10TROUBLESHOOTING

(3)Checking by GX Configurator-SC

Display the "Monitor/test others" screen.

MELSEC-Q

For details on display screens, see Section 8.6.9 of the User's Manual (Basic).

(4) Description of LED ON status and communications error status

 

Status

 

Description when ON

Description when OFF

 

 

Related protocol

 

 

Initial

 

 

Non

 

No.

signal

Description

(when LED is turned on

(when LED is turned off

state

MC

 

procedure

Bidirection-

 

name

 

(1))

(0))

 

 

 

protocol

al protocol

 

 

 

 

 

 

 

 

 

1

SD WAIT

Transmission wait status

Waiting for data

Data transmission start

OFF

 

 

 

 

transmission

 

 

 

 

 

 

 

Overrun or framing

 

OFF

 

 

 

 

 

 

 

error occurred.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

SIO

SIO error status

OS area is full.

Normal

 

 

 

 

 

 

 

 

Received data was

 

OFF

 

 

 

 

 

 

deleted.

 

 

 

 

 

 

3

PRO.

Communication protocol

Error occurred.

Normal

OFF

 

 

 

 

error status

 

 

 

 

 

 

 

4

P/S

Status of parity error or

Error occurred.

Normal

OFF

 

 

 

 

sum check error

 

 

 

 

 

 

 

 

 

 

 

 

 

5

C/N

Access status with the

( 1)

Normal

OFF

 

 

 

 

PLC CPU

 

 

 

 

 

 

 

 

 

 

 

 

 

6

NAK

Abnormal completion

Abnormal completion

Normal completion

OFF

 

 

 

 

status

transmission

transmission

 

 

 

 

 

 

 

 

 

 

 

7

ACK.

Normal completion

Normal completion

Abnormal completion

OFF

 

 

status

transmission

transmission

 

 

 

 

 

 

 

 

 

 

 

 

 

Neutral status

 

 

 

 

 

 

 

8

NEU.

Waiting to receive

Neutral

Command reception

( 2)

 

 

 

 

 

 

command

 

 

 

 

 

 

 

9

CH2. ERR

Error occurrence status

Switch setting error

 

OFF

 

 

 

 

on CH2 side

Mode switching error

 

 

 

 

 

 

 

Error occurrence status

Transmission error

Normal

 

 

 

 

 

10

CH1. ERR

Reception error

 

OFF

 

 

 

 

 

 

on CH1 side

On-demand error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 C/N turns on in the following cases:

An external device issued a data read request to the PLC CPU when write during RUN is set to prohibit in the switch settings by GX Developer (see Section 4.5.2).

For functions that cannot be used when write during RUN is set to prohibit, see the explanation section in each command list of the Reference Manual.

When an error has occurred during access between the Q series C24 and the

PLC CPU.

2 NEU. is valid when a target interface is set to use the MC protocol.

When the target interface is set to other than the MC protocol, the status of NEU. is off.

10 - 4