Balcar R410A 156, To Use the Remote Controller Setting to Wall, etc, How to Check the Address

Page 80

– 156 –

HOW TO HANDLE THE REMOTE CONTROLLER

Direct the transmitter of the remote controller toward the sensor (indoor unit body). When the signal is normally received, “Pi” sound is heard once.

(“Pi, pi” sounds are heard only when the operation has started.)

The standard distance which the signal can be received is approx. 7m. The distance differs a little according to the capacity of the battery, etc.

Be careful there is not something to block the signal between the sensor (indoor unit body) and the remote controller.

Do not put the remote controller on the place exposed to the direct sunlight or air from the air conditioner or near the stove, etc.

Do not drop, throw, or clean with water the remote controller.

The signal may be accepted in a room where the electronic instantaneous-ON type or inverter type florescent light is set. For details, contact the shop which you purchased the air conditioner.

To Use the Remote Controller Setting to Wall, etc.

Check a signal is received correctly by pushing Start/Stop button at the position to be fixed.

To take off remote controller, pull it toward you.

Fix the remote controller

Setting method of

holder with the screws.

remote controller

 

Put on.

Mounting screw

1

 

Truss tapping

 

Push.

2

Remote controller holder

HOW TO USE THE REMOTE CONTROLLER CORRECTLY

Set the remote controller so that it is not excessively far from the sensor

(indoor unit), otherwise a malfunction is caused.

Be sure to set the remote controller in the same room where the sensor (indoor unit) is installed.

Direct the remote controller toward the sensor (indoor unit) for operation.

When a signalis correctlyreceived, “Pi”soundcan be heard.

Avoid to set the remote controller at a place where it is covered with curtain, etc.

ADDRESS

When the multiple indoor units corresponding to the wireless remote controller are installed in the same room, an address can be set up to prevent an interference.

Matching the address switch of the sensor with number of the remote controller ad- dress, Max. 6 indoor units can be controlled by the corresponding remote controller individually.

The address switch for receiving the signal is prepared to the sensor (inside of panel or indoor unit) and the address switch for sending the signal is prepared to the remote controller. For details, contact the shop which you purchased the air conditioner.

How to Check the Address

When pushing ADR button on the remote controller, the present address is displayed on the display section of the remote controller. If this address matches with the address of the sensor (inside of panel or indoor unit), a buzzer sounds.

(When ALL is displayed, buzzer sound is necessarily heard.)

When ALL is displayed, the air conditioner can be operated regardless of any address of the sensor (inside of the indoor unit). Send the signal by directing the remote controller toward the sensor (panel or indoor unit body) to be handled.

How to Match the Address

Setup to remote controller address

1.When keeping ADR pushed for 4 seconds or more, ADR lamp goes on at the display section of the remote controller and the present address is displayed with flashing.

2. Every pushing ADR , the address is exchanged as ALL 1 2 3 … 6 ALL. Match one of them with the address switch of the indoor unit sensor to be handled.

3.When pushing C L , the address display goes on and is displayed for 5 seconds.

If the address matches with the address switch of the operation part, the buzzer sounds.

Display of

Address

Address

 

Address

 

Address

 

remote

 

 

 

 

 

 

 

 

 

 

 

 

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

 

address

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4–6

 

1–3

Address select

4–6

 

1–3

Address select

4–6

 

1–3

Address select

Address switch

* Address switch

S001

 

 

S001

 

 

S001

 

 

position of

of sensor unit

3

2

1

 

3

2

1

 

3

2

1

 

sensor

can be set any

6

5

4

Address

6

5

4

Address

6

5

4

Address

position.

S002

 

 

S002

 

 

S002

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn the knob to the right side for 1 to 3 while to the left side for 4 to 6 of Address select switch S001.

RBC-AX22CE

Image 80
Contents Split Type Type Indoor unit Outdoor unit DC motor AC motorName 0BT-E ∗∗ 1BT-E ∗∗ 1CT-EContents Installation Manual OutdoorPrecautions for Safety New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply RAV-SP1100, 1400AT-E RAV-SM1100, 1400AT-ERefrigerant Piping Accessory and RefrigerantAccessory and Installation Parts Selection of Installation Before installationInstallation Place Necessary Space for InstallationObstacle at rear side Upper side is free Obstacle at front side Upper side is freeInstallation of Outdoor Unit Standard installationSerial installation at front and rear sides Obstacle also at the upper sideOptional Installation Parts Local Procure Refrigerant Piping ConnectionFor Reference Knockout of Pipe CoverRefrigerant Piping Pipe Forming/End PositioningTightening of Connecting Part Outer dia. of copper pipe Tightening torqueVacuum pump EvacuatingAir Purge Charge port How to open the valveValve size Electrical Work Stripping length power cord and connecting cableHow to wire Self-Diagnosis by LED Indication Final Installation ChecksCheck and Test Operation New tools for R410A Applicable to R22 model Changes Changes in the product and componentsNew tools for R410A Indoor Part name ’ty Shape Standard wired remote Controller Separate sold partsRAV-SM560, 561, 800, 801BT-E RAV-SM1101, 1401BT-E Part name ’ty ShapeConnect the connecting cable correctly Inappropriate grounding may cause electric shock Selection of Installation Place Installation space Selection of installation placeAdvice Secure the space required to installation and servicingInstallation of Indoor Unit Installation procedureDimension External view100 RAV-SM1101, 1401BTInstallation of remote controller Sold separately Mounting of clamp AccessoryHanging down of indoor unit Clamp mounting Removal of air filterRestriction to installation Installation clearanceConcealed duct type Ledge ceiling concealed duct type103 Static pressure characteristics of each modelAIR Ducting Work RAV-SM1101BT Round duct RAV-SM1401BT Round ductConnecting method of the duct 106 Points at installation workGeneral cautions Mounting of remote controller Hanging of indoor unitMounting of filter and canvas for suction port 107Drain Piping Work Piping materialPiping and cautions Thermal-insulating processDrain-up Connection of the drain hoseCheck of water drain After electric piping workPermissible piping length and heat Flaring dia meter size a Unit mmTightening connection Tightening torque of flare pipe connectionsPacked valve handling precautions Open valve fullyGas leak check Use a vacuum pump112 For 801, 1101, 1401AT model801, 1101, 1401 type valve at gas side 113 Remote controller cabling Cabling diagramCabling 114How to execute a test run Case of wired remote controllerTest RUN Before test runTroubleshooting Confirmation of error historyProcedure Description Confirmation and check117 Applicable ControlsAutomatic address Setup of external static pressure When using wireless remote controllerTo incorporate a filter sold separately Short plug position CN112, CN111, CN110 from the left119 Change of lighting time of filter signTo secure better effect of heating INSTALLATION/SERVICING Tools MaintenanceCleaning of Return grille Clean the Return grilles with water121 RAV-SM561, 801CT-E RAV-SM1101, 1401CT-EPart name ’ty Shape Usage Part name122 123 124 Installation spaceAvoid installing in the following places Case of wireless type Height of ceilingHow to use attached installation pattern 126Model name 561CT 801CTInstallation of hanging bolts Knockout hole of power cable take-in portPipe knockout hole Draw-out direction of pipe/cableInstallation of indoor unit Piping/Heat insulating material Drain upCollective piping Adhesive inhibitedConnection of drain hose Thermal insulating process Connection of drain pipeCase of taking pipe from the left side 130Refrigerant Piping and Evacuating Flaring diam. meter size a Unit mm131 Outer diam. of copper pipePiping with outdoor unit Open the valve fullyRefrigerant amount to be added Gas leak check133 Be sure to connect earth wire. Grounding workRemote controller wiring Cable connection 134Wiring diagram 135136 137 138 Case of installation to high ceiling 139Set data 0000 Set data140 Tools Removal of suction grille141 Cleaning of air filter Accessories RBC-EXW21E 144Operation procedure Program button Cancel buttonTimer set button Holiday setting indication mark146 147 148 RBC-AS21E 149Automatic Cool/Heat 150AS21E RBC-AX22CE 151152 Remote ControllerSignal Receiving Part 153 Operation Section Display Section154 155 To Use the Remote Controller Setting to Wall, etc How to Check the AddressHow to Match the Address When a signalis correctlyreceived, Pisoundcan be heard157 StartPhenomenon Cause Measures Phenomenon Cause158 Accessory parts Requirement for installation Multiple remote controllersRemote controller test run setup How to perform cabling of the remote controllerProgram Weekly Timer 160Accessory parts Requirement to install the remote sensorHow to install the remote sensor 161162 Installation of sensor unitAccessory How to perform cabling of sensor units How to set the room temperature sensorHow to set the address switch Slide switchHow to set up filter sold separately of the high ceiling How to handle the remote controller164 Test runTo Personnel Charged in Installation Work and Service Never modify or repair the product Ceiling panel’ty ØM5mm x 40mm ØM4mm x 12mm FlapInstallation of adjust corner cap Installation of suction grilleCheck after installation For wireless remote controllerTCB-DP22CE 168Connect the connecting cable correctly New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply 169Before installation 170Knockout hole Connection of Elbow Piping KITHow to install drain up kit 171Thermal insulating process Tightening connection172 Connection of drain hose at indoor unit sideConnection of drain hose at drain up kit side Piping/Heat insulating material173 Check the draining174 For Installation Professionals 175Use for Indoor Unit Only Combination List of Adapter PartsCase of Concealed Duct RAV-SM **0 BT-E 176Case of 4-way Ceiling Cassette RAV-SM **0 UT-E Address No. setup table SW01 ProcedureSetup from the remote controller at the indoor unit side Setup by the switch on the adapter P.C. board178 To CustomersTCB-KP12CE TCB-KP22CE 179Parts List 180181 Installation of high-efficiency filter Setup of fan when building in the high-efficiency filter182 High-Efficiency FilterDeodorant Filter, Ammonium Filter Setup of fan when building in the filter sold separately183 Page Memo