In this time, the air speed is .

 

 

 

 

 

 

 

 

 

 

3

Fan speed select

 

 

only is displayed on the central remote controller.

is

 

 

displayed on the main remote controller even by change of the

in DRY mode

 

 

 

 

 

setup temperature/louver, and the air speed changes automatically.

 

 

 

 

 

 

 

 

 

 

 

 

[LOUVER]

[LOUVER] only is displayed on the central remote controller.

 

Air direction

and air direction

[LOUVER] is displayed when the flap is swinging, and ON and

4

 

OFF of the swing operation set to the louver are exchanged.

adjustment

adjustment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(No display)

[LOUVER] Manual

Set the air direction on the main remote controller.

 

 

 

 

 

 

 

 

 

 

 

In case of type without function of air direction adjustment

 

 

 

Test run

Display of check

The function differs when the

button is pushed for a long time.

5

Check button

code and Check

If the central remote controller-ON is reset during operation of the

(4 seconds)

 

 

reset (3 seconds)

air conditioner, the operation stops temporarily, and then the

 

 

 

 

 

 

 

operation is resumed. (Trouble of the air conditioner is cleared.)

 

 

 

 

 

 

 

 

 

 

Display with 3 digits

Display with 2 digits

The display of the check code differs.

 

 

 

 

 

 

 

 

 

 

 

6

Check code

(Alphabet + 2 digits

(Alphabet or

Ex.) Float switch operation

 

 

 

 

 

 

numerals)

numerals)

Main side : [P10], Collective side : [0b]

 

 

 

 

 

 

 

 

 

 

 

 

3.When using the remote controller with the former remote controller (RBC-AM1E, AT1E), if Last-push priority/Center/Locked is selectedon the central remotecontroller, the display differs on the main remotecontroller.

 

 

Contents

 

 

Item

 

 

Remarks

 

New remote

Former remote

 

 

controller

controller

 

 

 

(RBC-AMT21E)

(RBC-AM1E, AT1E)

 

 

 

 

 

 

1

Last-push priority

(No display)

(No display)

All the setups and Start/Stop operation are available.

 

 

 

 

 

2

Center

 

CENTER

The setup contents of the central remote controller are fixed, and

 

the Start/Stop operation and timer operation are available on the

 

goes on.

 

 

 

main remote controller.

 

 

CENTER

 

 

 

 

 

 

 

goes on.

CENTER

The setup contents of the central remote controller are fixed, and

 

 

 

3

Locked

 

the air conditioner stops. The operation on the main remote

 

flashes.

 

 

 

controller is unavailable.

 

 

 

 

 

 

 

 

 

* Before using the remote controller, read the Owner’s Manual thoroughly to use it correctly.

EH99774901- (EN)

TCB-PCNT20E

Image 102
Contents Split Type Name 0BT-E ∗∗ 1BT-E Type Indoor unit Outdoor unitDC motor AC motor ∗∗ 1CT-EContents Installation Manual OutdoorTo Disconnect the Appliance from Main Power Supply Precautions for SafetyNew Refrigerant Air Conditioner Installation RAV-SP1100, 1400AT-E RAV-SM1100, 1400AT-EAccessory and Refrigerant Accessory and Installation PartsRefrigerant Piping Selection of Installation Before installationObstacle at rear side Upper side is free Installation PlaceNecessary Space for Installation Obstacle at front side Upper side is freeSerial installation at front and rear sides Installation of Outdoor UnitStandard installation Obstacle also at the upper sideFor Reference Optional Installation Parts Local ProcureRefrigerant Piping Connection Knockout of Pipe CoverRefrigerant Piping Pipe Forming/End PositioningTightening of Connecting Part Outer dia. of copper pipe Tightening torqueEvacuating Air PurgeVacuum pump How to open the valve Valve sizeCharge port Stripping length power cord and connecting cable How to wireElectrical Work Final Installation Checks Check and Test OperationSelf-Diagnosis by LED Indication Changes in the product and components New tools for R410ANew tools for R410A Applicable to R22 model Changes Indoor RAV-SM560, 561, 800, 801BT-E RAV-SM1101, 1401BT-E Part name ’ty Shape Standard wired remote ControllerSeparate sold parts Part name ’ty ShapeConnect the connecting cable correctly Inappropriate grounding may cause electric shock Advice Selection of Installation PlaceInstallation space Selection of installation place Secure the space required to installation and servicingInstallation of Indoor Unit Installation procedure100 DimensionExternal view RAV-SM1101, 1401BTHanging down of indoor unit Installation of remote controller Sold separatelyMounting of clamp Accessory Clamp mounting Removal of air filterConcealed duct type Restriction to installationInstallation clearance Ledge ceiling concealed duct typeStatic pressure characteristics of each model AIR Ducting Work103 RAV-SM1101BT Round duct RAV-SM1401BT Round ductConnecting method of the duct Points at installation work General cautions106 Mounting of filter and canvas for suction port Mounting of remote controllerHanging of indoor unit 107Piping and cautions Drain Piping WorkPiping material Thermal-insulating processCheck of water drain Drain-upConnection of the drain hose After electric piping workTightening connection Permissible piping length and heatFlaring dia meter size a Unit mm Tightening torque of flare pipe connectionsGas leak check Packed valve handling precautionsOpen valve fully Use a vacuum pumpFor 801, 1101, 1401AT model 801, 1101, 1401 type valve at gas side112 113 Cabling Remote controller cablingCabling diagram 114Test RUN How to execute a test runCase of wired remote controller Before test runProcedure Description TroubleshootingConfirmation of error history Confirmation and checkApplicable Controls Automatic address117 To incorporate a filter sold separately Setup of external static pressureWhen using wireless remote controller Short plug position CN112, CN111, CN110 from the leftChange of lighting time of filter sign To secure better effect of heating119 Cleaning of Return grille INSTALLATION/SERVICING ToolsMaintenance Clean the Return grilles with waterPart name ’ty Shape Usage 121RAV-SM561, 801CT-E RAV-SM1101, 1401CT-E Part name122 123 Installation space Avoid installing in the following places124 Case of wireless type Height of ceilingModel name 561CT How to use attached installation pattern126 801CTPipe knockout hole Installation of hanging boltsKnockout hole of power cable take-in port Draw-out direction of pipe/cableInstallation of indoor unit Collective piping Piping/Heat insulating materialDrain up Adhesive inhibitedCase of taking pipe from the left side Connection of drain hose Thermal insulating processConnection of drain pipe 130131 Refrigerant Piping and EvacuatingFlaring diam. meter size a Unit mm Outer diam. of copper pipeRefrigerant amount to be added Piping with outdoor unitOpen the valve fully Gas leak checkBe sure to connect earth wire. Grounding work Remote controller wiring133 Cable connection 134Wiring diagram 135136 137 138 Set data 0000 Case of installation to high ceiling139 Set data140 Removal of suction grille 141Tools Cleaning of air filter Accessories RBC-EXW21E 144Timer set button Operation procedureProgram button Cancel button Holiday setting indication mark146 147 148 RBC-AS21E 149150 AS21EAutomatic Cool/Heat RBC-AX22CE 151Remote Controller Signal Receiving Part152 153 Operation Section Display Section154 155 How to Match the Address To Use the Remote Controller Setting to Wall, etcHow to Check the Address When a signalis correctlyreceived, Pisoundcan be heardPhenomenon Cause Measures 157Start Phenomenon Cause158 Remote controller test run setup Accessory partsRequirement for installation Multiple remote controllers How to perform cabling of the remote controllerProgram Weekly Timer 160How to install the remote sensor Accessory partsRequirement to install the remote sensor 161Installation of sensor unit Accessory162 How to set the address switch How to perform cabling of sensor unitsHow to set the room temperature sensor Slide switch164 How to set up filter sold separately of the high ceilingHow to handle the remote controller Test runTo Personnel Charged in Installation Work and Service ’ty ØM5mm x 40mm ØM4mm x 12mm Never modify or repair the productCeiling panel FlapCheck after installation Installation of adjust corner capInstallation of suction grille For wireless remote controllerTCB-DP22CE 168To Disconnect the Appliance from Main Power Supply Connect the connecting cable correctlyNew Refrigerant Air Conditioner Installation 169Knockout hole Before installation170 Connection of Elbow Piping KITThermal insulating process How to install drain up kit171 Tightening connectionConnection of drain hose at drain up kit side 172Connection of drain hose at indoor unit side Piping/Heat insulating material173 Check the draining174 Use for Indoor Unit Only For Installation Professionals175 Combination List of Adapter Parts176 Case of 4-way Ceiling Cassette RAV-SM **0 UT-ECase of Concealed Duct RAV-SM **0 BT-E Setup from the remote controller at the indoor unit side Address No. setup table SW01Procedure Setup by the switch on the adapter P.C. board178 To CustomersTCB-KP12CE TCB-KP22CE 179Parts List 180181 182 Installation of high-efficiency filterSetup of fan when building in the high-efficiency filter High-Efficiency FilterSetup of fan when building in the filter sold separately 183Deodorant Filter, Ammonium Filter Page Memo