STATOR VOLTAGE TESTS (continued)
FIGURE F.11 – LOCATION OF LEADS #7 AND #9 AT FIELD DIODE RECTIFIER BRIDGE
Return to Section TOC
Return to Section TOC
Return to Section TOC
Return to Master TOC
Return to Master TOC
Return to Master TOC
201
201A7
_ | AC |
|
200A
200B
+
9AC
7
201
201A
9
FIELD
RECTIFIER
BRIDGE
RETAINING
TAB
CABLE
CAPACITOR
To test the field winding:
1.Connect the volt/ohmmeter probes to leads #7 and #9 where they connect to the field diode rectifier bridge. See Figure F.11.
2.Start the engine and run it at high idle (3700 RPM).
3.Check the AC voltage reading. It should be between 40 and 50 VAC.
If any one or more of the readings are missing or not within specifications, check for loose or bro-
200A
200B
ken wires between the test points and the stator windings. See the Wiring Diagram. Make sure that the windings are NOT grounded internally to the stator iron. If the leads are intact, then the stator may be faulty. Replace the stator.
If the voltage readings are within specifications, then the windings are good and functioning prop- erly.
4.If finished testing, perform the Case Cover Replacement procedure.