Balcar R410A 159, Accessory parts, Requirement for installation Multiple remote controllers

Page 83

INSTALLATION MANUAL To Personnel Charged in Installation (Electric) Work and Service

Simple Remote Controller

MODEL : RBC-AS21E

Accessory parts

Part Name

Q’ty

Part Name

Q’ty

Remote controller

 

Spacer

2

 

 

 

 

1

Wire joint

 

 

 

2

(200mm-cable

 

 

attached)

 

 

 

Screw

2

Clamper

1

M4 x 25

 

Wood screw

2

Installation Manual

1

 

 

Requirement to install

the remote controller

How to install

the remote controller switch

NOTE 1 :

Avoid to twist the remote controller cable with the power supply cable, etc. or to store them in the same metal pipe, otherwise it causes a malfunc- tion.

NOTE 2 :

Install the remote controller apart from the generation source of noise.

NOTE 3 :

When noise is contained to the power source of the indoor unit, counter measures such as mounting the noise filter is necessary.

How to perform cabling of the remote controller

• Connection diagram

Remote

 

 

 

 

controller

Terminal block for

A

 

W

remote controller

 

B

 

B

cable in indoor unit

 

 

 

 

W : White

Remote controller cable

Connecting

Cable from

B : Black

(Procured locally)

section

Remote controller

 

 

 

 

body

Non polarity, 2 core cable is used.

Use 0.5mm² to 2 mm² cable.

Basic cabling diagram NOTE :

Connect cables without miswiring. (Miswiring breaks the unit.)

In a case to operate an indoor unit from the remote controllers at two positions

Remote controller

Remote controller

 

(Master)

 

(Sub)

 

 

 

 

 

 

 

 

 

 

 

(Sold separately)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller cable

 

 

 

 

 

 

 

 

 

 

(Procured locally)

Terminal block for remote controller cable

A B

– 159 –

Installation place

• Install the remote controller at a position within 1

to 1.5m from the floor, where the average tem-

perature in the room can be felt.

• Do not install the remote controller at a place

exposed to direct sunlight or direct outside air,

such as a side of window, etc.

• Do not install the remote controller at a place

behind something or rear side of something,

where air flow is poor in the room.

• Do not install the remote controller in the freezing

box or refrigerator because water proof or drop-

proof is not applied to this remote controller.

• Be sure to set the remote controller vertically on

In case of using the remote controller as a concealed type

Rear case

Spacer

 

Remote controller

 

body

Wall

Attached wire joint

(White, 2 pcs.)

Remote controller cable

 

Cable from

Wire joint

remote controller body

 

1)Peel the sheath of cable to be connected by approx. 14mm.

2)Twist two cables and pressure-connect them using a wire joint.

3)When an exclusive pressure-connecting tool is not used or soldering connection is used, apply insulation process with an insulation tape.

Indoor unit

Earth

In a case to operate a group control of multiple indoor units from the remote controllers at two positions

*Master and sub remote controllers are operable even if they are installed to any indoor unit.

Remote controller

 

Remote controller

(Master)

 

 

(Sub)

 

 

Remote controller inter-unit

 

 

cable for group control

 

(Sold

 

(Procured locally)

 

(Sold

separately)

 

 

 

separately)

Terminal block

 

 

 

 

for remote

 

 

 

 

controller

A B

A B

A B

A B

cable

 

 

 

 

the wall surface, etc.

How to select the room temp. sensor

The room temperature sensors are equipped in the indoor unit and the remote controller.

One of two sensors works. Usually, the room temperature sensor in the indoor unit is set to work. To select the sensor in the remote controller, turn the remote controller sensor from OFF to ON.

NOTE 1 :

Selecting the sensor in the remote controller is impossible on the sub remote controller.

NOTE 2 :

Do not select the sensor in the remote controller when a remote controller sensor is used. (Because it causes a straying.)

Screws

M4 x 25 or wood screws (2 pcs.)

1.Inserting a minus screwdriver, etc. into the groove at the lower side of the remote controller body, force open the rear case to remove it.

2.Using the attached M4 screws (2 pcs.), fix the rear case of the remote controller.

Before installation, press to open the screw hole with a screwdriver, etc.

Fix it with the spacer, but not so strongly. If the remote controller does not fit closely to the wall, adjust it by cutting off the spacer.

3.Connect the remote controller cable (2 cores) to the cable from the remote controller body. Connect the remote controller cable without miswiring upon confirmation of the terminal numbers of the indoor unit. (If applyied

AC 220/230/240V, may damage the unit.)

4.Install the remote controller body to hooks on the rear case and putting into the hooks.

Requirement for installation of

multiple remote controllers

“2 remote controller control” means that one or multiple units are operated by the multiple remote controllers.

• How to install

For 2 remote controller control, install the remote controllers in the following procedure.

1.Set one of the set multiple remote controllers to the master remote controller.

(At shipment from factory)

2.For other remote controllers, turn the remote controller address switch on the remote controller P.C. board from OFF to ON. They function as sub remote controllers under the above condition.

 

 

 

Indoor unit

 

 

 

 

Indoor unit

 

 

 

 

Indoor unit

 

 

 

 

Indoor unit

 

 

 

No.1

 

 

 

 

No.2

 

 

 

 

No.3

 

 

 

 

No.N

 

 

 

 

Earth

Earth

Earth

Earth

Remote controller test run setup

1.Push key after keeping [CHECK] button pushed on the remote controller for 4 seconds or more.

During the test run, “TEST” is displayed on LCD.

The temperature cannot be controlled if [TEST] is displayed. Do not use [TEST] in a case other than a test run, otherwise an excessive load is applied on the machine.

2.Use [TEST] in one of HEAT, COOL, and FAN operation modes.

NOTE :

The outdoor unit does not operate for approx. 3 minutes after the power supply has been turned on or the operation has stopped.

3.After the test run has finished, push [CHECK] button again to check “TEST” on LCD has gone off. (For this remote controller, a release function of 60 minutes timer is provided to prevent consecutive test runs.)

RBC-AS21E

85464359428000 (EN)

Image 83
Contents Split Type ∗∗ 1CT-E Type Indoor unit Outdoor unitDC motor AC motor Name 0BT-E ∗∗ 1BT-EContents Outdoor Installation ManualRAV-SP1100, 1400AT-E RAV-SM1100, 1400AT-E Precautions for SafetyNew Refrigerant Air Conditioner Installation To Disconnect the Appliance from Main Power SupplyRefrigerant Piping Accessory and RefrigerantAccessory and Installation Parts Before installation Selection of InstallationObstacle at front side Upper side is free Installation PlaceNecessary Space for Installation Obstacle at rear side Upper side is freeObstacle also at the upper side Installation of Outdoor UnitStandard installation Serial installation at front and rear sidesKnockout of Pipe Cover Optional Installation Parts Local ProcureRefrigerant Piping Connection For ReferencePipe Forming/End Positioning Refrigerant PipingOuter dia. of copper pipe Tightening torque Tightening of Connecting PartVacuum pump EvacuatingAir Purge Charge port How to open the valveValve size Electrical Work Stripping length power cord and connecting cableHow to wire Self-Diagnosis by LED Indication Final Installation ChecksCheck and Test Operation New tools for R410A Applicable to R22 model Changes Changes in the product and componentsNew tools for R410A Indoor Part name ’ty Shape Part name ’ty Shape Standard wired remote ControllerSeparate sold parts RAV-SM560, 561, 800, 801BT-E RAV-SM1101, 1401BT-EConnect the connecting cable correctly Inappropriate grounding may cause electric shock Secure the space required to installation and servicing Selection of Installation PlaceInstallation space Selection of installation place AdviceInstallation procedure Installation of Indoor UnitRAV-SM1101, 1401BT DimensionExternal view 100Clamp mounting Removal of air filter Installation of remote controller Sold separatelyMounting of clamp Accessory Hanging down of indoor unitLedge ceiling concealed duct type Restriction to installationInstallation clearance Concealed duct type103 Static pressure characteristics of each modelAIR Ducting Work RAV-SM1401BT Round duct RAV-SM1101BT Round ductConnecting method of the duct 106 Points at installation workGeneral cautions 107 Mounting of remote controllerHanging of indoor unit Mounting of filter and canvas for suction portThermal-insulating process Drain Piping WorkPiping material Piping and cautionsAfter electric piping work Drain-upConnection of the drain hose Check of water drainTightening torque of flare pipe connections Permissible piping length and heatFlaring dia meter size a Unit mm Tightening connectionUse a vacuum pump Packed valve handling precautionsOpen valve fully Gas leak check112 For 801, 1101, 1401AT model801, 1101, 1401 type valve at gas side 113 114 Remote controller cablingCabling diagram CablingBefore test run How to execute a test runCase of wired remote controller Test RUNConfirmation and check TroubleshootingConfirmation of error history Procedure Description117 Applicable ControlsAutomatic address Short plug position CN112, CN111, CN110 from the left Setup of external static pressureWhen using wireless remote controller To incorporate a filter sold separately119 Change of lighting time of filter signTo secure better effect of heating Clean the Return grilles with water INSTALLATION/SERVICING ToolsMaintenance Cleaning of Return grillePart name 121RAV-SM561, 801CT-E RAV-SM1101, 1401CT-E Part name ’ty Shape Usage122 123 124 Installation spaceAvoid installing in the following places Height of ceiling Case of wireless type801CT How to use attached installation pattern126 Model name 561CTDraw-out direction of pipe/cable Installation of hanging boltsKnockout hole of power cable take-in port Pipe knockout holeInstallation of indoor unit Adhesive inhibited Piping/Heat insulating materialDrain up Collective piping130 Connection of drain hose Thermal insulating processConnection of drain pipe Case of taking pipe from the left sideOuter diam. of copper pipe Refrigerant Piping and EvacuatingFlaring diam. meter size a Unit mm 131Gas leak check Piping with outdoor unitOpen the valve fully Refrigerant amount to be added133 Be sure to connect earth wire. Grounding workRemote controller wiring 134 Cable connection135 Wiring diagram136 137 138 Set data Case of installation to high ceiling139 Set data 0000140 Tools Removal of suction grille141 Cleaning of air filter Accessories 144 RBC-EXW21EHoliday setting indication mark Operation procedureProgram button Cancel button Timer set button146 147 148 149 RBC-AS21EAutomatic Cool/Heat 150AS21E 151 RBC-AX22CE152 Remote ControllerSignal Receiving Part Operation Section Display Section 153154 155 When a signalis correctlyreceived, Pisoundcan be heard To Use the Remote Controller Setting to Wall, etcHow to Check the Address How to Match the AddressPhenomenon Cause 157Start Phenomenon Cause Measures158 How to perform cabling of the remote controller Accessory partsRequirement for installation Multiple remote controllers Remote controller test run setup160 Program Weekly Timer161 Accessory partsRequirement to install the remote sensor How to install the remote sensor162 Installation of sensor unitAccessory Slide switch How to perform cabling of sensor unitsHow to set the room temperature sensor How to set the address switchTest run How to set up filter sold separately of the high ceilingHow to handle the remote controller 164To Personnel Charged in Installation Work and Service Flap Never modify or repair the productCeiling panel ’ty ØM5mm x 40mm ØM4mm x 12mmFor wireless remote controller Installation of adjust corner capInstallation of suction grille Check after installation168 TCB-DP22CE169 Connect the connecting cable correctlyNew Refrigerant Air Conditioner Installation To Disconnect the Appliance from Main Power SupplyConnection of Elbow Piping KIT Before installation170 Knockout holeTightening connection How to install drain up kit171 Thermal insulating processPiping/Heat insulating material 172Connection of drain hose at indoor unit side Connection of drain hose at drain up kit sideCheck the draining 173174 Combination List of Adapter Parts For Installation Professionals175 Use for Indoor Unit OnlyCase of Concealed Duct RAV-SM **0 BT-E 176Case of 4-way Ceiling Cassette RAV-SM **0 UT-E Setup by the switch on the adapter P.C. board Address No. setup table SW01Procedure Setup from the remote controller at the indoor unit sideTo Customers 178179 TCB-KP12CE TCB-KP22CE180 Parts List181 High-Efficiency Filter Installation of high-efficiency filterSetup of fan when building in the high-efficiency filter 182Deodorant Filter, Ammonium Filter Setup of fan when building in the filter sold separately183 Page Memo