Power
Heat dissipation | 2132 BTU/hr maximum (redundant, 550 W power |
NOTE: Heat dissipation is calculated | supply) |
| |
using the power supply wattage |
|
rating. |
|
Voltage |
NOTE: This system is also designed to be connected to IT power systems with a phase to phase voltage not exceeding 230 V.
Battery
3 V CR2032 Lithium coin cell |
Expanded Operating Temperature
NOTE: When operating in the expanded temperature range, system performance may be impacted.
NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD and in the System Event Log.
< 10% of annual operating hours | 5 °C to 40 °C at 5% to 85% RH with 26 °C dew |
| point. |
| NOTE: Outside the standard operating |
| temperature (10 °C to 35 °C), the system can |
| operate down to 5 °C or up to 40 °C for a |
| maximum of 10% of its annual operating |
| hours. |
| For temperatures between 35 °C and 40 °C, de- |
| rate maximum allowable dry bulb temperature by |
| 1 °C per 175 m above 950 m (1 °F per 319 ft). |
< 1% of annual operating hours | |
| point. |
| NOTE: Outside the standard operating |
| temperature (10 °C to 35 °C), the system can |
| operate down to |
| maximum of 1% of its annual operating hours. |
| For temperatures between 40 °C and 45 °C, de- |
| rate maximum allowable dry bulb temperature by |
| 1 °C per 125 m above 950 m (1 °F per 228 ft). |
Expanded Operating Temperature Restrictions | • Do not perform a cold startup below 5 °C. |
| • Allow processor performance degrade. |
| • |
| supported. |
| • Non Dell qualified peripheral cards and/or |
| peripheral cards are not supported. |
107