Balcar R410A service manual 183, Deodorant Filter, Ammonium Filter

Page 107

Concealed Duct type

Deodorant Filter, Ammonium Filter

Installation Manual

Installation of filter sold separately

 

 

1 Remove the air filter, and install a filter sold separately to the

 

Filter sold

suction port.

 

separately

Push the filter sold separately completely up to the end.

 

 

Check that the rear side is hanged to the hook.

 

 

2 Install the air filter

Indoor unit

Hook

Be sure to fix the air filter with clamps in order to prevent falling.

 

 

Filter sold separately

(Clamps are attached to the indoor unit.)

 

 

 

• Deodorant filter

Deodorant Filter

Model: TCB-DF11BE

 

TCB-DF21BE

 

TCB-DF31BE

NOTES

NOTE

• Ammonium filter

Air filter

These filter cannot be reused even if it is washed.

 

TCB-DF41BE

Ammonium Filter

Model: TCB-DF11BE-AM

 

TCB-DF21BE-AM

 

TCB-DF31BE-AM

 

TCB-DF41BE-AM

Do not unpack the filter until you use it. (Otherwise, life of the deodorant filter or ammonium filter is shortened.)

Keep this Manual with Owner’s Manual of the indoor unit.

Maintenance of filter sold separately

• Clean the filter sold separately once per 2 months.

1 Take out the filter sold separately in the reverse order of “Installation of filter sold separately”.

2 Sweep away the dust of the filter sold separately with a cleaner.

3

To install a filter sold separately, be sure to set the fan referring the following description.

*The filter sold separately cannot be installed to an air conditioner built in with auxiliary electric heater.

– 183 –

Safety Cautions

Before installation work, read thoroughly this “Safety Cautions” to install the air conditioner correctly.

This “Safety Cautions” describes the important contents concerned to the safety. Be sure to keep in mind these items. Symbols and meanings are as described below.

WARNING

Indicates “User may be dead or seriously injured (*1) if it is incorrectly used.”

 

 

CAUTION

Indicates “It is assumed that user may be injured (*2) or property damage (*3) may occur if it is

incorrectly used.”

 

 

 

*1: “Serious injury” means a disease which has an after-effect or requires hospitalization or long-term going to the hospital for treatment, such as loss of sight, burn (by high temperature or low temperature), electric shock, fracture, poisoning, etc.

*2: “Injury” means hurt, burn, electric shock, etc. which does not require hospitalization or long-term going to the hospital for treatment.

*3: “Property damage” means enlarged damage concerned to house, household effects, domestic animal, pet, etc.

Explanation of picture symbols

indicates prohibition (prohibited action).

The concrete prohibited action is indicated with picture or sentence in or near the picture symbol.

indicates that the forced instructed action (Act necessarily).

The concrete instructed action is indicated with picture or sentence in or near the picture symbol.

indicates an item with care.

Install the filter sold separately.

Setup of fan when building in the filter sold separately:

Necessary at initial installation only

Two methods are provided for setup, one is to use a wired remote controller sold separately

SET DATA

CODE No.

 

 

 

and the other is to exchange the short plug on the indoor microcomputer P.C. board.

 

UNIT No.

 

SETTING

R.C. No.

 

 

 

 

 

 

 

[Using a wired remote controller sold separately]

4

 

 

2

(Procedure) Perform the setup while the equipment stops.

 

 

1 Push SET + CL +

buttons concurrently for 4 seconds or more.

6

 

UNIT

3

The firstly displayed unit No. is the master indoor unit address of the group control.

1

SET CL

 

In this time, the fan of the selected indoor unit only operates.

 

 

 

5

2

Every pushing UNIT

button, No. of the group control units are displayed in

*

Setup can be performed only by the

 

 

wired remote controller. If setup is not

 

order.

 

 

 

 

 

 

 

 

 

 

 

 

 

performed, air volume is decreased and

 

In this time, the fan of the selected indoor unit only operates.

 

 

3

 

 

dewing occurs.

 

 

 

 

 

 

 

Using set temperature

and

buttons, specify the item code “5d”.

Item code 5d

4

Using timer time

and

buttons, select from the set data.

 

 

Set data

 

Filter sold separately

 

 

 

 

For contents of the setup data, refer to the table at the right.

 

 

 

5

 

 

0000

 

Standard filter (At shipment)

Push SET

button.

 

 

 

 

 

 

 

 

 

 

 

 

 

High-efficiency filter (65%)

 

(When flashing display changes to lighting display, the setup completes.)

 

 

 

 

6

 

 

0001

 

(TCB-UFM11BE to UFM41BE)

 

 

 

 

 

 

 

 

Pushing

button returns the state to the normal stop state.

 

 

 

High-efficiency filter (90%)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(TCB-UFH51BE to UFH81BE)

 

 

 

 

 

 

 

 

 

 

 

[Exchange of short plug on indoor microcomputer P.C. board]

The concrete item to be cautioned is indicated with picture or sentence in or near the picture symbol.

WARNING

CAUTION

• Do not put a plastic bag including filter on a place where

• Install the suction grille surely to the main unit.

hands of a small child can reach.

If an incomplete installation is performed,

If the child puts the bag on his head, it may seal

falling of the suction grille causes an injury.

his mouth or nose resulting in choke of death.

 

Specifications

Deodorant filter

TCB-

TCB-

TCB-

TCB-

Ammonium filter

TCB-

TCB-

 

TCB-

TCB-

model name

DF11BE

DF21BE

DF31BE

DF41BE

model name

UFH11BE-AM

UFH21BE-AM

UFH31BE-AM

UFH41BE-AM

 

 

 

 

 

 

 

 

 

 

 

Conformed air

561BT

801BT

1101BT

Conformed air

561BT

 

801BT

1101BT

conditioner model name

to

conditioner model name

 

to

 

 

 

1401BT

 

 

 

 

1401BT

 

 

 

 

 

 

 

 

 

 

 

Quantity

1

1

2

2

Quantity

1

1

 

2

2

 

 

 

 

 

 

 

 

 

 

 

Initial deodorant

 

85%

 

Initial deodorant

 

95%

 

 

performance

 

 

performance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Deodorant durable

 

Approx. 9 months

 

Deodorant durable

 

Approx. 15 months

 

performance

 

 

performance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To exchange the static pressure, there is a method other than the abovementioned method by wired remote controller, which is to shift the short plug on the indoor microcomputer P.C. board as shown in the following table. Adopt this method in case of using a wireless remote controller, etc.

*However, after exchanging once, be careful to shift the short plug to the standard position (At shipment) in order to return to the standard setup (follow to E2PROM setup) though the setup for high static-pressure 1, high static-pressure 2, or low static-pressure can be arbitrarily performed. It is necessary to rewrite data from the wired remote controller sold separately in the set data “0000”.

Select with shifting of the short plug on the indoor unit microcomputer P.C. board.

Short plug position (CN112, CN111, CN110 from the left)

*1 Resistance of high- efficiency filter 65 and 90, deodorant filter, or ammonium filter is equivalent to 30Pa. Therefore, set the resistance (external static pressure) of a duct to be connected to 40Pa.

Short plug position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External

Filter sold separately

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

static

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

Short Open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TCB-DF11,

TCB-DF11,

CN112 CN111 CN110

40Pa

Standard filter

 

 

 

 

 

 

 

 

 

 

Standard

(At shipment)

 

 

 

 

 

 

 

 

 

 

(At shipment)

Zeolite-3G deodrant filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure 1

*1

CN112 CN111 CN110

70Pa

 

 

 

 

 

 

 

 

 

 

 

 

High static-

High-efficiency filter 65

 

 

 

 

 

 

 

 

 

 

 

 

High-efficiency filter 90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100Pa

Deodorant filter

21,

21,

 

 

 

 

 

 

 

 

 

 

 

Ammonium filter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN112 CN111 CN110

 

 

31,

31,

 

 

 

 

 

 

 

 

 

 

High static-

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure 2

41BE-AM

41BE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN112 CN111 CN110

20Pa

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low static-

——

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEBF-E

Image 107
Contents Split Type ∗∗ 1CT-E Type Indoor unit Outdoor unitDC motor AC motor Name 0BT-E ∗∗ 1BT-EContents Outdoor Installation ManualRAV-SP1100, 1400AT-E RAV-SM1100, 1400AT-E Precautions for SafetyNew Refrigerant Air Conditioner Installation To Disconnect the Appliance from Main Power SupplyRefrigerant Piping Accessory and RefrigerantAccessory and Installation Parts Before installation Selection of InstallationObstacle at front side Upper side is free Installation PlaceNecessary Space for Installation Obstacle at rear side Upper side is freeObstacle also at the upper side Installation of Outdoor UnitStandard installation Serial installation at front and rear sidesKnockout of Pipe Cover Optional Installation Parts Local ProcureRefrigerant Piping Connection For ReferencePipe Forming/End Positioning Refrigerant PipingOuter dia. of copper pipe Tightening torque Tightening of Connecting PartVacuum pump EvacuatingAir Purge Charge port How to open the valveValve size Electrical Work Stripping length power cord and connecting cableHow to wire Self-Diagnosis by LED Indication Final Installation ChecksCheck and Test Operation New tools for R410A Applicable to R22 model Changes Changes in the product and componentsNew tools for R410A Indoor Part name ’ty Shape Part name ’ty Shape Standard wired remote ControllerSeparate sold parts RAV-SM560, 561, 800, 801BT-E RAV-SM1101, 1401BT-EConnect the connecting cable correctly Inappropriate grounding may cause electric shock Secure the space required to installation and servicing Selection of Installation PlaceInstallation space Selection of installation place AdviceInstallation procedure Installation of Indoor UnitRAV-SM1101, 1401BT DimensionExternal view 100Clamp mounting Removal of air filter Installation of remote controller Sold separatelyMounting of clamp Accessory Hanging down of indoor unitLedge ceiling concealed duct type Restriction to installationInstallation clearance Concealed duct type103 Static pressure characteristics of each modelAIR Ducting Work RAV-SM1401BT Round duct RAV-SM1101BT Round ductConnecting method of the duct 106 Points at installation workGeneral cautions 107 Mounting of remote controllerHanging of indoor unit Mounting of filter and canvas for suction portThermal-insulating process Drain Piping WorkPiping material Piping and cautionsAfter electric piping work Drain-upConnection of the drain hose Check of water drainTightening torque of flare pipe connections Permissible piping length and heatFlaring dia meter size a Unit mm Tightening connectionUse a vacuum pump Packed valve handling precautionsOpen valve fully Gas leak check112 For 801, 1101, 1401AT model801, 1101, 1401 type valve at gas side 113 114 Remote controller cablingCabling diagram CablingBefore test run How to execute a test runCase of wired remote controller Test RUNConfirmation and check TroubleshootingConfirmation of error history Procedure Description117 Applicable ControlsAutomatic address Short plug position CN112, CN111, CN110 from the left Setup of external static pressureWhen using wireless remote controller To incorporate a filter sold separately119 Change of lighting time of filter signTo secure better effect of heating Clean the Return grilles with water INSTALLATION/SERVICING ToolsMaintenance Cleaning of Return grillePart name 121RAV-SM561, 801CT-E RAV-SM1101, 1401CT-E Part name ’ty Shape Usage122 123 124 Installation spaceAvoid installing in the following places Height of ceiling Case of wireless type801CT How to use attached installation pattern126 Model name 561CTDraw-out direction of pipe/cable Installation of hanging boltsKnockout hole of power cable take-in port Pipe knockout holeInstallation of indoor unit Adhesive inhibited Piping/Heat insulating materialDrain up Collective piping130 Connection of drain hose Thermal insulating processConnection of drain pipe Case of taking pipe from the left sideOuter diam. of copper pipe Refrigerant Piping and EvacuatingFlaring diam. meter size a Unit mm 131Gas leak check Piping with outdoor unitOpen the valve fully Refrigerant amount to be added133 Be sure to connect earth wire. Grounding workRemote controller wiring 134 Cable connection135 Wiring diagram136 137 138 Set data Case of installation to high ceiling139 Set data 0000140 Tools Removal of suction grille141 Cleaning of air filter Accessories 144 RBC-EXW21EHoliday setting indication mark Operation procedureProgram button Cancel button Timer set button146 147 148 149 RBC-AS21EAutomatic Cool/Heat 150AS21E 151 RBC-AX22CE152 Remote ControllerSignal Receiving Part Operation Section Display Section 153154 155 When a signalis correctlyreceived, Pisoundcan be heard To Use the Remote Controller Setting to Wall, etcHow to Check the Address How to Match the AddressPhenomenon Cause 157Start Phenomenon Cause Measures158 How to perform cabling of the remote controller Accessory partsRequirement for installation Multiple remote controllers Remote controller test run setup160 Program Weekly Timer161 Accessory partsRequirement to install the remote sensor How to install the remote sensor162 Installation of sensor unitAccessory Slide switch How to perform cabling of sensor unitsHow to set the room temperature sensor How to set the address switchTest run How to set up filter sold separately of the high ceilingHow to handle the remote controller 164To Personnel Charged in Installation Work and Service Flap Never modify or repair the productCeiling panel ’ty ØM5mm x 40mm ØM4mm x 12mmFor wireless remote controller Installation of adjust corner capInstallation of suction grille Check after installation168 TCB-DP22CE169 Connect the connecting cable correctlyNew Refrigerant Air Conditioner Installation To Disconnect the Appliance from Main Power SupplyConnection of Elbow Piping KIT Before installation170 Knockout holeTightening connection How to install drain up kit171 Thermal insulating processPiping/Heat insulating material 172Connection of drain hose at indoor unit side Connection of drain hose at drain up kit sideCheck the draining 173174 Combination List of Adapter Parts For Installation Professionals175 Use for Indoor Unit OnlyCase of Concealed Duct RAV-SM **0 BT-E 176Case of 4-way Ceiling Cassette RAV-SM **0 UT-E Setup by the switch on the adapter P.C. board Address No. setup table SW01Procedure Setup from the remote controller at the indoor unit sideTo Customers 178179 TCB-KP12CE TCB-KP22CE180 Parts List181 High-Efficiency Filter Installation of high-efficiency filterSetup of fan when building in the high-efficiency filter 182Deodorant Filter, Ammonium Filter Setup of fan when building in the filter sold separately183 Page Memo