Balcar R410A 164, How to set up filter sold separately of the high ceiling, Test run

Page 88

How to set up filter sold separately of the high ceiling

When the height of ceiling to be installed with a filter exceeds 3.5m or when installing a filter sold separately, tap-up of DC fan is required. Tap-up of DC fan can be set at No.2 (Tap 1) and No.4 (Tap 2) of DIP switch [S003] on the wireless sensor P.C. board. The wireless sensor P.C. board appears by removing screws at the rear side of the wireless sensor unit and the rear cover.

Setup for high ceiling

 

[S003] No.2

[S003] No.4

Installable

 

(Tap 1)

(Tap 2)

height of ceiling

Standard (At shipment)

OFF

OFF

3.5m

Type 1

OFF

ON

4.0m

 

 

 

 

[S003] No.2 (Tap 1) and

[S003] No.4 (Tap 2) are used.

 

4

3

2 1

2 3 4

ON

 

 

 

 

 

Test run

Before test run

Before turning on the power supply, carry out the following procedure.

1)Using 500V-megger, check 1MW or more exists between the terminal block 1 to 3 and the earth. If 1MW or less is detected, do not run the unit. Do not apply to the remote controller circuit.

2)Check the valve of the outdoor unit being opened fully.

To protect the compressor at activation time, leave power-ON for 12 hours or more be for operating.

How to execute a test run

Using the remote controller, operate the unit as usual.

For the procedure of the operation, refer to the attached Owner’s Manual.

A forced test run can be executed in the following procedure if the operation stops by thermo.-OFF. In order to prevent a serial operation, the forced test run is released after 60 minutes have passed

Setup for filter sold separately

 

[S003] No.2 (Tap 1)

[S003] No.4 (Tap 2)

Filter sold separately

Standard (At shipment)

OFF

OFF

Standard filter

Type 1

OFF

ON

Optical regeneration deodorant filter

Type 3

ON

OFF

High-performance filter

Type 6

ON

ON

Deodorant filter / Ammonia deodorant filter

and returns to the usual operation.

CAUTION

When the remote controller is used for the first time, it accepts an operation approx. 5 minutes after the power supply has been turned on.

It is not a trouble, but is because the setup of the remote controller is being checked.

For the second power-ON time and after, approx. 1 minute is required to start the operation by the remote controller.

– 164 –

[NOTE]

If the setup has been once performed, the set contents of Type 1, 3, and 6 can be arbitrarily changed. However, it is required to turn off [S003] No.2 (Tap 1) and No.4 (Tap 2) of DIP switch and also required to rewrite by the wired remote controller sold separately to return the set content to the standard one (at shipment). (For rewriting by a wired remote controller sold separately, refer to the Installation Manual attached to the indoor unit.)

How to handle the remote controller

In case using remote controller mounting to the wall, etc.

Check a signal is received correctly by pushing button at the position to be fixed.

Replacement of battery

1. Holding the both ends of the cover and

remove it by sliding downward.

NOTE

Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices.

In case of wireless remote controller

Be sure to set the air speed to [ ].

2

ADR

2, 7

3, 4, 5, 6

Never set ON to DIP switch [S003] No.1 (Test run). (A test run is carried out on the remote controller.) (For the test run, refer to the Installation Manual attached to the indoor unit.)

2.

Correctly insert 2 AAA alkali batteries

 

matching + and - polarities with indica-

 

tions.

3.

Push SET button with something tipped

 

and attach the cover.

Procedure

Operation contents

 

Turn on power of the set.

1

 

 

After installation, the operation is not accepted for 5 minutes when the power has been turned on

at the first time, and 1 minute when the power has been turned on at the second time and after.

 

Perform a test run after a specified time has passed.

Cautions for installation of the remote controller

To operate the remote controller by fixing it to the wall, etc. with a remote controller holder, turn on the fluores- cent lamp, operate the remote controller at the position to be fixed, check the air conditioner normally operates, and then mount it.

When the room temperature is sensed by the remote controller, mount the remote controller paying attention to the following items.

Place not exposed directly to cold or hot wind.

Place not exposed directly to the sunlight.

Other places where the remote controller is not influenced.

Explanation to customers

Hand over the “Owner’s Manual” and “Installation Manuals” to the customer after installation works.

Explain usage and maintenance of the remote controller according to “Owner’s Manual”.

Mounting screw Truss tapping 4 x 16

Cover

Put on.

1

Push.

2

To take off remote controller, pull it toward you.

RESET button

2

Push [

] button on the remote controller, change the operation mode to [ ] or [ ] by using [ ]

button, and then change the air speed to [

] by [

] button.

3

 

Cooling test run

 

 

 

 

Heating test run

 

 

 

 

 

 

 

 

Set temperature to [18˚C] by using [

] button.

 

Set temperature to [30˚C] by using [ ] button.

 

 

 

 

 

 

 

 

4

Push [

] button to set temperature to [19˚C] just

 

Push [

] button to set temperature to [29˚C] just

after confirming the receiving sound “Pi”.

 

 

after confirming the receiving sound “Pi”.

 

 

 

 

 

 

5

Push [

] button to set temperature to [18˚C] just

 

Push [

] button to set temperature to [30˚C] just

after confirming the receiving sound “Pi”.

 

 

after confirming the receiving sound “Pi”.

 

 

 

 

 

 

6

Repeat the procedure 4 5

4

5 .

After approx. 10 seconds, all the display lamps [ ]

(Green), [ ] (Green), and [

] (Yellow) of the wireless sensors flash, and the operation starts.

 

If the lamps do not flash, repeat the procedure 2 and after.

 

7

When the test run has finished, push [

] button to stop the operation.

<Outline of test run by using a wireless remote controller>

Cooling test run : Start/Stop 18˚C 19˚C 18˚C 19˚C 18˚C 19˚C 18˚C (Test run) Start/Stop

Heating test run : Start/Stop 30˚C 29˚C 30˚C 29˚C 30˚C 29˚C 30˚C (Test run) Start/Stop

RBC-AX22CE

Image 88
Contents Split Type Type Indoor unit Outdoor unit DC motor AC motorName 0BT-E ∗∗ 1BT-E ∗∗ 1CT-EContents Installation Manual OutdoorPrecautions for Safety New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply RAV-SP1100, 1400AT-E RAV-SM1100, 1400AT-EAccessory and Installation Parts Accessory and RefrigerantRefrigerant Piping Selection of Installation Before installationInstallation Place Necessary Space for InstallationObstacle at rear side Upper side is free Obstacle at front side Upper side is freeInstallation of Outdoor Unit Standard installationSerial installation at front and rear sides Obstacle also at the upper sideOptional Installation Parts Local Procure Refrigerant Piping ConnectionFor Reference Knockout of Pipe CoverRefrigerant Piping Pipe Forming/End PositioningTightening of Connecting Part Outer dia. of copper pipe Tightening torqueAir Purge EvacuatingVacuum pump Valve size How to open the valveCharge port How to wire Stripping length power cord and connecting cableElectrical Work Check and Test Operation Final Installation ChecksSelf-Diagnosis by LED Indication New tools for R410A Changes in the product and componentsNew tools for R410A Applicable to R22 model Changes Indoor Part name ’ty Shape Standard wired remote Controller Separate sold partsRAV-SM560, 561, 800, 801BT-E RAV-SM1101, 1401BT-E Part name ’ty ShapeConnect the connecting cable correctly Inappropriate grounding may cause electric shock Selection of Installation Place Installation space Selection of installation placeAdvice Secure the space required to installation and servicingInstallation of Indoor Unit Installation procedureDimension External view100 RAV-SM1101, 1401BTInstallation of remote controller Sold separately Mounting of clamp AccessoryHanging down of indoor unit Clamp mounting Removal of air filterRestriction to installation Installation clearanceConcealed duct type Ledge ceiling concealed duct typeAIR Ducting Work Static pressure characteristics of each model103 RAV-SM1101BT Round duct RAV-SM1401BT Round ductConnecting method of the duct General cautions Points at installation work106 Mounting of remote controller Hanging of indoor unitMounting of filter and canvas for suction port 107Drain Piping Work Piping materialPiping and cautions Thermal-insulating processDrain-up Connection of the drain hoseCheck of water drain After electric piping workPermissible piping length and heat Flaring dia meter size a Unit mmTightening connection Tightening torque of flare pipe connectionsPacked valve handling precautions Open valve fullyGas leak check Use a vacuum pump801, 1101, 1401 type valve at gas side For 801, 1101, 1401AT model112 113 Remote controller cabling Cabling diagramCabling 114How to execute a test run Case of wired remote controllerTest RUN Before test runTroubleshooting Confirmation of error historyProcedure Description Confirmation and checkAutomatic address Applicable Controls117 Setup of external static pressure When using wireless remote controllerTo incorporate a filter sold separately Short plug position CN112, CN111, CN110 from the leftTo secure better effect of heating Change of lighting time of filter sign119 INSTALLATION/SERVICING Tools MaintenanceCleaning of Return grille Clean the Return grilles with water121 RAV-SM561, 801CT-E RAV-SM1101, 1401CT-EPart name ’ty Shape Usage Part name122 123 Avoid installing in the following places Installation space124 Case of wireless type Height of ceilingHow to use attached installation pattern 126Model name 561CT 801CTInstallation of hanging bolts Knockout hole of power cable take-in portPipe knockout hole Draw-out direction of pipe/cableInstallation of indoor unit Piping/Heat insulating material Drain upCollective piping Adhesive inhibitedConnection of drain hose Thermal insulating process Connection of drain pipeCase of taking pipe from the left side 130Refrigerant Piping and Evacuating Flaring diam. meter size a Unit mm131 Outer diam. of copper pipePiping with outdoor unit Open the valve fullyRefrigerant amount to be added Gas leak checkRemote controller wiring Be sure to connect earth wire. Grounding work133 Cable connection 134Wiring diagram 135136 137 138 Case of installation to high ceiling 139Set data 0000 Set data140 141 Removal of suction grilleTools Cleaning of air filter Accessories RBC-EXW21E 144Operation procedure Program button Cancel buttonTimer set button Holiday setting indication mark146 147 148 RBC-AS21E 149AS21E 150Automatic Cool/Heat RBC-AX22CE 151Signal Receiving Part Remote Controller152 153 Operation Section Display Section154 155 To Use the Remote Controller Setting to Wall, etc How to Check the AddressHow to Match the Address When a signalis correctlyreceived, Pisoundcan be heard157 StartPhenomenon Cause Measures Phenomenon Cause158 Accessory parts Requirement for installation Multiple remote controllersRemote controller test run setup How to perform cabling of the remote controllerProgram Weekly Timer 160Accessory parts Requirement to install the remote sensorHow to install the remote sensor 161Accessory Installation of sensor unit162 How to perform cabling of sensor units How to set the room temperature sensorHow to set the address switch Slide switchHow to set up filter sold separately of the high ceiling How to handle the remote controller164 Test runTo Personnel Charged in Installation Work and Service Never modify or repair the product Ceiling panel’ty ØM5mm x 40mm ØM4mm x 12mm FlapInstallation of adjust corner cap Installation of suction grilleCheck after installation For wireless remote controllerTCB-DP22CE 168Connect the connecting cable correctly New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply 169Before installation 170Knockout hole Connection of Elbow Piping KITHow to install drain up kit 171Thermal insulating process Tightening connection172 Connection of drain hose at indoor unit sideConnection of drain hose at drain up kit side Piping/Heat insulating material173 Check the draining174 For Installation Professionals 175Use for Indoor Unit Only Combination List of Adapter PartsCase of 4-way Ceiling Cassette RAV-SM **0 UT-E 176Case of Concealed Duct RAV-SM **0 BT-E Address No. setup table SW01 ProcedureSetup from the remote controller at the indoor unit side Setup by the switch on the adapter P.C. board178 To CustomersTCB-KP12CE TCB-KP22CE 179Parts List 180181 Installation of high-efficiency filter Setup of fan when building in the high-efficiency filter182 High-Efficiency Filter183 Setup of fan when building in the filter sold separatelyDeodorant Filter, Ammonium Filter Page Memo