Balcar R410A service manual AIR Ducting Work, Static pressure characteristics of each model, 103

Page 27

RAV-SM560, 561, 800, 801BT-E

RAV-SM1101, 1401BT-E

4 AIR DUCTING WORK

Static pressure characteristics of each model

Fig. 1 RAV-SM561BT (Round duct)

Standard air volume 780m³/h

 

140

 

 

 

 

 

 

 

 

 

 

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

static

pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

 

limit

 

 

 

2H

tap

 

 

Usable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

 

 

 

 

 

 

 

 

(Pa)

 

 

 

 

static

 

 

 

 

 

 

80

 

 

 

 

pressure

 

 

 

 

 

 

 

 

 

 

1H

 

 

 

Static pressure

 

 

 

 

 

 

 

tap

 

 

 

 

 

 

 

 

 

 

 

 

volume limit (Min.)

 

 

 

 

 

 

 

 

volume limit (Max.)

60

 

 

Standard

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

tap

 

 

 

 

40

Low

static

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

 

 

pressure

 

 

 

 

Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

20

 

 

Standard

 

tap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

tap

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

 

 

700

 

780

 

 

 

900

Air volume m³/h

Fig. 3 RAV-SM801BT (Round duct)

 

140

 

 

 

 

Standard air volume 1140m³/h

 

 

 

 

 

 

 

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

 

 

 

 

 

 

 

 

 

static

 

 

 

 

 

 

 

 

 

pressure

 

 

100

 

 

 

 

 

 

2H

tap

 

 

 

 

 

 

 

 

 

 

 

limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Usable

 

High

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

static

 

 

 

(Pa)

80

 

 

 

 

pressure

1H

tap

 

pressure

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

Static

(Min.)

 

 

Standard

 

 

(Max.)

 

 

 

 

 

 

 

 

 

 

 

H tap

 

 

 

 

40

limit

Low

static

 

 

limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

volume

 

 

 

H tap

 

 

volume

 

20

 

 

 

Standard L

 

 

 

 

Air

 

 

 

tap

 

 

Air

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

800

 

 

1000

1140

1200

1300

Air volume m³/h

Fig. 2 RAV-SM561BT (Square duct)

Standard air volume 780m³/h

 

140

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

static

pressure

 

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

limit

 

 

 

 

 

 

 

 

 

2H

tap

 

108

 

Usable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

 

High

static

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

 

 

 

 

 

 

1H

tap

 

(Pa)

 

 

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

(Min.)

 

Standard

 

 

 

 

 

 

 

(Max.)

60

 

 

 

 

H

tap

 

 

 

 

Static

volume limit

 

 

 

 

 

 

 

 

 

 

 

 

volume limit

 

 

Low

static

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

tap

 

 

 

Air

 

 

 

 

 

 

 

 

 

 

Air

 

 

 

 

Standard

 

 

 

 

 

 

 

20

 

 

 

L

tap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

 

 

700

 

 

 

780

 

 

900

Air volume m³/h

Fig. 4 RAV-SM801BT (Square duct)

Standard air volume 1140m³/h

 

140

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

 

 

 

 

 

 

120

 

 

 

static

 

pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2H

tap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

limit

 

 

 

 

 

 

 

100

 

Usable

 

High

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

static

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

 

 

 

 

 

1H

tap

 

 

 

 

 

 

 

 

 

 

 

(Pa)

80

 

 

 

 

 

 

 

 

 

Static pressure

 

limit (Min.)

 

 

Standard

 

 

 

 

limit (Max.)

60

 

 

H tap

 

 

 

 

 

 

 

 

 

 

 

 

Low

 

 

 

 

 

 

 

 

 

static

 

 

 

 

 

 

40

volume

 

 

pressure

H tap

 

volume

 

 

 

 

 

 

 

 

 

Standard L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air

 

 

tap

 

 

Air

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

800

 

 

1000

 

1140

1200

 

1300

Air volume m³/h

– 103 –

Image 27
Contents Split Type ∗∗ 1CT-E Type Indoor unit Outdoor unitDC motor AC motor Name 0BT-E ∗∗ 1BT-EContents Outdoor Installation ManualRAV-SP1100, 1400AT-E RAV-SM1100, 1400AT-E Precautions for SafetyNew Refrigerant Air Conditioner Installation To Disconnect the Appliance from Main Power SupplyAccessory and Refrigerant Accessory and Installation PartsRefrigerant Piping Before installation Selection of InstallationObstacle at front side Upper side is free Installation PlaceNecessary Space for Installation Obstacle at rear side Upper side is freeObstacle also at the upper side Installation of Outdoor UnitStandard installation Serial installation at front and rear sidesKnockout of Pipe Cover Optional Installation Parts Local ProcureRefrigerant Piping Connection For ReferencePipe Forming/End Positioning Refrigerant PipingOuter dia. of copper pipe Tightening torque Tightening of Connecting PartEvacuating Air PurgeVacuum pump How to open the valve Valve sizeCharge port Stripping length power cord and connecting cable How to wireElectrical Work Final Installation Checks Check and Test OperationSelf-Diagnosis by LED Indication Changes in the product and components New tools for R410ANew tools for R410A Applicable to R22 model Changes Indoor Part name ’ty Shape Part name ’ty Shape Standard wired remote ControllerSeparate sold parts RAV-SM560, 561, 800, 801BT-E RAV-SM1101, 1401BT-EConnect the connecting cable correctly Inappropriate grounding may cause electric shock Secure the space required to installation and servicing Selection of Installation PlaceInstallation space Selection of installation place AdviceInstallation procedure Installation of Indoor UnitRAV-SM1101, 1401BT DimensionExternal view 100Clamp mounting Removal of air filter Installation of remote controller Sold separatelyMounting of clamp Accessory Hanging down of indoor unitLedge ceiling concealed duct type Restriction to installationInstallation clearance Concealed duct typeStatic pressure characteristics of each model AIR Ducting Work103 RAV-SM1401BT Round duct RAV-SM1101BT Round ductConnecting method of the duct Points at installation work General cautions106 107 Mounting of remote controllerHanging of indoor unit Mounting of filter and canvas for suction portThermal-insulating process Drain Piping WorkPiping material Piping and cautionsAfter electric piping work Drain-upConnection of the drain hose Check of water drainTightening torque of flare pipe connections Permissible piping length and heatFlaring dia meter size a Unit mm Tightening connectionUse a vacuum pump Packed valve handling precautionsOpen valve fully Gas leak checkFor 801, 1101, 1401AT model 801, 1101, 1401 type valve at gas side112 113 114 Remote controller cablingCabling diagram CablingBefore test run How to execute a test runCase of wired remote controller Test RUNConfirmation and check TroubleshootingConfirmation of error history Procedure DescriptionApplicable Controls Automatic address117 Short plug position CN112, CN111, CN110 from the left Setup of external static pressureWhen using wireless remote controller To incorporate a filter sold separatelyChange of lighting time of filter sign To secure better effect of heating119 Clean the Return grilles with water INSTALLATION/SERVICING ToolsMaintenance Cleaning of Return grillePart name 121RAV-SM561, 801CT-E RAV-SM1101, 1401CT-E Part name ’ty Shape Usage122 123 Installation space Avoid installing in the following places124 Height of ceiling Case of wireless type801CT How to use attached installation pattern126 Model name 561CTDraw-out direction of pipe/cable Installation of hanging boltsKnockout hole of power cable take-in port Pipe knockout holeInstallation of indoor unit Adhesive inhibited Piping/Heat insulating materialDrain up Collective piping130 Connection of drain hose Thermal insulating processConnection of drain pipe Case of taking pipe from the left sideOuter diam. of copper pipe Refrigerant Piping and EvacuatingFlaring diam. meter size a Unit mm 131Gas leak check Piping with outdoor unitOpen the valve fully Refrigerant amount to be addedBe sure to connect earth wire. Grounding work Remote controller wiring133 134 Cable connection135 Wiring diagram136 137 138 Set data Case of installation to high ceiling139 Set data 0000140 Removal of suction grille 141Tools Cleaning of air filter Accessories 144 RBC-EXW21EHoliday setting indication mark Operation procedureProgram button Cancel button Timer set button146 147 148 149 RBC-AS21E150 AS21EAutomatic Cool/Heat 151 RBC-AX22CERemote Controller Signal Receiving Part152 Operation Section Display Section 153154 155 When a signalis correctlyreceived, Pisoundcan be heard To Use the Remote Controller Setting to Wall, etcHow to Check the Address How to Match the AddressPhenomenon Cause 157Start Phenomenon Cause Measures158 How to perform cabling of the remote controller Accessory partsRequirement for installation Multiple remote controllers Remote controller test run setup160 Program Weekly Timer161 Accessory partsRequirement to install the remote sensor How to install the remote sensorInstallation of sensor unit Accessory162 Slide switch How to perform cabling of sensor unitsHow to set the room temperature sensor How to set the address switchTest run How to set up filter sold separately of the high ceilingHow to handle the remote controller 164To Personnel Charged in Installation Work and Service Flap Never modify or repair the productCeiling panel ’ty ØM5mm x 40mm ØM4mm x 12mmFor wireless remote controller Installation of adjust corner capInstallation of suction grille Check after installation168 TCB-DP22CE169 Connect the connecting cable correctlyNew Refrigerant Air Conditioner Installation To Disconnect the Appliance from Main Power SupplyConnection of Elbow Piping KIT Before installation170 Knockout holeTightening connection How to install drain up kit171 Thermal insulating processPiping/Heat insulating material 172Connection of drain hose at indoor unit side Connection of drain hose at drain up kit sideCheck the draining 173174 Combination List of Adapter Parts For Installation Professionals175 Use for Indoor Unit Only176 Case of 4-way Ceiling Cassette RAV-SM **0 UT-ECase of Concealed Duct RAV-SM **0 BT-E Setup by the switch on the adapter P.C. board Address No. setup table SW01Procedure Setup from the remote controller at the indoor unit sideTo Customers 178179 TCB-KP12CE TCB-KP22CE180 Parts List181 High-Efficiency Filter Installation of high-efficiency filterSetup of fan when building in the high-efficiency filter 182Setup of fan when building in the filter sold separately 183Deodorant Filter, Ammonium Filter Page Memo