Balcar R410A service manual Accessory parts, Requirement to install the remote sensor, 161

Page 85

 

 

 

 

 

TCB-TC21LE

 

 

INSTALLATION MANUAL Remote sensor

To Personnel Charged in Installation (Electric) Work and Service

MODEL : TCB-TC21LE

 

 

Accessory parts

 

Fix it with the spacer, but not so strongly. If the remote

 

 

 

 

Part Name

Q’ty

Part Name

Q’ty

sensor does not fit closely to the wall, adjust it by

cutting off the spacer.

 

Remote sensor

 

Spacer

 

 

 

2

3. Connect the remote sensor cable (2 cores) to the

 

1

 

(200mm-cable

 

 

terminal numbers of the indoor unit.

 

 

 

attached)

 

Wire joint

 

(Applying AC 220/230/240V breaks the unit.)

Small screw

 

2

 

 

4. Install the remote sensor body by matching to hooks

 

 

 

M4 x 25

2

 

 

on the rear case and putting into the hooks.

 

Cable clamper

 

 

 

1

 

 

 

 

 

 

 

Wood screw

 

Installation Manual

 

How to perform cabling of the remote sensor

 

2

1

 

 

 

 

 

 

 

 

 

In case of using the remote sensor as a concealed type

Requirement to install the remote sensor

Installation place

• Install the remote sensor at a position with height 1 to

1.5m from the floor, where the average temperature in

the room can be felt.

• Do not install the remote sensor at a place exposed to

the direct sunlight or direct outside air, such as a side of

window, etc.

• Do not install the remote sensor at a place behind

something or rear side of something, where air flow is

poor in the room.

• Connection diagram

 

 

 

Approx. 200mm

Terminal block

A

W

Remote

for remote

 

controller cable

B

B

sensor

in indoor unit

 

 

 

 

W : White

Remote sensor cable

Connecting

Cable from

B : Black

(Procured locally)

section

remote sensor body

Non polarity, 2 core cable is used..

Use 0.5mm² to 2 mm² cable.

Do not install the remote controller near the freezing

 

box or refrigerator because water proof or drop-proof is

 

not applied to this remote controller.

Be sure to set the remote sensor vertically on the wall

 

surface, etc.

How to install the remote sensor

NOTE 1 : Avoid to twist the remote sensor cable with the power supply cable, etc. or to store them in the same metal pipe, otherwise it causes a malfunction.

Attached wire joint (White, 2 pcs.)

Remote sensor cable

 

Cable from

Wire joint, CE-1

remote sensor body

(Nichiatsu)

1)Peel the sheath of the cable to be connected by approx. 14mm.

2)Twist two cables and pressure-connect them using a wire joint.

3)When an exclusive pressure-connecting tool is not used or soldering connection is used, apply insulation process with an insulation tape.

NOTE 2 : Install the remote sensor apart from the generation source of noise.

NOTE 3 : When noise is induced to the power source of the indoor unit, some measures such as mounting the noise filter is necessary.

• In case of using the remote sensor as a concealed type

Rear case Spacer

Remote sensor body

Wall

Small screws

M4 x 25 (2 pcs.)

1.Inserting a minus screwdriver, etc. into the groove at the lower side of the remote sensor body, force open the rear case to remove it.

2.Using the attached M4 screws (2 pcs.), fix the rear case of the remote sensor. Before installation, press to open the screw hole with a screwdriver, etc.

Requirement for using the remote sensor

together with the remote controller

How to install

For the above control, install the remote sensor in the following procedure.

1.Set the remote controller as the master remote controller.

2.Do not change the remote sensor switch in the master remote controller for correct temperature control by remote sensor.

Basic cabling diagram

1.Connect cables without miswiring. (Miswiring breaks the unit.)

2.In a case to operate an indoor unit from the remote sensors and the remote controller.

Remote

 

 

 

 

Remote

 

 

 

 

(Sold

 

 

 

 

controller

 

 

 

 

sensor

 

 

 

 

 

 

 

 

separately)

 

 

 

 

(Master)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller cable

 

 

 

 

 

 

 

 

(Procured locally)

Terminal block for remote controller cable

A B

Indoor unit

Earth

– 161 –

85464359427000 (EN)-

 

Image 85
Contents Split Type DC motor AC motor Type Indoor unit Outdoor unitName 0BT-E ∗∗ 1BT-E ∗∗ 1CT-EContents Outdoor Installation ManualNew Refrigerant Air Conditioner Installation Precautions for SafetyTo Disconnect the Appliance from Main Power Supply RAV-SP1100, 1400AT-E RAV-SM1100, 1400AT-EAccessory and Installation Parts Accessory and RefrigerantRefrigerant Piping Before installation Selection of InstallationNecessary Space for Installation Installation PlaceObstacle at rear side Upper side is free Obstacle at front side Upper side is freeStandard installation Installation of Outdoor UnitSerial installation at front and rear sides Obstacle also at the upper sideRefrigerant Piping Connection Optional Installation Parts Local ProcureFor Reference Knockout of Pipe CoverPipe Forming/End Positioning Refrigerant PipingOuter dia. of copper pipe Tightening torque Tightening of Connecting PartAir Purge EvacuatingVacuum pump Valve size How to open the valveCharge port How to wire Stripping length power cord and connecting cableElectrical Work Check and Test Operation Final Installation ChecksSelf-Diagnosis by LED Indication New tools for R410A Changes in the product and componentsNew tools for R410A Applicable to R22 model Changes Indoor Separate sold parts Part name ’ty Shape Standard wired remote ControllerRAV-SM560, 561, 800, 801BT-E RAV-SM1101, 1401BT-E Part name ’ty ShapeConnect the connecting cable correctly Inappropriate grounding may cause electric shock Installation space Selection of installation place Selection of Installation PlaceAdvice Secure the space required to installation and servicingInstallation procedure Installation of Indoor UnitExternal view Dimension100 RAV-SM1101, 1401BTMounting of clamp Accessory Installation of remote controller Sold separatelyHanging down of indoor unit Clamp mounting Removal of air filterInstallation clearance Restriction to installationConcealed duct type Ledge ceiling concealed duct typeAIR Ducting Work Static pressure characteristics of each model103 RAV-SM1401BT Round duct RAV-SM1101BT Round ductConnecting method of the duct General cautions Points at installation work106 Hanging of indoor unit Mounting of remote controllerMounting of filter and canvas for suction port 107Piping material Drain Piping WorkPiping and cautions Thermal-insulating processConnection of the drain hose Drain-upCheck of water drain After electric piping workFlaring dia meter size a Unit mm Permissible piping length and heatTightening connection Tightening torque of flare pipe connectionsOpen valve fully Packed valve handling precautionsGas leak check Use a vacuum pump801, 1101, 1401 type valve at gas side For 801, 1101, 1401AT model112 113 Cabling diagram Remote controller cablingCabling 114Case of wired remote controller How to execute a test runTest RUN Before test runConfirmation of error history TroubleshootingProcedure Description Confirmation and checkAutomatic address Applicable Controls117 When using wireless remote controller Setup of external static pressureTo incorporate a filter sold separately Short plug position CN112, CN111, CN110 from the leftTo secure better effect of heating Change of lighting time of filter sign119 Maintenance INSTALLATION/SERVICING ToolsCleaning of Return grille Clean the Return grilles with waterRAV-SM561, 801CT-E RAV-SM1101, 1401CT-E 121Part name ’ty Shape Usage Part name122 123 Avoid installing in the following places Installation space124 Height of ceiling Case of wireless type126 How to use attached installation patternModel name 561CT 801CTKnockout hole of power cable take-in port Installation of hanging boltsPipe knockout hole Draw-out direction of pipe/cableInstallation of indoor unit Drain up Piping/Heat insulating materialCollective piping Adhesive inhibitedConnection of drain pipe Connection of drain hose Thermal insulating processCase of taking pipe from the left side 130Flaring diam. meter size a Unit mm Refrigerant Piping and Evacuating131 Outer diam. of copper pipeOpen the valve fully Piping with outdoor unitRefrigerant amount to be added Gas leak checkRemote controller wiring Be sure to connect earth wire. Grounding work133 134 Cable connection135 Wiring diagram136 137 138 139 Case of installation to high ceilingSet data 0000 Set data140 141 Removal of suction grilleTools Cleaning of air filter Accessories 144 RBC-EXW21EProgram button Cancel button Operation procedureTimer set button Holiday setting indication mark146 147 148 149 RBC-AS21EAS21E 150Automatic Cool/Heat 151 RBC-AX22CESignal Receiving Part Remote Controller152 Operation Section Display Section 153154 155 How to Check the Address To Use the Remote Controller Setting to Wall, etcHow to Match the Address When a signalis correctlyreceived, Pisoundcan be heardStart 157Phenomenon Cause Measures Phenomenon Cause158 Requirement for installation Multiple remote controllers Accessory partsRemote controller test run setup How to perform cabling of the remote controller160 Program Weekly TimerRequirement to install the remote sensor Accessory partsHow to install the remote sensor 161Accessory Installation of sensor unit162 How to set the room temperature sensor How to perform cabling of sensor unitsHow to set the address switch Slide switchHow to handle the remote controller How to set up filter sold separately of the high ceiling164 Test runTo Personnel Charged in Installation Work and Service Ceiling panel Never modify or repair the product’ty ØM5mm x 40mm ØM4mm x 12mm FlapInstallation of suction grille Installation of adjust corner capCheck after installation For wireless remote controller168 TCB-DP22CENew Refrigerant Air Conditioner Installation Connect the connecting cable correctlyTo Disconnect the Appliance from Main Power Supply 169170 Before installationKnockout hole Connection of Elbow Piping KIT171 How to install drain up kitThermal insulating process Tightening connectionConnection of drain hose at indoor unit side 172Connection of drain hose at drain up kit side Piping/Heat insulating materialCheck the draining 173174 175 For Installation ProfessionalsUse for Indoor Unit Only Combination List of Adapter PartsCase of 4-way Ceiling Cassette RAV-SM **0 UT-E 176Case of Concealed Duct RAV-SM **0 BT-E Procedure Address No. setup table SW01Setup from the remote controller at the indoor unit side Setup by the switch on the adapter P.C. boardTo Customers 178179 TCB-KP12CE TCB-KP22CE180 Parts List181 Setup of fan when building in the high-efficiency filter Installation of high-efficiency filter182 High-Efficiency Filter183 Setup of fan when building in the filter sold separatelyDeodorant Filter, Ammonium Filter Page Memo