DC POWER INPUT

CHAPTER B: DC POWER INPUT

B.5 UL Requirements for DC-powered units

48VDC products shall be installed with a readily accessible disconnect device in the building installation supply circuit to the product.

1.Minimum 18AWG cable for connection to a Centralized DC power source.

2.Minimum 14AWG cable for connection to a earth wiring.

3.Use only with Listed 10 A circuit breaker provided in building installation.

4.“Complies with FDA radiation performance standards, 21 CFR subchapter J.” or equivalent.

5.Fastening torque of the lugs on the terminal block: 9 inch-pound max.

6.To secure a centralized DC Power Source cable , use at least four cable ties to secure the cable to the rack at least 4 inches apart, with the first one located within 6 inches of the terminal block.