Balcar R410A Permissible piping length and heat, Flaring dia meter size a Unit mm, 110

Page 34
Flare at indoor unit side

RAV-SM560, 561, 800, 801BT-E

RAV-SM1101, 1401BT-E

6 REFRIGERANT PIPING

Refrigerant piping

1.If the outdoor units are to be mounted on a wall, make sure that the supporting platform is sufficiently strong. The platform should be designed and manufactured to maintain its strength over a long period of time, and sufficient consideration should be given to ensuring that the outdoor unit will not fall.

2.Use copper pipe with 0.8 mm or more thickness.

3.Flare nut and flare works are also different from those of the conventional refrigerant.

Take out the flare nut attached to the main unit of the air conditioner, and use it.

CAUTION

IMPORTANT 4 POINTS FOR PIPING WORK

1.Remove dust and moisture from the inside of the connecting pipes.

2.Tight connection (between pipes and unit)

3.Evacuate the air in the connecting pipes using

VACUUM PUMP.

4.Check the gas leakage. (connected points)

Permissible piping length and heat

The maximum piping length from the outdoor to indoor unit

30 m (Chargeless 20 m)

15 m (Chargeless 15 m)

(RAV-SM561/801AT)

(RAV-SM1101/1401AT)

The maximum height difference outdoor/indoor unit

Outdoor unit is above

Outdoor unit is below

 

 

30 m

30 m

 

 

Flaring

Insert a flare nut into the pipe, and flare the pipe.

As the flaring sizes of R410A differ from those of refrigerant R22, the flare tools newly manufactured for

R410A are recommended.

B

However, the conventional tools can be used by adjusting projection margin of the copper pipe.

• Projection margin in flaring : B (Unit : mm)

Rigid (Clutch type)

Outer diam. of

R410A tool used

Conventional tool used

 

 

 

 

copper pipe

 

R410A

R22

R410A

R22

 

 

 

 

 

 

 

6.4 to 15.9

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

 

Imperial (Wing nut type)

Outer diam. of copper pipe

R410A

R22

 

 

 

6.4 or 9.5

1.5 to 2.0

1.0 to 1.5

 

 

 

12.7 or 15.9

2.0 to 2.5

1.5 to 2.0

 

 

 

• Flaring dia meter size : A (Unit : mm)

 

 

A +0

Outer diam. of copper pipe

 

- 0.4

R410A

 

R22

 

 

 

 

 

 

6.4

9.1

 

9.0

 

 

 

 

9.5

13.2

 

13.0

 

 

 

 

12.7

16.6

 

16.2

 

 

 

 

15.9

19.7

 

19.4

 

 

 

 

*In the case of flaring for R410A with the conventional flare tool, pull out it approx.

0.5 mm more than that for R22 to

 

 

 

A

 

adjust to the specified flare size.

 

 

 

 

 

 

 

 

 

 

The copper pipe gauge is useful

 

 

 

 

 

 

 

 

 

for adjusting projection margin size.

 

 

 

Tightening connection

CAUTION

Do not apply excessive torque. Otherwise, the nut may crack depending on the conditions.

 

(Unit : N•m)

 

 

Outer diam. of copper pipe

Tightening torque

 

 

6.4 mm (diam.)

14 to 18 (1.4 to 1.8 kgf•m)

 

 

9.5 mm (diam.)

33 to 42 (3.3 to 4.2 kgf•m)

 

 

12.7 mm (diam.)

50 to 62 (5.0 to 6.2 kgf•m)

 

 

15.9 mm (diam.)

63 to 77 (6.3 to 7.7 kgf•m)

 

 

Tightening torque of flare pipe connections

Pressure of R410A becomes higher than that of R22. (Approx. 1.6 times) Therefore, using a torque wrench, tighten firmly the flare pipe connecting

sections which connect the indoor and outdoor units up to the specified tightening torque.

Incorrect connections may cause not only a gas leakage, but also a trouble of the refrigeration cycle or compressor damage.

Flare at outdoor unit side

Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.

Half union

Flare nut

Externally

Internally

threaded side

threaded side

Use a wrench to secure.

Use a torque wrench to tighten.

– 110 –

Image 34
Contents Split Type Name 0BT-E ∗∗ 1BT-E Type Indoor unit Outdoor unitDC motor AC motor ∗∗ 1CT-EContents Installation Manual OutdoorTo Disconnect the Appliance from Main Power Supply Precautions for SafetyNew Refrigerant Air Conditioner Installation RAV-SP1100, 1400AT-E RAV-SM1100, 1400AT-EAccessory and Installation Parts Accessory and RefrigerantRefrigerant Piping Selection of Installation Before installationObstacle at rear side Upper side is free Installation PlaceNecessary Space for Installation Obstacle at front side Upper side is freeSerial installation at front and rear sides Installation of Outdoor UnitStandard installation Obstacle also at the upper sideFor Reference Optional Installation Parts Local ProcureRefrigerant Piping Connection Knockout of Pipe CoverRefrigerant Piping Pipe Forming/End PositioningTightening of Connecting Part Outer dia. of copper pipe Tightening torqueAir Purge EvacuatingVacuum pump Valve size How to open the valveCharge port How to wire Stripping length power cord and connecting cableElectrical Work Check and Test Operation Final Installation ChecksSelf-Diagnosis by LED Indication New tools for R410A Changes in the product and componentsNew tools for R410A Applicable to R22 model Changes Indoor RAV-SM560, 561, 800, 801BT-E RAV-SM1101, 1401BT-E Part name ’ty Shape Standard wired remote ControllerSeparate sold parts Part name ’ty ShapeConnect the connecting cable correctly Inappropriate grounding may cause electric shock Advice Selection of Installation PlaceInstallation space Selection of installation place Secure the space required to installation and servicingInstallation of Indoor Unit Installation procedure100 DimensionExternal view RAV-SM1101, 1401BTHanging down of indoor unit Installation of remote controller Sold separatelyMounting of clamp Accessory Clamp mounting Removal of air filterConcealed duct type Restriction to installationInstallation clearance Ledge ceiling concealed duct typeAIR Ducting Work Static pressure characteristics of each model103 RAV-SM1101BT Round duct RAV-SM1401BT Round ductConnecting method of the duct General cautions Points at installation work106 Mounting of filter and canvas for suction port Mounting of remote controllerHanging of indoor unit 107Piping and cautions Drain Piping WorkPiping material Thermal-insulating processCheck of water drain Drain-upConnection of the drain hose After electric piping workTightening connection Permissible piping length and heatFlaring dia meter size a Unit mm Tightening torque of flare pipe connectionsGas leak check Packed valve handling precautionsOpen valve fully Use a vacuum pump801, 1101, 1401 type valve at gas side For 801, 1101, 1401AT model112 113 Cabling Remote controller cablingCabling diagram 114Test RUN How to execute a test runCase of wired remote controller Before test runProcedure Description TroubleshootingConfirmation of error history Confirmation and checkAutomatic address Applicable Controls117 To incorporate a filter sold separately Setup of external static pressureWhen using wireless remote controller Short plug position CN112, CN111, CN110 from the leftTo secure better effect of heating Change of lighting time of filter sign119 Cleaning of Return grille INSTALLATION/SERVICING ToolsMaintenance Clean the Return grilles with waterPart name ’ty Shape Usage 121RAV-SM561, 801CT-E RAV-SM1101, 1401CT-E Part name122 123 Avoid installing in the following places Installation space124 Case of wireless type Height of ceilingModel name 561CT How to use attached installation pattern126 801CTPipe knockout hole Installation of hanging boltsKnockout hole of power cable take-in port Draw-out direction of pipe/cableInstallation of indoor unit Collective piping Piping/Heat insulating materialDrain up Adhesive inhibitedCase of taking pipe from the left side Connection of drain hose Thermal insulating processConnection of drain pipe 130131 Refrigerant Piping and EvacuatingFlaring diam. meter size a Unit mm Outer diam. of copper pipeRefrigerant amount to be added Piping with outdoor unitOpen the valve fully Gas leak checkRemote controller wiring Be sure to connect earth wire. Grounding work133 Cable connection 134Wiring diagram 135136 137 138 Set data 0000 Case of installation to high ceiling139 Set data140 141 Removal of suction grilleTools Cleaning of air filter Accessories RBC-EXW21E 144Timer set button Operation procedureProgram button Cancel button Holiday setting indication mark146 147 148 RBC-AS21E 149AS21E 150Automatic Cool/Heat RBC-AX22CE 151Signal Receiving Part Remote Controller152 153 Operation Section Display Section154 155 How to Match the Address To Use the Remote Controller Setting to Wall, etcHow to Check the Address When a signalis correctlyreceived, Pisoundcan be heardPhenomenon Cause Measures 157Start Phenomenon Cause158 Remote controller test run setup Accessory partsRequirement for installation Multiple remote controllers How to perform cabling of the remote controllerProgram Weekly Timer 160How to install the remote sensor Accessory partsRequirement to install the remote sensor 161Accessory Installation of sensor unit162 How to set the address switch How to perform cabling of sensor unitsHow to set the room temperature sensor Slide switch164 How to set up filter sold separately of the high ceilingHow to handle the remote controller Test runTo Personnel Charged in Installation Work and Service ’ty ØM5mm x 40mm ØM4mm x 12mm Never modify or repair the productCeiling panel FlapCheck after installation Installation of adjust corner capInstallation of suction grille For wireless remote controllerTCB-DP22CE 168To Disconnect the Appliance from Main Power Supply Connect the connecting cable correctlyNew Refrigerant Air Conditioner Installation 169Knockout hole Before installation170 Connection of Elbow Piping KITThermal insulating process How to install drain up kit171 Tightening connectionConnection of drain hose at drain up kit side 172Connection of drain hose at indoor unit side Piping/Heat insulating material173 Check the draining174 Use for Indoor Unit Only For Installation Professionals175 Combination List of Adapter PartsCase of 4-way Ceiling Cassette RAV-SM **0 UT-E 176Case of Concealed Duct RAV-SM **0 BT-E Setup from the remote controller at the indoor unit side Address No. setup table SW01Procedure Setup by the switch on the adapter P.C. board178 To CustomersTCB-KP12CE TCB-KP22CE 179Parts List 180181 182 Installation of high-efficiency filterSetup of fan when building in the high-efficiency filter High-Efficiency Filter183 Setup of fan when building in the filter sold separatelyDeodorant Filter, Ammonium Filter Page Memo