APPENDIX

 

 

 

 

 

 

 

 

 

 

MELSEC-Q

 

 

 

 

 

 

 

 

 

 

 

 

(b) Input instruction

 

 

 

 

 

 

 

 

Tp = Sr + 0.09 Dr + T2

 

 

 

 

 

 

 

 

Tp (

1) : Time from the start of execution of the Input instruction to the

 

 

 

End processing of the sequence scan at the completion of

 

 

 

the Input instruction execution (ms)

 

 

 

 

 

Sr

 

: Scan time

 

 

 

 

 

 

 

 

Dr

 

: Number of bytes of reception data

 

 

 

 

 

T2

 

: QJ71C24N (-R2/R4)

T2 = 7.0

 

 

 

 

 

 

 

QJ71C24 (-R2)

T2 = 14.91

 

 

 

 

1

This stands for the time range of processing (Tp).

 

 

Start of the Input

 

 

 

Start of the End processing of

 

 

instruction execution

Tp

the scan at the completion of

 

 

 

 

 

 

 

 

the Input instruction execution

 

 

 

 

 

 

 

 

 

 

 

Step 0

END

 

 

 

 

 

 

 

 

 

 

Sequence program

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reception data read

 

 

 

 

 

 

 

 

 

 

 

 

 

request (X3)

 

 

 

 

 

 

 

 

 

 

 

 

 

Input instruction

 

 

 

 

 

 

INPUT

1 scan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input instruction complete device

(DX3)

Q series C24 side

Reception data External device side

2ms (2)

[Calculation example]

Estimate the time required to process the Input instruction when receiving 100 bytes of data using the non procedure protocol with the QJ71C24N. (Unit: ms)

• Scan time : 10 ms

10 + 0.09 100 + 7.0 26.00 (ms)

2 When only using CH1 of the Q series C24 and when processing only 30 bytes of data received, the time until the reception data read request (X3) comes on is displayed after the Q series C24 receives data from the network.

App. - 15

App. - 15