4 SETTINGS AND PROCEDURES PRIOR TO OPERATION
4.6 Settings with the Utility Package (GX
The settings defined with GX
The following concerns the data set from GX
1)Data set in the Q series C24 for the use of specific functions
2)Data set in the PLC CPU to communicate information between the Q series C24 and the PLC CPU of the mounting station.
This section explains the "Auto refresh settings" of the data mentioned in 2) above.
[Setting purpose]
The auto refresh settings are defined to automatically store the error and status information stored in the buffer memory of the Q series C24 in devices designated by the PLC CPU.
By this setting, the users can see the module error and status information without accessing the Q series C24.
[Setup procedure]
[GX Developer] [Tools] [Intelligent function utility] [Start] "Intelligent function module parameter setting module select" Auto refresh .
For display screen, see Section 8.3.
[Setting screen]
4 - 22 | 4 - 22 |