CHAPTER 5: IP ADDRESSING

IP ADDRESSING

To set the SNTP server to be 3.94.210.5 (with a time out of 3 seconds and a number of retries set to 3 times); allowing the synchronization to be ever 5 hours, the following sequence of commands are used

ML1200# sntp

ML1200(sntp)## setsntp server=3.94.210.5 timeout=3 retry=3

SNTP server is added to SNTP server database

ML1200(sntp)## sync hour=5

ML1200(sntp)## sntp enable

SNTP is already enabled.

ML1200(sntp)## exit

ML1200(sntp)#

SNTP parameters can be configured through the EnerVista Secure Web Management software with the Configuration > SNTP menu item. The SNTP menu allows the time zone (hours from GMT) to be defined along with other appropriate parameters on setting the time and synchronizing clocks on network devices.

The edit button allows editing of the SNTP parameters as shown below. Adding or deleting SNTP servers is accomplished by using the add and delete buttons. Clicking the edit button allows the specific SNTP parameter settings to be modified.