Balcar R410A Change of lighting time of filter sign, To secure better effect of heating, 119

Page 43

RAV-SM560, 561, 800, 801BT-E RAV-SM1101, 1401BT-E

Change of lighting time of filter sign

According to the installation condition, the lighting time of the filter sign (Notification of filter cleaning) can be changed.

Follow to the basic operation procedure

(1 2 3 4 5 6 ).

For the item code in Procedure 3, specify [01].

For the set data in Procedure 4, select the setup data of lighting time of filter sign to be changed from the table below.

Set data

Filter sign lighting time

 

 

0000

None

 

 

 

0001

150H

 

 

 

 

0002

2500H

(At shipment)

 

 

 

0003

5000H

 

 

 

 

0004

10000H

 

 

 

 

Check and test operation

Be sure to test the pipe connections for gas leak.

Check the flare nut connections, valve stem cap connections and service port cap connections for gas leak with a leak detector or some soap water.

To secure better effect of heating

When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room, the detection temperature of heating can be raised. Also use a circulator, etc. to circulate heat air near the ceiling.

Follow to the basic operation procedure

(1 2 3 4 5 6 ).

For the item code in Procedure 3, specify [06].

For the set data in Procedure 4, select the setup data of shift value of detection temperature to be set up from the table below.

Set data

Shift value of detection temp.

 

 

0000

No shift

 

 

0001

+1°C

 

 

0002

+2°C (At shipment)

 

 

0003

+3°C

 

 

0004

+4°C

 

 

0005

+5°C

 

 

0006

+6°C

 

 

– 119 –

Image 43
Contents Split Type ∗∗ 1CT-E Type Indoor unit Outdoor unitDC motor AC motor Name 0BT-E ∗∗ 1BT-EContents Outdoor Installation ManualRAV-SP1100, 1400AT-E RAV-SM1100, 1400AT-E Precautions for SafetyNew Refrigerant Air Conditioner Installation To Disconnect the Appliance from Main Power SupplyAccessory and Installation Parts Accessory and RefrigerantRefrigerant Piping Before installation Selection of InstallationObstacle at front side Upper side is free Installation PlaceNecessary Space for Installation Obstacle at rear side Upper side is freeObstacle also at the upper side Installation of Outdoor UnitStandard installation Serial installation at front and rear sidesKnockout of Pipe Cover Optional Installation Parts Local ProcureRefrigerant Piping Connection For ReferencePipe Forming/End Positioning Refrigerant PipingOuter dia. of copper pipe Tightening torque Tightening of Connecting PartAir Purge EvacuatingVacuum pump Valve size How to open the valveCharge port How to wire Stripping length power cord and connecting cableElectrical Work Check and Test Operation Final Installation ChecksSelf-Diagnosis by LED Indication New tools for R410A Changes in the product and componentsNew tools for R410A Applicable to R22 model Changes Indoor Part name ’ty Shape Part name ’ty Shape Standard wired remote ControllerSeparate sold parts RAV-SM560, 561, 800, 801BT-E RAV-SM1101, 1401BT-EConnect the connecting cable correctly Inappropriate grounding may cause electric shock Secure the space required to installation and servicing Selection of Installation PlaceInstallation space Selection of installation place AdviceInstallation procedure Installation of Indoor UnitRAV-SM1101, 1401BT DimensionExternal view 100Clamp mounting Removal of air filter Installation of remote controller Sold separatelyMounting of clamp Accessory Hanging down of indoor unitLedge ceiling concealed duct type Restriction to installationInstallation clearance Concealed duct typeAIR Ducting Work Static pressure characteristics of each model103 RAV-SM1401BT Round duct RAV-SM1101BT Round ductConnecting method of the duct General cautions Points at installation work106 107 Mounting of remote controllerHanging of indoor unit Mounting of filter and canvas for suction portThermal-insulating process Drain Piping WorkPiping material Piping and cautionsAfter electric piping work Drain-upConnection of the drain hose Check of water drainTightening torque of flare pipe connections Permissible piping length and heatFlaring dia meter size a Unit mm Tightening connectionUse a vacuum pump Packed valve handling precautionsOpen valve fully Gas leak check801, 1101, 1401 type valve at gas side For 801, 1101, 1401AT model112 113 114 Remote controller cablingCabling diagram CablingBefore test run How to execute a test runCase of wired remote controller Test RUNConfirmation and check TroubleshootingConfirmation of error history Procedure DescriptionAutomatic address Applicable Controls117 Short plug position CN112, CN111, CN110 from the left Setup of external static pressureWhen using wireless remote controller To incorporate a filter sold separatelyTo secure better effect of heating Change of lighting time of filter sign119 Clean the Return grilles with water INSTALLATION/SERVICING ToolsMaintenance Cleaning of Return grillePart name 121RAV-SM561, 801CT-E RAV-SM1101, 1401CT-E Part name ’ty Shape Usage122 123 Avoid installing in the following places Installation space124 Height of ceiling Case of wireless type801CT How to use attached installation pattern126 Model name 561CTDraw-out direction of pipe/cable Installation of hanging boltsKnockout hole of power cable take-in port Pipe knockout holeInstallation of indoor unit Adhesive inhibited Piping/Heat insulating materialDrain up Collective piping130 Connection of drain hose Thermal insulating processConnection of drain pipe Case of taking pipe from the left sideOuter diam. of copper pipe Refrigerant Piping and EvacuatingFlaring diam. meter size a Unit mm 131Gas leak check Piping with outdoor unitOpen the valve fully Refrigerant amount to be addedRemote controller wiring Be sure to connect earth wire. Grounding work133 134 Cable connection135 Wiring diagram136 137 138 Set data Case of installation to high ceiling139 Set data 0000140 141 Removal of suction grilleTools Cleaning of air filter Accessories 144 RBC-EXW21EHoliday setting indication mark Operation procedureProgram button Cancel button Timer set button146 147 148 149 RBC-AS21EAS21E 150Automatic Cool/Heat 151 RBC-AX22CESignal Receiving Part Remote Controller152 Operation Section Display Section 153154 155 When a signalis correctlyreceived, Pisoundcan be heard To Use the Remote Controller Setting to Wall, etcHow to Check the Address How to Match the AddressPhenomenon Cause 157Start Phenomenon Cause Measures158 How to perform cabling of the remote controller Accessory partsRequirement for installation Multiple remote controllers Remote controller test run setup160 Program Weekly Timer161 Accessory partsRequirement to install the remote sensor How to install the remote sensorAccessory Installation of sensor unit162 Slide switch How to perform cabling of sensor unitsHow to set the room temperature sensor How to set the address switchTest run How to set up filter sold separately of the high ceilingHow to handle the remote controller 164To Personnel Charged in Installation Work and Service Flap Never modify or repair the productCeiling panel ’ty ØM5mm x 40mm ØM4mm x 12mmFor wireless remote controller Installation of adjust corner capInstallation of suction grille Check after installation168 TCB-DP22CE169 Connect the connecting cable correctlyNew Refrigerant Air Conditioner Installation To Disconnect the Appliance from Main Power SupplyConnection of Elbow Piping KIT Before installation170 Knockout holeTightening connection How to install drain up kit171 Thermal insulating processPiping/Heat insulating material 172Connection of drain hose at indoor unit side Connection of drain hose at drain up kit sideCheck the draining 173174 Combination List of Adapter Parts For Installation Professionals175 Use for Indoor Unit OnlyCase of 4-way Ceiling Cassette RAV-SM **0 UT-E 176Case of Concealed Duct RAV-SM **0 BT-E Setup by the switch on the adapter P.C. board Address No. setup table SW01Procedure Setup from the remote controller at the indoor unit sideTo Customers 178179 TCB-KP12CE TCB-KP22CE180 Parts List181 High-Efficiency Filter Installation of high-efficiency filterSetup of fan when building in the high-efficiency filter 182183 Setup of fan when building in the filter sold separatelyDeodorant Filter, Ammonium Filter Page Memo