Concealed Duct type
Deodorant Filter, Ammonium Filter | Installation Manual |
Installation of filter sold separately |
|
|
1 Remove the air filter, and install a filter sold separately to the |
| Filter sold |
suction port. |
| separately |
Push the filter sold separately completely up to the end. |
|
|
Check that the rear side is hanged to the hook. |
|
|
2 Install the air filter | Indoor unit | Hook |
Be sure to fix the air filter with clamps in order to prevent falling. |
| |
| Filter sold separately | |
(Clamps are attached to the indoor unit.) |
| |
|
| • Deodorant filter |
Deodorant Filter | Model: |
| |
|
NOTES
NOTE | • Ammonium filter |
Air filter |
These filter cannot be reused even if it is washed.
| |
Ammonium Filter | Model: |
| |
| |
|
|
•Do not unpack the filter until you use it. (Otherwise, life of the deodorant filter or ammonium filter is shortened.)
•Keep this Manual with Owner’s Manual of the indoor unit.
Maintenance of filter sold separately
• Clean the filter sold separately once per 2 months.
1 Take out the filter sold separately in the reverse order of “Installation of filter sold separately”.
2 Sweep away the dust of the filter sold separately with a cleaner.
3
To install a filter sold separately, be sure to set the fan referring the following description.
*The filter sold separately cannot be installed to an air conditioner built in with auxiliary electric heater.
– 183 –
Safety Cautions
•Before installation work, read thoroughly this “Safety Cautions” to install the air conditioner correctly.
•This “Safety Cautions” describes the important contents concerned to the safety. Be sure to keep in mind these items. Symbols and meanings are as described below.
WARNING | Indicates “User may be dead or seriously injured (*1) if it is incorrectly used.” | |
|
| |
CAUTION | Indicates “It is assumed that user may be injured (*2) or property damage (*3) may occur if it is | |
incorrectly used.” | ||
| ||
|
|
*1: “Serious injury” means a disease which has an
*2: “Injury” means hurt, burn, electric shock, etc. which does not require hospitalization or
*3: “Property damage” means enlarged damage concerned to house, household effects, domestic animal, pet, etc.
Explanation of picture symbols
indicates prohibition (prohibited action).
The concrete prohibited action is indicated with picture or sentence in or near the picture symbol.
indicates that the forced instructed action (Act necessarily).
The concrete instructed action is indicated with picture or sentence in or near the picture symbol.
indicates an item with care.
Install the filter sold separately.
Setup of fan when building in the filter sold separately:
Necessary at initial installation only
Two methods are provided for setup, one is to use a wired remote controller sold separately | SET DATA | CODE No. | |
|
|
| |
and the other is to exchange the short plug on the indoor microcomputer P.C. board. |
| UNIT No. |
|
SETTING | R.C. No. |
| |
|
| ||
|
|
|
|
[Using a wired remote controller sold separately] | 4 |
|
| 2 | |
(Procedure) Perform the setup while the equipment stops. |
|
| |||
1 Push SET + CL + | buttons concurrently for 4 seconds or more. | 6 |
| UNIT | 3 |
The firstly displayed unit No. is the master indoor unit address of the group control. | 1 | SET CL |
| ||
In this time, the fan of the selected indoor unit only operates. |
|
|
| 5 |
2 | Every pushing UNIT | button, No. of the group control units are displayed in | * | Setup can be performed only by the | ||||||
|
| wired remote controller. If setup is not | ||||||||
| order. |
|
|
|
|
|
| |||
|
|
|
|
|
|
| performed, air volume is decreased and | |||
| In this time, the fan of the selected indoor unit only operates. |
|
| |||||||
3 |
|
| dewing occurs. | |||||||
|
|
|
|
|
|
| ||||
Using set temperature | and | buttons, specify the item code “5d”. | • | Item code 5d | ||||||
4 | Using timer time | and | buttons, select from the set data. |
|
| Set data |
| Filter sold separately | ||
|
|
| ||||||||
| For contents of the setup data, refer to the table at the right. |
|
|
| ||||||
5 |
|
| 0000 |
| Standard filter (At shipment) | |||||
Push SET | button. |
|
|
|
|
|
| |||
|
|
|
|
|
|
| ||||
| (When flashing display changes to lighting display, the setup completes.) |
|
|
|
| |||||
6 |
|
| 0001 |
| ||||||
|
|
|
|
|
|
|
| |||
Pushing | button returns the state to the normal stop state. |
|
|
| ||||||
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
[Exchange of short plug on indoor microcomputer P.C. board]
The concrete item to be cautioned is indicated with picture or sentence in or near the picture symbol.
WARNING | CAUTION |
• Do not put a plastic bag including filter on a place where | • Install the suction grille surely to the main unit. |
hands of a small child can reach. | If an incomplete installation is performed, | |
If the child puts the bag on his head, it may seal | ||
falling of the suction grille causes an injury. | ||
his mouth or nose resulting in choke of death. | ||
|
Specifications
Deodorant filter | TCB- | TCB- | TCB- | TCB- | Ammonium filter | TCB- | TCB- |
| TCB- | TCB- |
model name | DF11BE | DF21BE | DF31BE | DF41BE | model name | |||||
|
|
|
|
|
|
|
|
|
|
|
Conformed air | — | 561BT | 801BT | 1101BT | Conformed air | — | 561BT |
| 801BT | 1101BT |
conditioner model name | to | conditioner model name |
| to | ||||||
|
|
| 1401BT |
|
|
|
| 1401BT | ||
|
|
|
|
|
|
|
|
|
|
|
Quantity | 1 | 1 | 2 | 2 | Quantity | 1 | 1 |
| 2 | 2 |
|
|
|
|
|
|
|
|
|
|
|
Initial deodorant |
| 85% |
| Initial deodorant |
| 95% |
|
| ||
performance |
|
| performance |
|
|
| ||||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
Deodorant durable |
| Approx. 9 months |
| Deodorant durable |
| Approx. 15 months |
| |||
performance |
|
| performance |
|
| |||||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
To exchange the static pressure, there is a method other than the abovementioned method by wired remote controller, which is to shift the short plug on the indoor microcomputer P.C. board as shown in the following table. Adopt this method in case of using a wireless remote controller, etc.
*However, after exchanging once, be careful to shift the short plug to the standard position (At shipment) in order to return to the standard setup (follow to E2PROM setup) though the setup for high
•Select with shifting of the short plug on the indoor unit microcomputer P.C. board.
Short plug position (CN112, CN111, CN110 from the left)
*1 Resistance of high- efficiency filter 65 and 90, deodorant filter, or ammonium filter is equivalent to 30Pa. Therefore, set the resistance (external static pressure) of a duct to be connected to 40Pa.
Short plug position |
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
| External | Filter sold separately |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| static |
|
| |
|
|
|
|
|
|
|
|
|
| pressure |
|
|
|
|
| Short Open |
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
CN112 CN111 CN110 | 40Pa | Standard filter | |||||||||||
|
|
|
|
|
|
|
|
|
| Standard | (At shipment) | ||
|
|
|
|
|
|
|
|
|
| (At shipment) | |||
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| pressure 1 | *1 | ||
CN112 CN111 CN110 | 70Pa |
|
| ||||||||||
|
|
|
|
|
|
|
|
|
| High static- |
|
| |
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| 100Pa | Deodorant filter | 21, | 21, |
|
|
|
|
|
|
|
|
|
|
| Ammonium filter |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CN112 CN111 CN110 |
|
| 31, | 31, | |||||||||
|
|
|
|
|
|
|
|
|
| High static- | |||
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| pressure 2 | 41BE | ||
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| ||
CN112 CN111 CN110 | 20Pa |
| |||||||||||
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
| Low static- |
|
| |
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| pressure |
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|