INSTALLATION

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

TABLE A.1 – TOTAL COMBINED LENGTH OF ELECTRODE AND WORK CABLES

Cable

Cable Size for

250 Amps

Length

100% Duty Cycle

 

0-100 ft. (0-30 meters)

1 AWG

100-200 ft. (30-46 meters)

1 AWG

150-200 ft. (46-61 meters)

1/0 AWG

CABLE INSTALLATION

Install the welding cables to your Ranger 250 as fol- lows.

1.The engine must be OFF to install welding cables.

2.Remove the flanged nuts from the output terminals.

3.Connect the electrode holder and work cables to the weld output terminals. The terminals are iden- tified on the case front.

4.Tighten the flanged nuts securely.

5.Be certain that the metal piece you are welding (the “work”) is properly connected to the work clamp and cable.

6.Check and tighten the connections periodically.

CAUTION

Loose connections will cause the output terminals to overheat. The terminals may eventually melt.

Do not cross the welding cables at the output termi- nal connection. Keep the cables isolated and sepa- rate from one another.

AUXILIARY POWER RECEPTACLES

The auxiliary power of the Ranger 250 consists of two 20 amp-120 VAC (5-20R) duplex receptacles and one 50 amp 120/240 VAC (14-50R) receptacle. The 240 VAC receptacle can be split for single-phase 120 VAC operation.

The auxiliary power capacity is 8,000 watts of 60 Hz, single-phase power. The auxiliary power capacity rat- ing in watts is equivalent to volt-amperes at unity power factor. The maximum permissible current of the 240 VAC output is 33 amps. The 240 VAC output can be split to provide two separate 120 VAC outputs with a maximum permissible current of 33 amps per output to

two separate 120 VAC branch circuits (these circuits cannot be paralleled). Output voltage is within ±10% at all loads up to rated capacity.

The 120 VAC auxiliary power receptacles should only be used with three-wire grounded type plugs or approved double insulated tools with two-wire plugs. The current rating of any plug used with the system must be at least equal to the current capacity of the associated receptacle.

NOTE: The 240 VAC receptacle has two 120 VAC cir- cuits, but they are of opposite polarities and cannot be paralleled.

STANDBY POWER CONNECTIONS

The Ranger 250 is suitable for temporary, standby or emergency power using the engine manufacturer’s rec- ommended maintenance schedule.

The Ranger 250 can be permanently installed as a standby power unit for 240 VAC, three-wire, single- phase, 35 amp service. Connections must be made by a licensed electrician who can determine how the 120/240 VAC power can be adapted to the particular installation and comply with all applicable electrical codes. The following information can be used as a guide by the electrician for most applications. Refer to the connection diagram in Figure A-2.

1.Install the double-pole, double-throw switch between the power company meter and the premises disconnect. Switch rating must be the same or greater than the customer’s premises dis- connect and service over current protection.

2.Take necessary steps to assure load is limited to the capacity of the Ranger 250 by installing a 35 amp, 240 VAC double-pole circuit breaker.

Maximum rated load for each leg of the 240 VAC auxiliary is 33 amperes. Loading above the rated output will reduce output voltage below the allow- able ±10% of rated voltage, which may damage appliances or other motor-driven equipment and may result in overheating of the Ranger 250 engine and/or alternator windings.

3.Install a 50 amp, 120/240 VAC plug (NEMA Type 14-50) to the double-pole circuit breaker using No. 6, 4-conductor cable of the desired length. (The 50 amp, 120/240 VAC plug is available in the optional K802R plug kit or as part number T12153-9.)

4.Plug this cable into the 50 amp, 120/240 VAC receptacle on the Ranger 250 case front.