4 SETTINGS AND PROCEDURES PRIOR TO OPERATION

MELSEC-Q

(d)Station number setting (switch 5 (common for both CH1 and CH2 sides))

This setting is for communication using the MC protocol.

When several the Q series C24s are connected on the same line with multidrop connection, set the station number designated in the data items of the transmission frame in each external device to 0 to 31 (0H to 1FH). This number designates which external device is to be communicated

with the Q series C24.

Set the station number to 0 when the system configuration of the external device and the PLC CPU is 1:1.

Q series C24

External device

Station 0

Station 1

Station 2

Station 31

POINT

If the communication of data with external device is to be started, check the specifications of the functions to be used and then make the settings and connect the cables.

Make the following switch settings from the GX Developer if there is to be no communication (if the cables are not to be connected) at the interface.

• Communication protocol setting: Set between 0H and 7H.

• Transmission setting, communication rate setting: Set all to OFF.

(2)The setting and data flow in linked operation

(a)Set the related switches as follows when two Q series C24 interfaces are in linked operation.

Switch number

Settings

Setting value

 

 

 

Operation setting

b0 = OFF

Switch 1

 

Transmission setting

Data bit setting

Set each switch on both CH1 and CH2 sides to

CH1 side

 

:

the same specification.

 

 

 

 

Communication rate setting

 

Match the external device.

Switch 2

 

Communication protocol setting

8

 

 

 

Operation setting

b0 = ON

Switch 3

 

Transmission setting

Data bit setting

Set each switch on both CH1 and CH2 sides to

CH2 side

 

:

the same specification.

 

 

 

 

Communication rate setting

 

Match the external device.

Switch 4

 

Communication protocol setting

0 to 7

Switch 5

Station number setting

 

Set according to (d) of (1)

4 - 17

4 - 17