Balcar R410A Setup of external static pressure, To incorporate a filter sold separately, 118

Page 42

RAV-SM560, 561, 800, 801BT-E

RAV-SM1101, 1401BT-E

11 APPLICABLE CONTROLS

Setup of external static pressure

Select with shifting of the short plug on the indoor unit microcomputer P.C. board.

Matching with the resistance (External static pressure) of the duct to be connected, be sure to set up the tap exchange according to the basic operation procedure

(1 2 3 4 5 6 ).

For the item code in Procedure 3, specify [5d].

For the set data in Procedure 4, select the setup data of static pressure outside of the machine to be set up from the table below.

(Exchange by wired remote controller)

Set data

 

 

External static pressure

 

 

 

 

 

0000

40Pa

 

 

Standard (At shipment)

 

 

 

 

 

0001

70Pa

*1

 

High static pressure 1

 

 

 

 

 

0003

100Pa

*2

 

High static pressure 2

 

 

 

 

 

0006

20Pa

 

 

Low static pressure

 

 

 

 

 

*1: For SM1401BT, set 65Pa.

*2: For SM1401BT, set 90Pa.

To incorporate a filter sold separately

Short plug position

External static

pressure

40Pa

Standard

(At shipment)

70Pa

High static-

pressure 1

100Pa

High static-

pressure 2

20Pa

Low static-

pressure

Filter sold separately

Standard filter (At shipment)

Optical regeneration deodorizing filter

*1

High-performance filter 65 High-performance filter 90 Deodorant filter Ammonia deodorizing filter

——

——

When mounting a filter sold separately, be sure to set up the tap exchange according to the type of filter.

In this case, also follow to the basic operation procedure (1 2 3 4 5 6 ).

For the item code in Procedure 3, specify [5d].

For the set data in Procedure 4, select the setup data of filter to be incorporated from the table below.

Set data

Filter sold separately

 

 

0000

Standard filter (At shipment)

 

 

 

Optical regeneration deodorizing filter

 

 

0001

High-performance filter 65, 90

 

 

 

Deodorant filter Ammonia deodorizing filter

 

 

When using wireless remote controller

To exchange the static pressure, there is a method other than the abovementioned method by wired remote controller, which is to shift the short plug on the indoor microcomputer P.C. board as shown in the following table. Adopt this method in case of using a wireless remote controller, etc.

*However, after exchanging once, be careful to shift the short plug to the standard position (At shipment) in order to return to the standard setup (follow to E2PROM setup) though the setup for high static- pressure 1, high static-pressure 2, or low static- pressure can be arbitrarily performed.

It is necessary to rewrite data from the wired remote controller sold separately in the set data “0000”.

*1 Resistance of high-performance filter 65 and 90, deodorant filter, or ammonia deodorizing filter is equivalent to 30Pa. Therefore, set the resistance (external static pressure) of a duct to be connected to 40Pa.

Short plug position

(CN112, CN111, CN110 from the left)

– 118 –

Image 42
Contents Split Type Name 0BT-E ∗∗ 1BT-E Type Indoor unit Outdoor unitDC motor AC motor ∗∗ 1CT-EContents Installation Manual OutdoorTo Disconnect the Appliance from Main Power Supply Precautions for SafetyNew Refrigerant Air Conditioner Installation RAV-SP1100, 1400AT-E RAV-SM1100, 1400AT-EAccessory and Refrigerant Accessory and Installation PartsRefrigerant Piping Selection of Installation Before installationObstacle at rear side Upper side is free Installation PlaceNecessary Space for Installation Obstacle at front side Upper side is freeSerial installation at front and rear sides Installation of Outdoor UnitStandard installation Obstacle also at the upper sideFor Reference Optional Installation Parts Local ProcureRefrigerant Piping Connection Knockout of Pipe CoverRefrigerant Piping Pipe Forming/End PositioningTightening of Connecting Part Outer dia. of copper pipe Tightening torqueEvacuating Air PurgeVacuum pump How to open the valve Valve sizeCharge port Stripping length power cord and connecting cable How to wireElectrical Work Final Installation Checks Check and Test OperationSelf-Diagnosis by LED Indication Changes in the product and components New tools for R410ANew tools for R410A Applicable to R22 model Changes Indoor RAV-SM560, 561, 800, 801BT-E RAV-SM1101, 1401BT-E Part name ’ty Shape Standard wired remote ControllerSeparate sold parts Part name ’ty ShapeConnect the connecting cable correctly Inappropriate grounding may cause electric shock Advice Selection of Installation PlaceInstallation space Selection of installation place Secure the space required to installation and servicingInstallation of Indoor Unit Installation procedure100 DimensionExternal view RAV-SM1101, 1401BTHanging down of indoor unit Installation of remote controller Sold separatelyMounting of clamp Accessory Clamp mounting Removal of air filterConcealed duct type Restriction to installationInstallation clearance Ledge ceiling concealed duct typeStatic pressure characteristics of each model AIR Ducting Work103 RAV-SM1101BT Round duct RAV-SM1401BT Round ductConnecting method of the duct Points at installation work General cautions106 Mounting of filter and canvas for suction port Mounting of remote controllerHanging of indoor unit 107Piping and cautions Drain Piping WorkPiping material Thermal-insulating processCheck of water drain Drain-upConnection of the drain hose After electric piping workTightening connection Permissible piping length and heatFlaring dia meter size a Unit mm Tightening torque of flare pipe connectionsGas leak check Packed valve handling precautionsOpen valve fully Use a vacuum pumpFor 801, 1101, 1401AT model 801, 1101, 1401 type valve at gas side112 113 Cabling Remote controller cablingCabling diagram 114Test RUN How to execute a test runCase of wired remote controller Before test runProcedure Description TroubleshootingConfirmation of error history Confirmation and checkApplicable Controls Automatic address117 To incorporate a filter sold separately Setup of external static pressureWhen using wireless remote controller Short plug position CN112, CN111, CN110 from the leftChange of lighting time of filter sign To secure better effect of heating119 Cleaning of Return grille INSTALLATION/SERVICING ToolsMaintenance Clean the Return grilles with waterPart name ’ty Shape Usage 121RAV-SM561, 801CT-E RAV-SM1101, 1401CT-E Part name122 123 Installation space Avoid installing in the following places124 Case of wireless type Height of ceilingModel name 561CT How to use attached installation pattern126 801CTPipe knockout hole Installation of hanging boltsKnockout hole of power cable take-in port Draw-out direction of pipe/cableInstallation of indoor unit Collective piping Piping/Heat insulating materialDrain up Adhesive inhibitedCase of taking pipe from the left side Connection of drain hose Thermal insulating processConnection of drain pipe 130131 Refrigerant Piping and EvacuatingFlaring diam. meter size a Unit mm Outer diam. of copper pipeRefrigerant amount to be added Piping with outdoor unitOpen the valve fully Gas leak checkBe sure to connect earth wire. Grounding work Remote controller wiring133 Cable connection 134Wiring diagram 135136 137 138 Set data 0000 Case of installation to high ceiling139 Set data140 Removal of suction grille 141Tools Cleaning of air filter Accessories RBC-EXW21E 144Timer set button Operation procedureProgram button Cancel button Holiday setting indication mark146 147 148 RBC-AS21E 149150 AS21EAutomatic Cool/Heat RBC-AX22CE 151Remote Controller Signal Receiving Part152 153 Operation Section Display Section154 155 How to Match the Address To Use the Remote Controller Setting to Wall, etcHow to Check the Address When a signalis correctlyreceived, Pisoundcan be heardPhenomenon Cause Measures 157Start Phenomenon Cause158 Remote controller test run setup Accessory partsRequirement for installation Multiple remote controllers How to perform cabling of the remote controllerProgram Weekly Timer 160How to install the remote sensor Accessory partsRequirement to install the remote sensor 161Installation of sensor unit Accessory162 How to set the address switch How to perform cabling of sensor unitsHow to set the room temperature sensor Slide switch164 How to set up filter sold separately of the high ceilingHow to handle the remote controller Test runTo Personnel Charged in Installation Work and Service ’ty ØM5mm x 40mm ØM4mm x 12mm Never modify or repair the productCeiling panel FlapCheck after installation Installation of adjust corner capInstallation of suction grille For wireless remote controllerTCB-DP22CE 168To Disconnect the Appliance from Main Power Supply Connect the connecting cable correctlyNew Refrigerant Air Conditioner Installation 169Knockout hole Before installation170 Connection of Elbow Piping KITThermal insulating process How to install drain up kit171 Tightening connectionConnection of drain hose at drain up kit side 172Connection of drain hose at indoor unit side Piping/Heat insulating material173 Check the draining174 Use for Indoor Unit Only For Installation Professionals175 Combination List of Adapter Parts176 Case of 4-way Ceiling Cassette RAV-SM **0 UT-ECase of Concealed Duct RAV-SM **0 BT-E Setup from the remote controller at the indoor unit side Address No. setup table SW01Procedure Setup by the switch on the adapter P.C. board178 To CustomersTCB-KP12CE TCB-KP22CE 179Parts List 180181 182 Installation of high-efficiency filterSetup of fan when building in the high-efficiency filter High-Efficiency FilterSetup of fan when building in the filter sold separately 183Deodorant Filter, Ammonium Filter Page Memo