3 SPECIFICATIONS
3.3.2
The following shows the
(1)Use a 1200 m (3937 ft.), or shorter, cable that satisfies the following specification for the
(2)Make the total distance within 1200 m (3937 ft.) when two or more device are connected in a 1:n or m:n configuration.
(3)The
Item |
|
| Description |
Cable type |
|
| Shielded cable |
Number of pairs |
|
| 3P |
Conductor resistance (20 C° ) |
|
| 88.0 /km or less |
Insulation resistance |
|
| 10000 M - km or more |
Dielectric strength |
|
| 500 V DC, 1 minute |
Electrostatic capacitance (1 kHz) |
|
| 60nF/km or less on average |
Characteristic impedance (100 kHz) |
|
| 110 ± 10 |
(Recommended cable) | ..... (MITSUBISHI CABLE INDUSTRIES, Ltd.) | ||
SPEV | 3P | ||
SPEV | .............. (MITSUBISHI CABLE INDUSTRIES, Ltd.) | ||
SPEV | 3P and SPEV |
characteristics, but different external diameter and internal wire colors.
3 - 7 | 3 - 7 |