Chapter 3 Installing the Cisco ASR 903 Router

Installing the Power Supply

Caution Secure the wires coming in from the terminal block plug so that they cannot be disturbed by casual contact.

Step 7 Ensure that the terminal block plug is fully seated in the terminal block header on the DC power supply panel. The plug has a locking feature. You should hear a snap or click when it is installed properly.

Step 8 Use a tie wrap to secure the wires to the rack, so that the wires are not pulled from the terminal block plug by casual contact. Make sure the tie wrap allows for some slack in the ground wire, as shown in Figure 3-22.

Figure 3-22 Complete DC Terminal Block Plug Insertion and Secure Tie Wrap

RUDY RSP

INPUT

OK

OUTPUT

FAIL

MEM

 

 

 

 

 

CONSOLE

1PPS

1PPS

 

 

 

 

IN

1OMHZ

 

 

 

 

OUT

1OMHZ

S

 

 

 

IN

 

 

 

 

OUT

YNC

 

 

 

 

TOD

ACT

 

 

 

 

BITS

PWR

 

 

 

 

MGMT

 

 

 

 

STAT

 

 

 

 

ENET

24V—60V

28A

 

 

 

 

24V—60V

28A

 

 

2

FAN TEMP

CRIT

MAJ MIN

 

ALARM

255731

1

1

Lead wires secured with a tie wrap

2

DC power supply terminal block plug being inserted into terminal block header.

Step 9 Use a tie wrap to secure the wires to the handle. Leave a service loop on the ground wire between the handle and the connector such that it is the last to receive strain if the wires are pulled.

This completes the procedure for connecting the DC power supply in the Cisco ASR 903 Router.

If you are installing a redundant DC power supply, repeat these steps for the second power source.

Installing Terminal Block Connector on the DC PEM Unit (A900-PWR550-D-E)

Tools

12 AWG to 16 AWG cables

Lugs fork-type or ring-type (Burndy, see Table 6-2)—TP10 -6 or TP10-8F (recommended)

 

 