10 TROUBLESHOOTING
10.3.1 Troubleshooting when "RUN" LED is turned OFF
Symptom |
| Cause |
|
| Corrective action | MC |
| • | A transmission setting | • | Set the switch by GX Developer correctly and |
| |
|
| switch is set to an |
| after writing to the CPU reset the CPU. |
| |
|
| unusable position. |
|
|
|
|
|
|
| • Remove the cause of the CPU error and reset |
| ||
|
|
|
| the CPU. |
| |
| • PLC CPU error. |
| Note |
|
| |
|
| • During the Q series C24 and external device |
| |||
|
|
|
|
| ||
|
|
|
| loopback test, the minimum parameters file |
| |
|
|
|
| must be written to the CPU beforehand. |
| |
• The Q series C24 |
|
| • | Calculate the 5 V current drain of each installed |
| |
|
|
| module. If the current capacity is insufficient, |
| ||
"RUN" LED turned off. |
|
|
|
| ||
|
|
| check power module selection. |
| ||
| • Power module 5 V |
|
| |||
|
| Note |
|
| ||
|
| current capacity is |
|
|
| |
|
|
| • Whether or not the current capacity is |
| ||
|
| insufficient. |
|
| ||
|
|
| insufficient can be checked by disconnecting |
| ||
|
|
|
|
| ||
|
|
|
| the expansion base and installing only the Q |
| |
|
|
|
| series C24 to the basic base. |
| |
| • | Extraneous noise | • | Check if the shield wire is |
| |
|
| caused the Q series | • When ground is used with other devices, |
| ||
|
| C24 to abnormal |
| ground the Q series C24 independently. |
| |
|
| operation. |
|
|
|
|
|
|
|
|
|
|
|