APPENDIX

MELSEC-Q

Appendix 9.12 When changing the communication protocol and transmission setting

This section provides a program example that changes the communication protocol and transmission setting using the REMFR/REMTO instructions and I/O signals. (When the module is used on a MELSECNET/H remote I/O station, the station No. cannot be changed because the UINI instruction is unavailable.)

For changing the communication protocol and transmission setting, refer to Chapter 15 of the User's Manual (Application).

(1) Program conditions

When the change command (X1031) turns on, the communication protocol and transmission setting are changed.

 

 

(a) Devices used by user

 

 

 

 

 

 

• Change command ..................................................................

 

 

 

X1031

 

 

• Changing flag

..........................................................................

 

 

 

M300

 

 

• Change completion flag..........................................................

 

 

 

M301

 

 

• CH1 change command pulse signal ......................................

M10

 

 

• CH1 change command...........................................................

 

 

 

M11

 

 

• CH1 mode switching completion............................................

M12

 

 

• CH1 receive processing..........................................................

 

 

 

M13

 

 

• CH1 send processing .............................................................

 

 

 

M14

 

 

• CH2 change command pulse signal ......................................

M20

 

 

• CH2 change command...........................................................

 

 

 

M21

 

 

• CH2 mode switching completion............................................

M22

 

 

• CH2 receive processing..........................................................

 

 

 

M23

 

 

• CH2 send processing .............................................................

 

 

 

M24

 

 

• REMFR/REMTO instruction completion device.....................

M100 to 107

 

 

• REMFR/REMTO instruction abnormal completion flag.........

M200 to 205

 

 

• Switching mode No. designation............................................

D0, D10

 

 

Transmission specifications after switching designation.......

D1, D11

 

 

Switch setting error and mode switching error status............

D2, D12

 

 

(b) Buffer memory settings used in this example

 

 

 

 

 

 

 

 

 

 

 

 

Address, Decimal

 

Bit

 

 

 

 

 

(Hexadecimal)

 

 

Description

 

Set value

 

 

 

 

 

CH1

CH2

Position

 

Specified

 

 

 

 

 

 

 

 

 

value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

114 (90H)

304 (130H)

 

Switching mode No. designation

 

MC protocol

0001H

 

 

(Format 1)

 

 

 

 

 

 

 

 

 

 

 

b0

 

OFF

 

Operation

 

Independent

 

 

 

 

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

b1

 

OFF

 

Data bit

 

7 bits

 

 

 

b2

 

OFF

 

Parity bit

 

No

 

 

 

b3

 

OFF

 

Even/odd parity

 

Odd

 

 

 

b4

 

ON

 

Stop bit

 

2 bits

 

 

 

b5

 

ON

 

Sum check

 

Yes

 

 

 

 

Transmission

code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Write during

 

 

 

145 (91 H)

305 (131H)

b6

 

OFF

specifications

 

Prohibited

85B0H

 

RUN

 

 

 

 

after switching

 

 

 

 

b7

 

ON

designation

Setting

 

Allowed

 

 

 

 

modifications

 

 

 

 

 

 

 

 

 

 

 

 

 

b8 to b11

 

 

Communication

 

9600bps

 

 

 

 

 

rate setting

 

 

 

 

 

 

 

 

 

 

 

 

 

B12 to 14

 

All OFF

 

For system

 

 

 

 

 

 

 

 

Transmission

 

Make setting

 

 

 

B15

 

ON

 

specifications

 

 

 

 

 

 

 

as set in this

 

 

 

 

 

after switching

 

 

 

 

 

 

 

 

 

area.

 

 

 

 

 

 

 

designation

 

 

 

 

 

 

 

 

 

 

 

515

(203H)

 

Switch setting error and mode switching error status