HOW TO OPERATE THE UNIT

Cool/Heat AUTO, Heat, Dry, Cool, Fan

Power supply

HOW TO OPERATE THE TIMER

After setting of the timer, set the remote controller at a position where the signal can reach the sensors (indoor unit body) .

(The signal of the timer operation is sent from the remote controller.)

Set up the timer during display of the operation mode.

Turn on the power of the wireless remote controller 12 hours before starting the operation.

After the power supply has been turned on, the operation of the remote controller is not accepted for approx. 1 minute. It is not a failure.

(The sensor receives the signal once, but the received contents are cleared.)

Use in the following cases

During display

To stop the air conditioner after the previously set time has passed

<Use example>

How to use OFF timer

(Ex.) To stop the unit 30 minutes after

2

3

1

4

1

Push Start/Stop button.

2

Push (Operation Select button)

 

operation to select one of , ,

 

, , and .

3 Push (Fan Mode Select button) to select one of fan speed modes.

When selecting , the fan speed is automatically changed.

(During FAN mode, the air speed is not automatically changed.)

To stop the air conditioner every time after the previously set time has passed

To operate the air conditioner after the previously set time has passed

Timer time

Every pushing , the setup time increases by 0.5 hour (30 minutes).

1When pushing the timer SET once,

and the time flash on the remote controller.

2Push TIME or to set the time to 0.5.

3Push SET and the go on timer.

How to use the repeat timer

(Ex.) To stop the air conditioner every time after 2.5 hours has passed

1 When pushing the timer SET twice,

– 154 –

4 Push either or to select the desired temperature.

• During FAN mode, the temperature cannot be set up.

5 Stop

Push Start/Stop button.

When using the remote controller to stop the unit, the outdoor unit fan may keep operating for a while even if the compressor of the outdoor unit has stopped.

In heating operation, if the room is not comfortably heated with FAN , select FAN or .

Although they are displayed, the function may not be provided according to the used indoor unit. (Fan speed is constant.)

When the unit cannot be stopped by the normal operation

Turn off the power switch or leakage breaker, and then contact the shop which you purchased the unit.

Automatic cool/heat

When all indoor units in the identical refrigerant system are controlled as a group, the cooling/ heating operation is automatically performed with the difference between the setup temperature and the room temperature.

Dry operation

There is no dry function according to the used indoor unit even if DRY is displayed on the display section of the remote controller. (Same to Cooling operation)

When the room temperature approaches the setup temperature, running/stop operations are automatically repeated.

In order not to return humidity to the room as possible, the mode of indoor fan enters LOW mode when the operation has stopped.

The fan speed cannot be adjusted according to the used indoor unit or status of the room temperature.

The DRY mode cannot be used according to the used indoor unit when the outdoor tempera- ture is 15˚C or lower.

The maximum time to be set is 72.0 hours.

Every pushing , the setup time decreases by

0.5 hour (30 minutes).

The minimum time to be set is 0.5 hours.

Timer display

Every pushing SET , the display changes as follows;

ADR

No display

 

,

and the time flash on the

 

remote controller.

 

2

Push TIME

or

to set the time

 

to 2.5.

 

 

 

3

Push

SET and the ,

go on

 

timer.

 

 

 

 

The

works, and the operation stops

 

after 2.5 hours. When pushing

 

(Start/Stop) button again to operate the

 

unit, the operation stops after 2.5 hours.

How to use ON timer

(Ex.) To operate the unit 8 hours after

1When pushing the timer SET three

times, and the timer flash on the remote controller.

2Push TIME or to set the time to 8.0.

3Push SET

The operation mode display disappears,

and then time and the go on.

To stop the timer operation

To stop the timer operation

Push C L button. Then the timer display disappears.

RBC-AX22CE

Image 78
Contents Split Type Name 0BT-E ∗∗ 1BT-E Type Indoor unit Outdoor unitDC motor AC motor ∗∗ 1CT-EContents Installation Manual OutdoorTo Disconnect the Appliance from Main Power Supply Precautions for SafetyNew Refrigerant Air Conditioner Installation RAV-SP1100, 1400AT-E RAV-SM1100, 1400AT-EAccessory and Refrigerant Accessory and Installation PartsRefrigerant Piping Selection of Installation Before installationObstacle at rear side Upper side is free Installation PlaceNecessary Space for Installation Obstacle at front side Upper side is freeSerial installation at front and rear sides Installation of Outdoor UnitStandard installation Obstacle also at the upper sideFor Reference Optional Installation Parts Local ProcureRefrigerant Piping Connection Knockout of Pipe CoverRefrigerant Piping Pipe Forming/End PositioningTightening of Connecting Part Outer dia. of copper pipe Tightening torqueEvacuating Air PurgeVacuum pump How to open the valve Valve sizeCharge port Stripping length power cord and connecting cable How to wireElectrical Work Final Installation Checks Check and Test OperationSelf-Diagnosis by LED Indication Changes in the product and components New tools for R410ANew tools for R410A Applicable to R22 model Changes Indoor RAV-SM560, 561, 800, 801BT-E RAV-SM1101, 1401BT-E Part name ’ty Shape Standard wired remote ControllerSeparate sold parts Part name ’ty ShapeConnect the connecting cable correctly Inappropriate grounding may cause electric shock Advice Selection of Installation PlaceInstallation space Selection of installation place Secure the space required to installation and servicingInstallation of Indoor Unit Installation procedure100 DimensionExternal view RAV-SM1101, 1401BTHanging down of indoor unit Installation of remote controller Sold separatelyMounting of clamp Accessory Clamp mounting Removal of air filterConcealed duct type Restriction to installationInstallation clearance Ledge ceiling concealed duct typeStatic pressure characteristics of each model AIR Ducting Work103 RAV-SM1101BT Round duct RAV-SM1401BT Round ductConnecting method of the duct Points at installation work General cautions106 Mounting of filter and canvas for suction port Mounting of remote controllerHanging of indoor unit 107Piping and cautions Drain Piping WorkPiping material Thermal-insulating processCheck of water drain Drain-upConnection of the drain hose After electric piping workTightening connection Permissible piping length and heatFlaring dia meter size a Unit mm Tightening torque of flare pipe connectionsGas leak check Packed valve handling precautionsOpen valve fully Use a vacuum pumpFor 801, 1101, 1401AT model 801, 1101, 1401 type valve at gas side112 113 Cabling Remote controller cablingCabling diagram 114Test RUN How to execute a test runCase of wired remote controller Before test runProcedure Description TroubleshootingConfirmation of error history Confirmation and checkApplicable Controls Automatic address117 To incorporate a filter sold separately Setup of external static pressureWhen using wireless remote controller Short plug position CN112, CN111, CN110 from the leftChange of lighting time of filter sign To secure better effect of heating119 Cleaning of Return grille INSTALLATION/SERVICING ToolsMaintenance Clean the Return grilles with waterPart name ’ty Shape Usage 121RAV-SM561, 801CT-E RAV-SM1101, 1401CT-E Part name122 123 Installation space Avoid installing in the following places124 Case of wireless type Height of ceilingModel name 561CT How to use attached installation pattern126 801CTPipe knockout hole Installation of hanging boltsKnockout hole of power cable take-in port Draw-out direction of pipe/cableInstallation of indoor unit Collective piping Piping/Heat insulating materialDrain up Adhesive inhibitedCase of taking pipe from the left side Connection of drain hose Thermal insulating processConnection of drain pipe 130131 Refrigerant Piping and EvacuatingFlaring diam. meter size a Unit mm Outer diam. of copper pipeRefrigerant amount to be added Piping with outdoor unitOpen the valve fully Gas leak checkBe sure to connect earth wire. Grounding work Remote controller wiring133 Cable connection 134Wiring diagram 135136 137 138 Set data 0000 Case of installation to high ceiling139 Set data140 Removal of suction grille 141Tools Cleaning of air filter Accessories RBC-EXW21E 144Timer set button Operation procedureProgram button Cancel button Holiday setting indication mark146 147 148 RBC-AS21E 149150 AS21EAutomatic Cool/Heat RBC-AX22CE 151Remote Controller Signal Receiving Part152 153 Operation Section Display Section154 155 How to Match the Address To Use the Remote Controller Setting to Wall, etcHow to Check the Address When a signalis correctlyreceived, Pisoundcan be heardPhenomenon Cause Measures 157Start Phenomenon Cause158 Remote controller test run setup Accessory partsRequirement for installation Multiple remote controllers How to perform cabling of the remote controllerProgram Weekly Timer 160How to install the remote sensor Accessory partsRequirement to install the remote sensor 161Installation of sensor unit Accessory162 How to set the address switch How to perform cabling of sensor unitsHow to set the room temperature sensor Slide switch164 How to set up filter sold separately of the high ceilingHow to handle the remote controller Test runTo Personnel Charged in Installation Work and Service ’ty ØM5mm x 40mm ØM4mm x 12mm Never modify or repair the productCeiling panel FlapCheck after installation Installation of adjust corner capInstallation of suction grille For wireless remote controllerTCB-DP22CE 168To Disconnect the Appliance from Main Power Supply Connect the connecting cable correctlyNew Refrigerant Air Conditioner Installation 169Knockout hole Before installation170 Connection of Elbow Piping KITThermal insulating process How to install drain up kit171 Tightening connectionConnection of drain hose at drain up kit side 172Connection of drain hose at indoor unit side Piping/Heat insulating material173 Check the draining174 Use for Indoor Unit Only For Installation Professionals175 Combination List of Adapter Parts176 Case of 4-way Ceiling Cassette RAV-SM **0 UT-ECase of Concealed Duct RAV-SM **0 BT-E Setup from the remote controller at the indoor unit side Address No. setup table SW01Procedure Setup by the switch on the adapter P.C. board178 To CustomersTCB-KP12CE TCB-KP22CE 179Parts List 180181 182 Installation of high-efficiency filterSetup of fan when building in the high-efficiency filter High-Efficiency FilterSetup of fan when building in the filter sold separately 183Deodorant Filter, Ammonium Filter Page Memo