pH ARC Sensors Modbus RTU Programmer’s Manual (EPHUM011)

By writing to register 3466, the active physical unit for PA12 can be selected, by choosing one of the physical units that are defined in register 3464. The value of the parameter can be set as well.

Command: Moving average

 

Modbus address: 3466

Length: 4

Type: 16

Write

Parameter:

Unit

Value

 

 

 

 

Format:

Hex

Decimal

 

 

 

 

Value:

0x01

7

 

 

 

 

 

Figure 2.6.3.2.4: Example to set the physical unit of PA12 to “none”(0x01) and the value of the moving average R to 7.

2.6.3.3Reading all Values for PA12

By reading register 3466, the active physical unit of measurement, the selected value, and the min and max values can be read.

Start

Number of

Reg1 /

 

Reg3 /

Reg5 /

 

Reg7 /

Modbus

Read

Write

register

registers

Reg2

 

Reg4

Reg6

 

Reg8

function

access

access

 

 

 

 

 

 

 

 

 

 

 

code

 

 

 

 

3466

8

 

Physical

 

Current

Min

 

Max

3, 4

 

 

U/A/S

none

 

 

 

unit

 

value

value

 

value

 

 

 

 

 

 

Figure 2.6.3.3.1: Definition of register 3466.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Command: Moving average

 

 

Modbus address: 3466

Length: 8

 

Type: 3

Read

 

Parameter:

Unit

 

Value

 

Min value

 

 

Max value

 

 

Format:

 

Hex

 

Decimal

 

Decimal

 

 

Decimal

 

 

Value:

 

0x01

 

7

 

 

1

 

 

 

 

16

 

 

 

Figure 2.6.3.3.2: Example to read PA12. The physical unit is 0x01 (“none”), the value is 7, and the limits are 1 to 16.