Chapter 1 Preparing for Installation
Site Requirement Guidelines
Caution Proper grounding is necessary to avoid damage from lightning and power surges. See NEBS Supplemental Unit Bonding and Grounding Guidelines, page
AC Powered Routers
AC power modules operate in the input range of 100 VAC to 240 VAC, 50 to 60 Hz and require a minimum service of:
•15 A for operation in North America and Japan
•10 A for international operation
•13 A for operation in the UK
Each of the AC power inputs requires a separate dedicated branch circuit. For a list of the nominal and acceptable value ranges for source AC power, see Table
Table
Table |
|
| |||
|
|
|
|
|
|
|
|
|
| Power Cord | Reference |
Locale |
| Part Number | Length | Rating | Illustration |
|
|
|
|
|
|
USA |
| 8.2 feet (2.5 m) | 15 A, 250 V | Figure | |
|
|
|
|
|
|
Japan |
| 8.2 feet (2.5 m) | 15 A, 250 V | Figure | |
|
|
|
|
|
|
Australia |
| 8.2 feet (2.5 m) | 10 A, 250 V | Figure | |
|
|
|
|
|
|
Italy |
| 8.2 feet (2.5 m) | 10 A, 250 V | Figure | |
|
|
|
|
|
|
Argentina |
| 8.2 feet (2.5 m) | 10 A, 250 V | Figure | |
|
|
|
|
|
|
Switzerland |
| 8.2 feet (2.5 m) | 10 A, 250 V | Figure | |
|
|
|
|
|
|
UK |
| 8.2 feet (2.5 m) | 13 A, 250 V | Figure | |
|
|
|
|
|
|
China |
| 8.2 feet (2.5 m) | 10 A, 250 V | Figure | |
|
|
|
|
| |
South Africa/India | 8.2 feet (2.5 m) | 10 A, 250 V | Figure | ||
|
|
|
|
|
|
Europe |
| 8.2 feet (2.5 m) | 10 A, 250 V | Figure | |
|
|
|
|
|
|
Israel |
| 8.2 feet (2.5 m) | 10 A, 250 V | Figure | |
|
|
|
|
|
|
AC Power Cord Illustrations
This section contains the AC power cord illustrations, as described in Table
Cisco ASR 9001 and Cisco ASR