Balcar R410A Be sure to connect earth wire. Grounding work, Remote controller wiring, 133

Page 57

RAV-SM561, 801CT-E

RAV-SM1101, 1401CT-E

5 ELECTRICAL WORK

WARNING

1.Using the specified cables, ensure to connect the wires, and fix wires securely so that the external tension to the cables do not affect the connecting part of the terminals.

Incomplete connection or fixation may cause a fire, etc.

2.Be sure to connect earth wire. (Grounding work)

Do not connect the earth wire to gas pipe, city water pipe, lightning rod, or the earth wire of telephone. Incomplete grounding causes an electric shock.

3.For electric work, strictly follow the Local Regulation in each country and the Installation Manual, and use an exclusive circuit.

Capacity shortage of power circuit or incomplete installation may cause an electric shock or a fire.

CAUTIONS

This indoor unit has no power cord.

If incorrect/incomplete wiring is carried out, it will cause an electrical fire or smoke.

Be sure to install an earth leakage breaker that is not tripped by shock waves. If an earth leakage breaker is not installed, an electric shock may be caused.

Be sure to use the cord clamps attached to the product.

Do not damage or scratch the conductive core and inner insulator of power and inter-connecting cables when peeling them.

Be sure to comply with local regulations on running the wire from outdoor unit to indoor unit (size of wire and wiring method etc.)

Use the power cord and Inter-connecting cable of specified thickness, type, and protective devices required.

REQUIREMENT

For power supply wiring, strictly conform to the Local Regulation in each country.

For wiring of power supply of the outdoor units, follow the Installation Manual of each outdoor unit.

Never connect 220–240V power to the terminal blocks ( A , B , etc.) for control wiring. (Otherwise, the system will fail.)

Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe. The coating may melt resulting in an accident.

After connecting cables to the terminal blocks, provide a trap and fix cables with the cable clamp.

Run the refrigerant piping line and control wiring line in the same line.

Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes.

Remote controller wiring

2-core non polarity cable is used for the remote controller wiring.

How to wire

1.Connect the connecting cable to the terminal as identified with their respective numbers on the terminal block of indoor and outdoor unit. H07 RN-F or 245 IEC 66 (1.5 mm2 or more)

2.Mount a leakage breaker.

3.Insulate the unsheathed redundant cords (conductors) with tape.

4.For inter-unit wiring, do not use a wire jointed to another on the way.

5.Fix the cable with cord clamp.

– 133 –

Image 57
Contents Split Type DC motor AC motor Type Indoor unit Outdoor unitName 0BT-E ∗∗ 1BT-E ∗∗ 1CT-EContents Outdoor Installation ManualNew Refrigerant Air Conditioner Installation Precautions for SafetyTo Disconnect the Appliance from Main Power Supply RAV-SP1100, 1400AT-E RAV-SM1100, 1400AT-EAccessory and Refrigerant Accessory and Installation PartsRefrigerant Piping Before installation Selection of InstallationNecessary Space for Installation Installation PlaceObstacle at rear side Upper side is free Obstacle at front side Upper side is freeStandard installation Installation of Outdoor UnitSerial installation at front and rear sides Obstacle also at the upper sideRefrigerant Piping Connection Optional Installation Parts Local ProcureFor Reference Knockout of Pipe CoverPipe Forming/End Positioning Refrigerant PipingOuter dia. of copper pipe Tightening torque Tightening of Connecting PartEvacuating Air PurgeVacuum pump How to open the valve Valve sizeCharge port Stripping length power cord and connecting cable How to wireElectrical Work Final Installation Checks Check and Test OperationSelf-Diagnosis by LED Indication Changes in the product and components New tools for R410ANew tools for R410A Applicable to R22 model Changes Indoor Separate sold parts Part name ’ty Shape Standard wired remote ControllerRAV-SM560, 561, 800, 801BT-E RAV-SM1101, 1401BT-E Part name ’ty ShapeConnect the connecting cable correctly Inappropriate grounding may cause electric shock Installation space Selection of installation place Selection of Installation PlaceAdvice Secure the space required to installation and servicingInstallation procedure Installation of Indoor UnitExternal view Dimension100 RAV-SM1101, 1401BTMounting of clamp Accessory Installation of remote controller Sold separatelyHanging down of indoor unit Clamp mounting Removal of air filterInstallation clearance Restriction to installationConcealed duct type Ledge ceiling concealed duct typeStatic pressure characteristics of each model AIR Ducting Work103 RAV-SM1401BT Round duct RAV-SM1101BT Round ductConnecting method of the duct Points at installation work General cautions106 Hanging of indoor unit Mounting of remote controllerMounting of filter and canvas for suction port 107Piping material Drain Piping WorkPiping and cautions Thermal-insulating processConnection of the drain hose Drain-upCheck of water drain After electric piping workFlaring dia meter size a Unit mm Permissible piping length and heatTightening connection Tightening torque of flare pipe connectionsOpen valve fully Packed valve handling precautionsGas leak check Use a vacuum pumpFor 801, 1101, 1401AT model 801, 1101, 1401 type valve at gas side112 113 Cabling diagram Remote controller cablingCabling 114Case of wired remote controller How to execute a test runTest RUN Before test runConfirmation of error history TroubleshootingProcedure Description Confirmation and checkApplicable Controls Automatic address117 When using wireless remote controller Setup of external static pressureTo incorporate a filter sold separately Short plug position CN112, CN111, CN110 from the leftChange of lighting time of filter sign To secure better effect of heating119 Maintenance INSTALLATION/SERVICING ToolsCleaning of Return grille Clean the Return grilles with waterRAV-SM561, 801CT-E RAV-SM1101, 1401CT-E 121Part name ’ty Shape Usage Part name122 123 Installation space Avoid installing in the following places124 Height of ceiling Case of wireless type126 How to use attached installation patternModel name 561CT 801CTKnockout hole of power cable take-in port Installation of hanging boltsPipe knockout hole Draw-out direction of pipe/cableInstallation of indoor unit Drain up Piping/Heat insulating materialCollective piping Adhesive inhibited Connection of drain pipe Connection of drain hose Thermal insulating process Case of taking pipe from the left side 130Flaring diam. meter size a Unit mm Refrigerant Piping and Evacuating131 Outer diam. of copper pipeOpen the valve fully Piping with outdoor unitRefrigerant amount to be added Gas leak checkBe sure to connect earth wire. Grounding work Remote controller wiring133 134 Cable connection135 Wiring diagram136 137 138 139 Case of installation to high ceilingSet data 0000 Set data140 Removal of suction grille 141Tools Cleaning of air filter Accessories 144 RBC-EXW21EProgram button Cancel button Operation procedureTimer set button Holiday setting indication mark146 147 148 149 RBC-AS21E150 AS21EAutomatic Cool/Heat 151 RBC-AX22CERemote Controller Signal Receiving Part152 Operation Section Display Section 153154 155 How to Check the Address To Use the Remote Controller Setting to Wall, etcHow to Match the Address When a signalis correctlyreceived, Pisoundcan be heardStart 157Phenomenon Cause Measures Phenomenon Cause158 Requirement for installation Multiple remote controllers Accessory partsRemote controller test run setup How to perform cabling of the remote controller160 Program Weekly TimerRequirement to install the remote sensor Accessory partsHow to install the remote sensor 161Installation of sensor unit Accessory162 How to set the room temperature sensor How to perform cabling of sensor unitsHow to set the address switch Slide switchHow to handle the remote controller How to set up filter sold separately of the high ceiling164 Test runTo Personnel Charged in Installation Work and Service Ceiling panel Never modify or repair the product’ty ØM5mm x 40mm ØM4mm x 12mm FlapInstallation of suction grille Installation of adjust corner capCheck after installation For wireless remote controller168 TCB-DP22CENew Refrigerant Air Conditioner Installation Connect the connecting cable correctlyTo Disconnect the Appliance from Main Power Supply 169170 Before installationKnockout hole Connection of Elbow Piping KIT171 How to install drain up kitThermal insulating process Tightening connectionConnection of drain hose at indoor unit side 172Connection of drain hose at drain up kit side Piping/Heat insulating materialCheck the draining 173174 175 For Installation ProfessionalsUse for Indoor Unit Only Combination List of Adapter Parts176 Case of 4-way Ceiling Cassette RAV-SM **0 UT-ECase of Concealed Duct RAV-SM **0 BT-E Procedure Address No. setup table SW01Setup from the remote controller at the indoor unit side Setup by the switch on the adapter P.C. boardTo Customers 178179 TCB-KP12CE TCB-KP22CE180 Parts List181 Setup of fan when building in the high-efficiency filter Installation of high-efficiency filter182 High-Efficiency FilterSetup of fan when building in the filter sold separately 183Deodorant Filter, Ammonium Filter Page Memo