pH ARC Sensors Modbus RTU Programmer’s Manual (EPHUM011)

2.4.6 Reading the Internally Measured Output Current

Reg. 4414 / 4542 provides internal parameters of AO1 / AO2:

the setpoint to which the current is regulated in a closed loop control

the electrical current the sensor is measuring to feed the closed loop control

These values are helpful in order to compare against the externally measured electrical current.

Start

Number of

Reg1 / Reg2

Reg3 / Reg4

Modbus

Read

Write

register

registers

 

 

function code

access

access

4414

4

Set point

Internally measured

3, 4

U/A/S

none

 

 

[mA]

[mA]

 

 

 

 

 

AO1

AO1

 

 

 

4542

4

Set point

Internally measured

3, 4

U/A/S

none

 

 

[mA]

[mA]

 

 

 

 

 

AO2

AO2

 

 

 

Figure 2.4.6.1: Definition of register 4414 / 4542.

Command: Internal values AO1

Modbus address: 4414

Length: 4

Type: 3

Read

Parameter:

Set point

Internally measured

 

 

 

 

 

[mA]

[mA]

 

 

 

 

Format:

Float

Float

 

 

 

 

Value:

9.99186

9.99742

 

 

 

 

Figure 2.4.6.2: Example to read the internal values of AO1, depending on the analog interface mode.

624300/01

page 17 / 67

Page 17
Image 17
Hamilton Electronics EPHUM011 manual Reading the Internally Measured Output Current, 99186 99742